MXZ-SM42NAMHZ Submittal

SPECIFICATIONS: MXZ-SM42NAMHZ-U1
test
Outdoor unit operating temperature
range
Cooling Intake Air Temp (Maximum / Minimum) °FDB 115 / 23
Cooling Thermal Lock-out / Re-start Temperatures °FDB N/A / N/A
Heating Intake Air Temp (Maximum / Minimum) °FWB 59 / -13
Heating Thermal Lock-out / Re-start Temperatures °FDB -24 / -14
Refrigerant
Type R410A
Charge Lbs, oz 10, 9.0
Indoor unit connection
Maximum Number of Connected IDU with Branch Box 5 (4)
*A
Maximum Number of Connected IDU without Branch Box 12
Minimum Number of Connected IDU with Branch Box 2
Minimum Number of Connected IDU without Branch Box 1
Minimum Connected Capacity with Branch Box BTU/H 12,000
Maximum Connected Capacity BTU/H 54,000
Piping
Liquid Pipe Size O.D. (Flared) In.[mm] 3/8 [9.52]
Gas Pipe Size O.D. (Flared) In.[mm] 5/8 [15.88]
Total Piping Length when using Branch Box Ft. [m] 492 [150]
Total Piping Length without Branch Box Ft. [m] 984 [ 300]
Maximum Height Difference
*B
, ODU above IDU Ft. [m] 164 [50]
Maximum Height Difference
*B
, ODU below IDU Ft. [m] 131 [40]
Maximum Height Difference
*B
, between branch boxes Ft. [m] 49 [ 15]
Maximum Height Difference
*B
, between branch boxes and IDU Ft. [m] 49 [15]
Maximum Height Difference between IDU and IDU without branch
box
Ft. [m] 49 [ 15]
Max. Piping Length between ODU and Branch Box Ft. [m] 180 [55]
Farthest Piping Length from ODU to IDU with Branch Box Ft. [m] 262 [80]
Farthest Piping Length from ODU to IDU without Branch Box Ft. [m] 492 [ 150]
Farthest Piping Length after Branch Box Ft. [m] 82 [25]
Total Piping Length between Branch Boxes and IDU Ft. [m] 311 [95]
Maximum Number of Bends for IDU 15
NOTES:
AHRI Rated Conditions
1
Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB
(Rated data is determined at a xed compressor speed)
2
Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB
3
Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB
Conditions
4
Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB
*
Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
*A
when 1 or more PLA-A·EA7 connected
*B
Branch box should be placed within the level between the outdoor unit and indoor units
*C
5°F DB - 115°F DB when optional wind bafes are installed
For actual capacity performance based on indoor unit type and number of indoor units connected, please refer to MXZ Operational Performance.
Although the maximum connectable capacity is 130%, the outdoor unit cannot provide more than 100% of the rated capacity. Please utilize this over capacity capability for load shedding or applications
where it is known that all connected units will NOT be operating at the same time.
Specications are subject to change without notice. © 2022 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.