M-Series SEZ-KA Engineering Manual

SEZ Ducted Heat Pump Systems (August 2014)
SEZ-25
© 2014 Mitsubishi Electric US, Inc.
Due to continuing improvement, above specication may be subject to change without notice.
3-7. CAPACITY CORRECTION TABLE BY TEMPERATURE
(1) Cooling Capacity
Model
Indoor air Outdoor intake air DB temperature (˚F)
IWB (˚ F)
75 85 95 105 115
TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC
SUZ-KA09NA.TH
71 9.9 6.6 0.60 9.3 6.2 0.65 8.7 5.8 0.70 8.1 5.4 0.74 7.5 5.0 0.77
67 9.4 7.5 0.56 8.7 7.0 0.62 8.1 6.5 0.67 7.5 6.0 0.71 6.9 5.5 0.74
63 8.8 8.2 0.54 8.2 7.6 0.59 7.6 7.1 0.64 6.9 6.5 0.68 6.3 5.9 0.71
SUZ-KA12NA.TH
71 14.1 8.8 0.82 13.2 8.3 0.90 12.4 7.7 0.97 11.5 7.2 1.02 10.6 6.6 1.06
67 13.3 10.1 0.77 12.4 9.4 0.85 11.5 8.7 0.92 10.7 8.1 0.98 9.8 7.5 1.02
63 12.5 11.2 0.74 11.6 10.4 0.81 10.8 9.7 0.88 9.8 8.8 0.94 9.0 8.0 0.98
SUZ-KA15NA.TH
71 17.3 11.5 1.04 16.1 10.8 1.14 15.2 10.1 1.23 14.1 9.4 1.29 13.0 8.6 1.35
67 16.4 13.1 0.98 15.2 12.2 1.08 14.1 11.3 1.17 13.1 10.5 1.24 12.1 9.6 1.30
63 15.4 14.3 0.94 14.2 13.3 1.04 13.3 12.4 1.12 12.1 11.3 1.19 11.0 10.3 1.24
SUZ-KA18NA.TH
71 21.1 13.8 1.23 19.7 12.9 1.35 18.5 12.1 1.45 17.2 11.3 1.52 15.8 10.4 1.59
67 20.0 15.8 1.16 18.6 14.7 1.28 17.2 13.6 1.38 16.0 12.6 1.46 14.7 11.6 1.53
63 18.7 17.3 1.10 17.4 16.0 1.22 16.2 14.9 1.32 14.7 13.6 1.41 13.4 12.4 1.46
NOTE
: 1. IWB: Intake air wet-bulb temperature
TC: Total Capacity (×10
3
Btu/h)
SHC: Sensible Heat Capacity (×10
3
Btu/h)
TPC: Total Power Consumption (kW)
2. SHC is based on 80˚F of indoor Intake air DB temperature.
SUZ-KA09NA.TH SUZ-KA12NA.TH SUZ-KA15NA.TH
SUZ-KA15NA.TH
SUZ-KA18NA.TH