Revision D: • Capacity corrections have been corrected [7-1. 2), 3)]. OBH684 REVISED EDITION-C is void. OUTDOOR UNIT No. OBH684 HFC utilized SERVICE MANUAL REVISED EDITION-D R410A Models MUZ-FH06NA MUZ-FH09NA MUZ-FH09NA MUZ-FH12NA MUZ-FH12NA MUZ-FH15NA MUZ-FH18NA MUZ-FH18NA2 1 1 MUZ-FH06NAH MUZ-FH09NAH MUZ-FH09NAH MUZ-FH12NAH MUZ-FH12NAH MUZ-FH15NAH MUZ-FH18NAH MUZ-FH18NAH2 1 1 Indoor unit service manual MSZ-FH•NA Series (OBH683) CONTENTS 1. TECHNICAL CHANGES ······························2 2.
Use the specified refrigerant only Never use any refrigerant other than that specified. Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions. Revision A: • 3. SPECIFICATION has been modified.
2 PART NAMES AND FUNCTIONS MUZ-FH06NA MUZ-FH09NA MUZ-FH12NA MUZ-FH06NAH MUZ-FH09NAH MUZ-FH12NAH Air inlet (back and side) Piping Air outlet Drain hose Drain outlet MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2 Air inlet (back and side) Piping Drain hose Air outlet Drain outlet OBH684D 3
3 SPECIFICATION MUZ-FH06NA MUZ-FH09NA MUZ-FH12NA MUZ-FH15NA MUZ-FH18NA MUZ-FH18NA2 MUZ-FH06NAH MUZ-FH09NAH MUZ-FH12NAH MUZ-FH15NAH MUZ-FH18NAH MUZ-FH18NAH2 Outdoor unit model Capacity Rated (Minimum~Maximum) Capacity Cooling 1 Btu/h 6,000 9,000 12,000 15,000 (1,700 ~ 9,000) (1,700 ~ 12,000) (2,500 ~ 13,600) (6,450 ~ 19,000) 17,200 (6,450 ~ 21,000) Heating 47 1 Btu/h 8,700 10,900 13,600 18,000 (1,600 ~ 14,000) (1,600 ~ 18,000) (3,700 ~ 21,000) (5,150 ~ 24,000) 20,300 (5,150 ~ 30,000) Heating 17
Test condition 3, 4 ARI Mode Indoor air condition (°F) Dry bulb Wet bulb Test Outdoor air condition (°F) Dry bulb Wet bulb "A-2" Cooling Steady State at rated compressor Speed 80 67 95 (75) "B-2" Cooling Steady State at rated compressor Speed 80 67 82 (65) SEER "B-1" Cooling Steady State (Cooling) at minimum compressor Speed 80 67 82 (65) "F-1" Cooling Steady State at minimum compressor Speed 80 67 67 (53.
4 OUTLINES AND DIMENSIONS MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH Unit: inch *1 4 in. (100 mm) or more when front and sides of the unit are clear clear *1 REQUIRED SPACE m) 0 me 0 1 r ( o n. 4 i or m 4 in .( or 100 m mo re m) (MUZ-FH06/09/12NA) (MUZ-FH06/09/12NAH) ) mm 200 e *2 ( . 8 in r mor o 14 in.
MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2 REQUIRED SPACE *1 20 in. (500 mm) or more when front and sides of the unit are clear Clear *1 Unit: inch 16-7/16 2 13 Drain hole 1-9/16 ) mm 00 . (1 re n i 4 mo or 1-5/8 4i or mn. (10 ore 0 mm ) 14-3/16 Air in Air in ) mm 00 . (5 *2 n i 20 ore or m Air out 2 x hole 13/32 x 13/16 6-7/8 19-11/16 14 or min.
