M-Series SEZ-KA Engineering Manual

SEZ-28
SEZ Ducted Heat Pump Systems (August 2014)
Due to continuing improvement, above specication may be subject to change without notice.
© 2014 Mitsubishi Electric US, Inc.
3-7. CAPACITY CORRECTION TABLE BY TEMPERATURE
Outdoor W.B. [° F]
-13 -4 5 14 23 32 41 50
Indoor
EAT DB
SUZ-KA09NA.TH 60 0.56 0.66 0.80 0.95 1.07 1.07
SUZ-KA12NA.TH 60 0.56 0.66 0.80 0.95 1.07 1.07
SUZ-KA15NA.TH 60 0.56 0.66 0.80 0.95 1.07 1.07
SUZ-KA18NA.TH 60 0.56 0.66 0.80 0.95 1.07 1.07
Interpolated Data Between 60 and 65 Indoor EAT DB data sets
SUZ-KA09NA.TH 63 0.55 0.65 0.79 0.93 1.05 1.05
SUZ-KA12NA.TH 63 0.55 0.65 0.79 0.93 1.05 1.05
SUZ-KA15NA.TH 63 0.55 0.65 0.79 0.93 1.05 1.05
SUZ-KA18NA.TH 63 0.55 0.65 0.79 0.93 1.05 1.05
SUZ-KA09NA.TH 65 0.54 0.64 0.78 0.92 1.03 1.03
SUZ-KA12NA.TH 65 0.54 0.64 0.78 0.92 1.03 1.03
SUZ-KA15NA.TH 65 0.54 0.64 0.78 0.92 1.03 1.03
SUZ-KA18NA.TH 65 0.54 0.64 0.78 0.92 1.03 1.03
SUZ-KA09NA.TH 70 0.52 0.62 0.75 0.885 1.00 1.00
SUZ-KA12NA.TH 70 0.52 0.62 0.75 0.885 1.00 1.00
SUZ-KA15NA.TH 70 0.52 0.62 0.75 0.885 1.00 1.00
SUZ-KA18NA.TH 70 0.52 0.62 0.75 0.885 1.00 1.00
SUZ-KA09NA.TH 75 0.50 0.60 0.72 0.85 0.96 0.96
SUZ-KA12NA.TH 75 0.50 0.60 0.72 0.85 0.96 0.96
SUZ-KA15NA.TH 75 0.50 0.60 0.72 0.85 0.96 0.96
SUZ-KA18NA.TH 75 0.50 0.60 0.72 0.85 0.96 0.96
SUZ-KA09NA.TH 80 0.48 0.58 0.70 0.82 0.93 0.93
SUZ-KA12NA.TH 80 0.48 0.58 0.70 0.82 0.93 0.93
SUZ-KA15NA.TH 80 0.48 0.58 0.70 0.82 0.93 0.93
SUZ-KA18NA.TH 80 0.48 0.58 0.70 0.82 0.93 0.93
(5) M-Series Heating Correction