M-Series SEZ-KA Engineering Manual

SEZ Ducted Heat Pump Systems (August 2014)
SEZ-31
© 2014 Mitsubishi Electric US, Inc.
Due to continuing improvement, above specication may be subject to change without notice.
3-9. CAPACITY CORRECTION TABLE BY REFRIGERANT PIPING LENGTH
Refrigerant piping length (ft)
25(std) 40 65 100
1.000 0.954 0.878 0.771
(3) M-Series Piping Correction Cooling
Refrigerant piping length (ft)
25(std) 40 65 100
1.000 0.989 0.972 0.955
(4) M-Series Piping Correction Heating