5 WIRING DIAGRAM MUZ-FH06NA MUZ-FH09NA- 1 MUZ-FH06NAH MUZ-FH09NAH- OBH684D MUZ-FH12NA- 1 1 MUZ-FH12NAH- 8 1
MUZ-FH09NA MUZ-FH12NA MUZ-FH09NAH MUZ-FH12NAH OBH684D 9
MUZ-FH15NA MUZ-FH18NA OBH684D 10
MUZ-FH18NA2 OBH684D 11
MUZ-FH15NAH MUZ-FH18NAH OBH684D 12
MUZ-FH18NAH2 OBH684D 13
6 REFRIGERANT SYSTEM DIAGRAM MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH Unit: inch Refrigerant pipe ø3/8 (with heat insulator) 4-way valve Muffler Stop valve Discharge temperature Service thermistor port RT62 Flared connection Outdoor heat exchanger Muffler Service port Outdoor heat exchanger temperature thermistor RT68 Ambient temperature thermistor RT65 Compressor Defrost thermistor RT61 Flared connection Refrigerant pipe ø1/4 (with heat insulator) Capillary tube O
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE Model Refrigerant piping: ft. Max. Length Max. Height difference A B Piping size O.D: in. Gas Liquid MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH 65 40 3/8 1/4 MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2 100 50 1/2 1/4 Indoor unit Max. Height difference B Max. Length A Outdoor unit ADDITIONAL REFRIGERANT CHARGE (R410A: oz.) NOTE: Refrigerant piping exceeding 25 ft.
7 DATA MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2 7-1. PERFORMANCE DATA 1) COOLING CAPACITY Indoor air Model MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2 IWB (˚F) 71 67 63 71 67 63 71 67 63 71 67 63 71 67 63 71 67 63 TC 7.4 7.0 6.5 11.0 10.4 9.8 14.7 13.9 13.1 18.4 17.4 16.4 21.1 20.0 18.7 21.1 20.0 18.
4) HEATING CAPACITY Indoor air Model MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2 IDB (˚F) 75 70 65 75 70 65 75 70 65 75 70 65 75 70 65 75 70 65 75 70 65 75 70 65 75 70 65 75 70 65 75 70 65 75 70 65 5 TC 3.8 4.1 4.4 3.8 4.1 4.4 4.8 5.2 5.5 4.8 5.2 5.5 6.0 6.5 6.8 6.0 6.5 6.8 7.9 8.6 9.0 7.9 8.6 9.0 8.9 9.6 10.2 8.9 9.6 10.2 8.9 9.6 10.2 8.9 9.6 10.2 15 TPC 0.32 0.31 0.29 0.45 0.44 0.42 0.42 0.40 0.
7-2. PERFORMANCE CURVE Cooling Cooling capacity (at Rated frequency) Capacity correction factors Indoor air Wet-bulb temperature difference (°F) 1.5 Indoor intake air Wet-bulb temperature( F) 1.4 1.3 1.2 76 1.1 75 1.0 0.9 14 23 32 41 50 59 68 77 86 95 104 72 68 64 113 Outdoor intake air DB temperature(°F) MUZ-FH09NA MUZ-FH09NAH SHF at rating condition = 0.96 Airflow = 381 CFM 0.5 0.4 (°F) mperature ir WB te r intake a Indoo 0.3 71 67 63 0.2 0.
Heating Heating capacity (at Rated frequency) 1.2 Capacity correction factor Indoor air Dry-bulb temperature difference (°F) 1.3 ure ( F) 59 68 79 rat 1.1 1.0 ulb e mp te y-b 0.9 0.8 r oo r ir D ea ak int Ind 0.7 0.6 0.5 0.4 -4 5 14 23 32 41 50 Outdoor intake air WB temperature (°F) MUZ-FH06NA 59 MUZ-FH06NAH 0.6 take or in Indo ) e (°F ratur mpe te B air D 75 70 65 0.4 0.
MUZ-FH18NA MUZ-FH18NAH 2.00 Airflow = 514 CFM 65 70 75 1.75 1.50 1.25 1.00 ke air inta Indoor 0.75 0.50 -5 5 re (°F) peratu DB tem 65 15 25 35 45 55 Outdoor intake air WB temperature (°F) MUZ-FH18NA2 Total power consumption (kW) Total power consumption (kW) Airflow = 514 CFM 2.00 75 70 65 1.75 1.50 1.25 B take air D Indoor in 1.00 0.75 -5 5 15 25 35 45 55 Outdoor intake air WB temperature (°F) Airflow = 514 CFM 65 70 75 1.75 1.50 1.25 1.00 0.
