MXZ-5C42NA3 Service Manual

124
How to check inverter/compressor
• When heating, room does not get warm.
• When cooling, room does not get cool.
Disconnect the terminal of the compressor or the connector (CNMC) between the compressor
and the outdoor power P.C. board.
3 minutes after the power supply is turned ON,
start EMERGENCY OPERATION.
Is output balanced?
Clarify the causes by counting time until the inverter stops.
0 to 10 seconds: compressor layer short
10 to 60 seconds: compressor lock
60 seconds to 5minutes: refrigerant circuit defective
5 minutes or more: normal
Turn OFF the power supply of indoor and
outdoor unit, and measure the compressor
winding resistance between the compressor
terminals.
Is the resistance between each terminal normal?
(Refer to 12-5.)
Is the input voltage to the outdoor control
P.C. board 370 V DC or more?
Reconnect the lead wire of compressor, and turn ON
the power supply to indoor and outdoor unit.
3 minutes later, start EMERGENCY OPERATION.
Replace the compressor.
Replace the outdoor power P.C. board.
*1 After the outdoor fan starts running, wait for 1 minute
or more before measuring the voltage.
The output voltage values have the tolerance of ± 20%.
*2 The output differs depending on the capacity or the
number of indoor units to be operated.
Measure the voltage between each
lead wire leading to the compressor.
U (BLK) - V (WHT)
V (WHT) - W (RED)
W (RED) - U (BLK)
Output voltage:
50V-250V
Is proper output voltage detected?
*1, *2
No
No
Yes
Yes
Yes
No
Yes
No
OBH702M