SEZ-42
SEZ Ducted Heat Pump Systems (August 2014)
Due to continuing improvement, above specication may be subject to change without notice.
© 2014 Mitsubishi Electric US, Inc.
Outdoor unit
Rating Guaranteed Voltage
Min. 187V
Max. 253V
208V
208/230V
60Hz
1 Phase
230V
Mode
Intake Air Temperature Indoor Outdoor
Condition DB (°F) WB (°F) DB (°F) WB (°F)
Cooling
Standard temperature 80 67 95 —
Maximum temperature 90 73 115 —
Minimum temperature 67 57 14 —
Maximum humidity 78% —
Heating
Standard temperature 70 60 47 43
Maximum temperature 80 67 75 65
Minimum temperature 70 60 6 5
3-13. STANDARD OPERATION RANGE