MUZ-FH12NA MUZ-FH12NAH (PSIG) 500 ture ) (°F a per 400 (PSIG) 180 86 80 75 70 m B te rD doo In Suction pressure Condensing pressure 450 350 300 250 200 65 70 75 80 85 90 95 86 80 75 70 140 120 100 80 65 100 105 (°F) rature (°F) Indoor DB tempe 160 70 Outdoor ambient temperature 75 80 85 90 95 Outdoor ambient temperature 100 105 (°F) MUZ-FH15NA MUZ-FH15NAH (PSIG) 500 ture ) (°F a per 400 In 350 300 250 200 65 (PSIG) 180 86 80 75 70 m B te rD doo Suction pressure
Heating Data are based on the condition of outdoor humidity 75%. Air flow should be set to High speed. Data are for heating operation without any frost.
MUZ-FH18NA MUZ-FH18NAH (PSIG) 600 75 70 65 500 ture era mp oor 450 Ind ) (°F te DB 400 350 300 75 70 65 175 Suction pressure Condensing pressure 550 (PSIG) 200 ) 150 re (°F tu a er p m 125 B rD te o do In 100 75 5 15 25 35 45 55 Outdoor ambient temperature 65 75 (°F) 50 5 15 25 35 45 55 Outdoor ambient temperature 65 75 (°F) MUZ-FH18NA2 MUZ-FH18NAH2 (PSIG) 600 75 70 65 500 oor 450 Ind tur era mp te DB F) e (° 400 350 300 75 70 65 175 Suction pressure
7-4. STANDARD OPERATION DATA Model Item MSZ-FH06NA MSZ-FH09NA MSZ-FH12NA MSZ-FH15NA MSZ-FH18NA MSZ-FH18NA2 Unit Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Total Capacity Btu/h 6,000 — 0.96 — 0.92 — 0.83 — 0.70 — 0.67 — 0.69 — Input kW 0.315 0.545 0.560 0.710 0.870 0.950 1.200 1.300 1.430 1.720 1.375 1.72 Rated frequency Hz 28 50 47 58.5 46 49 50.5 50 59.5 61 57.
7-5. CAPACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY MUZ-FH06NA MUZ-FH06NAH Correction of Cooling total input 1.5 1.0 0.5 0.0 0 25 50 75 100 (Hz) 2.0 Capacity correction factors Input correction factors Capacity correction factors 2.0 1.5 1.0 0.5 0.0 0 25 50 75 100 (Hz) Correction of Heating capacity 1.5 1.0 0.5 0.0 0 2.5 Input correction factors Correction of Cooling capacity 2.
MUZ-FH18NA MUZ-FH18NAH 1.5 1.0 0.5 0.0 0 25 50 75 100 (Hz) Correction of Cooling total input 2.0 1.5 1.0 0.5 0.0 0 25 50 75 100 (Hz) Correction of Heating capacity 1.5 1.0 0.5 0.0 0 2.5 Input correction factors Input correction factors Capacity correction factors 2.0 Capacity correction factors Correction of Cooling capacity 2.
8 ACTUATOR CONTROL MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2 8-1. OUTDOOR FAN MOTOR CONTROL The fan motor turns ON/OFF, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running. 5 seconds 15 seconds ON Compressor OFF ON Outdoor fan motor OFF 8-2. R.V. COIL CONTROL Heating . . . .
9 SERVICE FUNCTIONS MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2 9-1. CHANGE IN DEFROST SETTING Changing defrost finish temperature To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board (Refer to 10-6.1.).
10 TROUBLESHOOTING MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2 10-1. CAUTIONS ON TROUBLESHOOTING 1. Before troubleshooting, check the following 1) Check the power supply voltage. 2) Check the indoor/outdoor connecting wire for miswiring. 2.
10-2. FAILURE MODE RECALL FUNCTION Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details can be recalled. 1. Flow chart of failure mode recall function for the indoor/outdoor unit Operational procedure The cause of abnormality cannot be found because the abnormality does not recur.
2. Flow chart of the detailed outdoor unit failure mode recall function Operational procedure The outdoor unit might be abnormal. Check if outdoor unit is abnormal according to the following procedures. Make sure that the remote controller is set to the failure mode recall function. With the remote controller headed towards the indoor unit, press TEMP button to adjust the set temperature to 77°F (25°C). 1 Does the left lamp of the OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.
