MXZ-SM48NAMHZ Service Manual

126
OCH789
8-10. OUTDOOR UNIT FUNCTIONS
SW: setting
0....OFF
1....ON
No.
SW1
setting
Display mode
Display on the LED1, 2 (display data)
Notes
12345678 1 2 3 4 5 6 7 8
0 00000000
Relay output display Compressor operation
52C 21S4 SV1 (SV2) Always lighting ON: light on OFF: light o󰀨
Check display 0000–9999 (Alternating display of addresses and check code)
•When abnormality occurs, check display.
1 10000000
Indoor unit check status
No.1 unit check No.2 unit check No.3 unit check No.4 unit check No.5 unit check No.6 unit check No.7 unit check No.8 unit check
Light on at time of abnormality
2 01000000 Protection input
High pressure
abnormality
Superheat due
to low discharge
temperature
Compressor
shell temperature
abnormality
TH4 abnormality TH3 abnormality
Outdoor fan rotation
frequency abnormality
TH7 abnormality TH8 abnormality
Display detected
microprocessor protection or
abnormality
3 11000000 Protection input
Heat sink
overheating
Compressor
over current
interception
Voltage
abnormality
Insu󰀩cient refrigerant
amount abnormality
Current sensor/
primary current
abnormality
63LS
abnormality
63HS
abnormality
start over current
interception abnormality
delay
4 00100000 Protection input
Abnormality in the
number of indoor units
Address double
setting abnormality
Indoor unit
capacity error
Over capacity
Indoor unit
address error
Outdoor unit
address error
Current sensor
open/short
serial
communication
abnormality
(outdoor unit)
5 10100000
Abnormality delay display 1
High pressure
abnormality delay
Superheat due
to low discharge
temperature delay
Compressor
shell temperature
abnormality delay
TH4 abnormality
delay
TH3 abnormality
delay
Outdoor fan rotation
frequency abnormality delay
TH7 abnormality
delay
TH8 abnormality
delay
Display all abnormalities
remaining in abnormality
delay
6 01100000
Abnormality delay display 2
Heat sink
overheating delay
Compressor
over current
interception delay
Voltage
abnormality delay
Insu󰀩cient refrigerant
amount abnormality delay
Current sensor/
primary current
abnormality delay
63LS
abnormality
delay
63HS abnormality delay
start over current interception
abnormality delay
7 11100000
Abnormality delay display 3
63LS abnormality delay
TH2 abnormality
delay
4-way valve abnormality
delay
Delay caused by blocked
valve in cooling mode
Power module
abnormality delay
TH6 abnormality
delay
Current sensor
open/short delay
8 00010000
Abnormality delay history 1
High pressure
abnormality delay
Superheat due
to low discharge
temperature delay
Compressor
shell temperature
abnormality delay
TH4 abnormality
delay
TH3 abnormality
delay
Outdoor fan rotation
frequency abnormality delay
TH7 abnormality
delay
TH8 abnormality
delay
Display all abnormalities
remaining in abnormality
delay
9 10010000
Abnormality delay history 2
Heat sink
overheating delay
Compressor
over current
interception delay
Voltage abnormality
delay
Insu󰀩cient refrigerant
amount abnormality delay
Current sensor
/
primary current
abnormality delay
63LS
abnormality
delay
63HS abnormality delay
start over current
interception
abnormality delay
10 01010000
Abnormality delay history 3
63LS abnormality delay
TH2 abnormality
delay
4-way valve
abnormality delay
Delay caused by blocked
valve in cooling mode
Power module
abnormality delay
TH6 abnormality
delay
Current sensor
open/short delay
11 11010000
Abnormality code history 1
(the latest)
Alternating display of addresses
0000–9999 and abnormality code
(including abnormality delay code)
• Display abnormalities up to
present (including
abnormality
terminals)
• History record in 1 is the
latest; records become older
in sequence; history record
in 10 is the oldest.
12 00110000
Abnormality code history 2
13 10110000
Abnormality code history 3
14 01110000
Abnormality code history 4
15 11110000
Abnormality code history 5
16 00001000
Abnormality code history 6
17 10001000
Abnormality code history 7
18 01001000
Abnormality code history 8
19 11001000
Abnormality code history 9
20 00101000
Abnormality code history 10
(the oldest)
21 10101000 Cumulative time
0–9999 (unit: 1 hour)
Display of cumulative
compressor operating time
22 01101000 Cumulative time
0
9999 (unit: 10 hour)
23 11101000
Outdoor unit operation display
Compressor energizing
Compressor operating prohibition
Compressor in operation
Abnormality detection
Light ON/Light OFF
24 00011000
Indoor unit operation mode
No.1 unit mode No.2 unit mode No.3 unit mode No.4 unit mode No.5 unit mode No.6 unit mode No.7 unit mode No.8 unit mode
Cooling : light on, Heating: light blinking
Stop fan: light o󰀨
25 10011000
Indoor unit operation display
No.1 unit operation No.2 unit operation No.3 unit operation No.4 unit operation No.5 unit operation No.6 unit operation No.7 unit operation No.8 unit operation
Thermo ON : light on Thermo OFF : light o󰀨
Delay code Abnormality delay Delay code Abnormality delay
1202 Discharge/Comp. temperature 1600 Discharge superheat (SHd)
Thermistor <Compressor>(TH4) Over charge refrigerant
1205 Thermistor <Outdoor liquid pipe> (TH3) 1601 Insu󰀩cient refrigerant
1211 Thermistor <Suction pipe> (TH6) Closed cooling valve
1214 Thermistor <Heat sink> (TH8) 1608 4-way valve disconnection
1221 Thermistor <Ambient> (TH7) 4310 Current sensor open/short
1222 Thermistor <HIC> (TH2) 4320
Undervoltage, overvoltage, or power module
1400 Low pressure sensor 4330 Heat sink temperature
1402 High pressure (63H) 4350 Power module
High pressure sensor (63HS) 4500 Outdoor fan motor