Spec Sheet

M-SERIES
SUBMITTAL DATA: MXZ-3C30NA2-U1
MULTI-INDOOR INVERTER HEAT-PUMP SYSTEM
Job Name: Location: Date:
Purchaser: Engineer:
Submitted to: For Reference Approval Construction
System Designation: Schedule No.:
GENERAL FEATURES
Quiet operation
Optional base pan heater to prevent ice in drain pan
ACCESSORIES
3/8" x 1/2" Port Adapter (MAC-A454JP-E)
1/2" x 3/8" Port Adapter (MAC-A455JP-E)
1/2" x 5/8" Port Adapter (MAC-A456JP-E)
1/4" x 3/8" Port Adapter (PAC-493PI)
3/8" x 5/8" Port Adapter (PAC-SG76RJ-E)
M-NET Adapter (PAC-IF01MNT-E)
Outdoor Unit: MXZ-3C30NA2
Base Heater (PAC-645BH-E)
Model Name
Unit Type
MXZ-3C30NA2-U1
Rated Capacity Btu/h 28,400 / 27,400
Cooling*
Non-ducted / Ducted (*2)
Capacity Range Btu/h 12,600-28,400 / 12,600-27,400
Rated Total Input W 2,680 / 2,860
Rated Capacity Btu/h 28,600 / 27,600
Heating at 47°F* (8.3°C*)
Non-ducted / Ducted (*2)
Capacity Range Btu/h 11,400-36,000 / 11,400-35,000
Rated Total Input W 2,150 / 2,220
Heating at 17°F* (-8.3°C*)
Non-ducted / Ducted (*2)
Rated Capacity Btu/h 21,000 / 21,000
Rated Total Input W 2,120 / 2,140
Power Supply Voltage, Phase, Hertz 208 / 230V, 1-Phase, 60 Hz
Electrical Requirements
Recommended Fuse/Breaker Size A 25
MCA A 22.1
Voltage
Indoor - Outdoor S1-S2 V AC 208 / 230
Indoor - Outdoor S2-S3 V +12VDC to 24VDC
Compressor INVERTER-driven Scroll Hermetic
Fan Motor (ECM) F.L.A. 1.9
Sound Pressure Level
Cooling 52
Heating
dB(A)
56
External Dimensions (H x W x D) In (mm)
31-11/32 x 37-13/32 x 13
(796 x 950 x 330)
Net Weight Lbs (kg) 135 (61)
External Finish Munsell 3.0Y 7.8/1.1
Refrigerant Pipe Size O.D. ―
Three Ports
Liquid 1/4 (12.7)
Gas
In (mm)
A: 1/2 (6.35) ; B,C: 3/8 (9.52)
Max. Refrigerant Line Length $%& Ft (m) 230 (70)
Max. Piping Length for Each Indoor Unit Ft (m) 82 (25)
Max. Refrigerant Pipe Height
Difference
If IDU is Above ODU 49 (15)
If IDU is Below ODU
Ft (m)
49 (15)
Connection Method ,QGRRU2XWGRRU
Flared/Flared
Refrigerant R410A
* Rating Conditions per AHRI Standard:
Cooling | Indoor: 80º F (27º C) DB / 67º F (19º C) WB
Cooling | Outdoor: 95º F (35º C) DB / 23.9° C (75° F) WB
Heating at 47ºF | Indoor: 70º F (21º C) DB / 60º F (16º C) WB
Heating at 47ºF | Outdoor: 47º F (8º C) DB / 43º F (6º C) WB
Heating at 17º F | Indoor: 70º F (21º C) DB
Heating at 17º F | Outdoor: 17º F (-8º C) DB / 15º F (-9º C) WB
Specifications are subject to change without notice.
© 2016 Mitsubishi Electric Sales Canada Inc.
Page 1 of 3
Form # SB_MXZ-3C30NA2-U1_201905
Windscreens (*1)
*
1 5HTXLUHGLQZLQG\ORFDWLRQVRUDUHDVWKDWH[SHULHQFHORZWHPSHUDWXUHV
*2 Non-ducted (06+09+12) / Ducted (09+09+12) combinations
NA
Heating at 5°F* (-15°C*) (*2)
Btu/h
Capacity
Should this document be altered or changed without MESCA’s permission, it becomes null and void. MESCA assumes no responsibility for any consequences in such cases.
Note: Mitsubishi Electric (MESCA) supports the use of only MESCA supplied and approved Snow Guard / Wind Deflectors / Windscreens and accessories for
proper functioning of the unit(s). Use of non-MESCA supported Snow Guard / Wind Deflectors / Windscreens and accessories will affect warranty coverage.
*
All electrical work shall comply with National (CEC) and local codes and regulations.

Summary of content (3 pages)