3. Outdoor unit failure mode table The left lamp of the OPERATION INDICATOR lamp (Indoor unit) OFF 1-time flash 2.5 seconds OFF Abnormal point (Failure mode/protection) None (Normal) Indoor/outdoor communication, receiving error Indoor/outdoor communication, receiving error LED indication (Outdoor P.C. board) — — — 2-time flash 2.5 seconds OFF Outdoor power system 3-time flash 2.5 seconds OFF Discharge temperature thermistor Defrost thermistor 1-time flash every 2.
The left lamp of the Abnormal point OPERATION (Failure mode/protection) INDICATOR lamp (Indoor unit) 10-time flash Discharge temperature 2.5 seconds OFF 11-time flash 2.5 seconds OFF 14-time flash or more 2.5 seconds OFF DC voltage Each phase current of compressor Stop valve (Closed valve) LED indication (Outdoor P.C. board) — 8-time flash 2.5 seconds OFF 9-time flash 2.5 seconds OFF 14-time flash 2.
10-3. TROUBLESHOOTING CHECK TABLE No. 1 Symptom Outdoor unit does not operate. Abnormal point/ Condition 1-time flash every Outdoor power sys2.5 seconds tem Condition LED indication • Reconnect connector of compressor. • Refer to 10-5. "How to check inverter/compressor". • Check stop valve. Outdoor thermistors Discharge temperature thermistor, fin temperature thermistor, • Refer to 10-5. "Check of outdoor defrost thermistor, P.C. board temperature thermistor, outdoor thermistors".
No. Symptom Outdoor unit operates. LED indication 1-time flash 2.5 seconds OFF Abnormal point/ Condition Frequency drop by current protection 16 3-time flash 2.5 seconds OFF 17 4-time flash 2.5 seconds OFF 18 Outdoor unit operates. Frequency drop by defrosting in COOL mode Indoor coil thermistor reads 46°F (8°C) or less in COOL mode, compressor frequency lowers.
10-4. TROUBLE CRITERION OF MAIN PARTS MUZ-FH06NA MUZ-FH06NAH MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2 Part name Defrost thermistor (RT61) Fin temperature thermistor (RT64) Ambient temperature thermistor (RT65) Check method and criterion Figure Measure the resistance with a tester. Refer to 10-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, for the chart of thermistor.
10-5. TROUBLESHOOTING FLOW A How to check inverter/compressor Disconnect the connector between the compressor and the power module (IC700) (MUZ-FH06/09/12)/ IGBT module (IC700) (MUZ-FH15/18). See 10-5. Check the voltage between terminals. Are the voltages balanced? Yes No Replace the inverter P.C. board. See 10-5. Check the compressor. “Check of open phase”. “Check of compressor”.
D Check of compressor winding ●Disconnect the connector between the compressor and the power module (IC700) (MUZ-FH06/09/12)/IGBT module (IC700) (MUZ-FH15/18), and measure the resistance between the compressor terminals. <> At 3 points BLK-WHT Measure the resistance between the lead wires at 3 points. BLK-RED WHT-RED <> Refer to 10-4. 0 [Ω] ················Abnormal [short] Infinite [Ω] ·······Abnormal [open] NOTE: Be sure to zero the ohmmeter before measurement.
G Check of outdoor thermistors Disconnect the connector of thermistor in the inverter P.C. board (see below table), and measure the resistance of thermistor. Is the resistance of thermistor normal? (Refer to 10-6.1.) Yes No Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P.C. board. Reconnect the connector of thermistor. Turn ON the power supply and press EMERGENCY OPERATION switch.
H Check of R.V. coil MUZ-FH06/09/12 First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 10-4. In case CN721 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector although no signal is being transmitted to R.V. coil. Check if CN721 is connected. Unit operates COOL mode even if it is set to HEAT mode. Disconnect connector between the compressor and the power module (IC700).
I Check of outdoor fan motor Disconnect the connectors CN931 and CN932 from the inverter P.C. board. Check the connection between the connector CN931 and CN932. Is the resistance between each terminal of outdoor fan motor normal? (Refer to 10-4.) No Yes Disconnect CN932 from the inverter P.C. board, and turn on the power supply. Rotate the outdoor fan motor manually and measure the voltage of CN931.
