MXZ-5C42NA3 Service Manual

81
9-1. OPERATING RANGE
(1) POWER SUPPLY
Model Rating Guaranteed Voltage
Outdoor unit
MXZ-2C20NA2
MXZ-2C20NA3
MXZ-2C20NA4
MXZ-3C24NA
MXZ-3C24NA2
MXZ-3C24NA3
MXZ-3C24NA4
MXZ-3C30NA
MXZ-3C30NA2
MXZ-3C30NA3
MXZ-3C30NA4
MXZ-4C36NA
MXZ-4C36NA2
MXZ-4C36NA3
MXZ-4C36NA4
MXZ-5C42NA
MXZ-5C42NA2
MXZ-5C42NA3
MXZ-5C42NA4
MXZ-2C20NAHZ
MXZ-2C20NAHZ2
MXZ-2C20NAHZ3
MXZ-2C20NAHZ4
MXZ-3C24NAHZ
MXZ-3C24NAHZ2
MXZ-3C24NAHZ3
MXZ-3C24NAHZ4
MXZ-3C30NAHZ
MXZ-3C30NAHZ2
MXZ-3C30NAHZ3
MXZ-3C30NAHZ4
208/230 V 60 Hz 1ø
Min. 198 V 208 V 230 V Max. 253 V
(2) OPERATION
Function
Intake air
temperature
Condition
Indoor Outdoor
DB (°F) WB (°F) DB (°F) WB (°F)
Cooling
"A" Cooling steady state
at rated compressor speed
80 67 95 (75)
"B-2" Cooling steady state
at rated compressor speed
80 67 82 (65)
"B-1" Cooling steady state
at minimum compressor speed
80 67 82 (65)
Low ambient cooling steady state
at minimum compressor speed
80 67 67 (53.5)
Intermediate cooling steady state
at intermediate compressor speed
80 67 87 (69)
Heating
Standard rating-heating
at rated compressor speed
70 60 47 43
Low temperature heating
at rated compressor speed
70 60 17 15
Max. temperature heating
at minimum compressor speed
70 60 62 56.5
High temperature heating
at minimum compressor speed
70 60 47 43
Frost accumulation
at rated compressor speed
70 60 35 33
Frost accumulation
at intermediate compressor speed
70 60 35 33
OBH702M