Part name Check method and criterion
High pressure switch(HPS)
Pressure Normal
HPS
537 ± 22 PSIG Close
696
+7
-15
PSIG Open
Defrost heater Measure the resistance using a multimeter. (Part temperature: 14°F - 104°F)
Normal
MXZ-2C20NAHZ MXZ-3C24NAHZ MXZ-3C30NAHZ
MXZ-2C20NAHZ2 MXZ-3C24NAHZ2 MXZ-3C30NAHZ2
MXZ-2C20NAHZ3 MXZ-3C24NAHZ3 MXZ-3C30NAHZ3
MXZ-2C20NAHZ4 MXZ-3C24NAHZ4 MXZ-3C30NAHZ4
0.35 kΩ - 0.50 kΩ
OBH702M