MXZ-5C42NA3 Service Manual

113
NOTE: Blinking patterns of this mode di󰀨er from the ones of
TROUBLESHOOTING CHECK TABLE (12-4.).
The left lamp of
OPERATION
INDICATOR lamp
(Indoor unit)
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C.
board)
Condition Remedy
Indoor/outdoor
unit failure
mode recall
function
LED 1 LED 2
8-time blink Outdoor fan motor Lit Lit A failure occurs 3 consecutive times within
30 seconds after the fan gets started.
• Refer to 12-6. "Check of outdoor
fan motor".
4-way valve switching operation
abnormality.
Lit
12 times
Connector of R.V. coil is disconnected,
poorly connected or 4-way valve is faulty.
Refer to 12-6. "Check of R.V. coil".
• Check the 4-way valve.
9-time blink Outdoor control system Lit 5 times Nonvolatile memory data cannot be read
properly.
• Replace the outdoor control P.C.
board.
10-time blink Low discharge temperature
protection
Lit Lit The frequency of the compressor is kept
80 Hz or more and the discharge tempera-
ture is kept under 102.2°F for more than
20 minutes.
• Check refrigerant circuit and refrig-
erant amount.
• Refer to 12-6. "Check of LEV".
11-time blink Communication error
between P.C. boards
Lit 6 times
Communication error occurs between the
outdoor control P.C. board and outdoor
power P.C. board for more than 10 seconds.
Check the connecting wire between
outdoor control P.C. board and out-
door power P.C. board.
The communication between boards protec-
tion cut-out operates 2 consecutive times.
Current sensor Lit 7 times A short or open circuit is detected in the cur-
rent sensor during compressor operating.
Current sensor protection cut-out operates
2 consecutive times.
Zero cross detecting circuit 5 times Not lit Zero cross signal cannot be detected while
the compressor is operating.
Check the connecting wire among
outdoor control P.C. board and out-
door power P.C. board.
The protection cut-out of the zero cross
detecting circuit operates 10 consecutive
times.
Converter 5 times Not lit A failure is detected in the operation of the
converter during operation.
• Check the voltage of power supply.
Replace the outdoor power P.C.
board.
Bus-bar voltage 5 times Not lit The bus-bar voltage exceeds 400 V or falls
to low level during compressor operating.
• Check the voltage of power supply.
Replace the outdoor power P.C. board
or the outdoor control P.C. board.
14-time blink 4-way valve switching operation
abnormality.
Lit 12
times
Connector of R.V. coil is disconnected,
poorly connected or 4-way valve is faulty.
Refer to 12-6. "Check of R.V. coil".
• Check the 4-way valve.
15-time blink LEV and drain pump Lit Lit The indoor unit detects an abnormality in
the LEV and drain pump.
Refer to 12-6. "Check of LEV".
Check the drain pump of the indoor unit.