J Check of power supply Disconnect the connector between the compressor and the power module (IC700) (MUZ-FH06/09/12)/IGBT module (IC700) (MUZ-FH15/18). Turn ON power supply and press EMERGENCY OPERATION switch. Does the left lamp of the OPERATION INDICATOR lamp on the indoor unit light up? Yes Is there DC voltage 260 - 370 VDC between DB61 (+) and DB61 (–) (MUZ-FH06/09/12)/294 - 370 VDC between JP715 (+) and JP30 (–) (MUZ-FH15/18) on the inverter P.C. board? (Refer to 10-6.1.
K Check of LEV (Expansion valve) Turn ON the power supply. While pressing both OPERATION SELECT button and TEMP button on the remote controller at the same time, press RESET button. First, release RESET button. Hold down the other 2 buttons for another 3 seconds. Make sure that the indicators on the LCD screen shown in the right figure are all displayed. Then release the buttons.
L Check of inverter P.C. board Check the outdoor fan motor. (Refer to 10-5. .) Is the fuse (F901) blown on the inverter P.C. board? No Yes Check the connection of the connectors (CN931, CN932) of the outdoor fan motor. If the connection is poor, make it correct. Operate the outdoor unit by starting EMERGENCY OPERATION. Check the LED indication on the inverter P.C. board. Does the LED flash 10 times? Yes (10-time flash) No Check the corresponding parts following LED indication. (Refer to 10-3.
M How to check miswiring and serial signal error NOTE: Refer to the indoor unit service manual. Turn OFF the power supply. Is there rated voltage in the power supply? Yes Check the power supply. No Turn ON the power supply. Is there rated voltage between the outdoor terminal block S1 and S2? Yes No Check the wiring. Press EMERGENCY OPERATION switch once.
N Check of defrost heater MUZ-FH06NAH MUZ-FH09NAH MUZ-FH12NAH MUZ-FH15NAH MUZ-FH18NAH MUZ-FH18NAH2 Check the following points before checking electric continuity. 1. Does the resistance of ambient temperature thermistor have the characteristics? Refer to 10-6.1. 2. Is the resistance of defrost heater normal? Refer to 10-4. 3. Does the heater protector remain conducted (not open)? 4.
P Electromagnetic noise enters into TV sets or radios Is the unit grounded? Yes Is the distance between the antennas and the indoor unit within 9.91 ft. (3m), or is the distance between the antennas and the outdoor unit within 9.91 ft. (3m)? No Is the distance between the TV sets or radios and the indoor unit within 3.28 ft. (1m), or is the distance between the TV sets or radios and the outdoor unit within 9.91 ft. (3m)? Ground the unit.
10-6. TEST POINT DIAGRAM AND VOLTAGE 1. Inverter P.C. board MUZ-FH06NA MUZ-FH12NA- 1 Back side of unit MUZ-FH06NAH MUZ-FH12NAH- MUZ-FH09NA- 1 MUZ-FH09NAH- 1 1 Smoothing capacitor (C62) DB61 260 - 370 VDC (-) (+) Heater connector R.V.coil (CN722) (CN721) Smoothing capacitor (C61) 208/230 VAC (MUZ-FH06NAH MUZ-FH09/12NAHFuse (F701) T3.15AL250V Fuse (F801) T3.15AL250V 208/230 VAC 1 Fuse (F901) T3.
MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH Back side of unit Smoothing capacitor (C62) DB61 260 - 370 VDC (-) (+) R.V.coil Heater connector (CN721) (CN722) (MUZ208/230 VAC FH09/12NAH) Smoothing capacitor (C61) Fuse (F701) T3.15AL250V Fuse (F801) T3.15AL250V 208/230 VAC Fuse (F901) T3.
MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NA2 MUZ-FH18NAH MUZ-FH18NAH2 Fuse (F601) T3.15AL250V R.V.
11 DISASSEMBLY INSTRUCTIONS <"Terminal with locking mechanism" Detaching points> The terminal which has the locking mechanism can be detached as shown below. There are 2 types (refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching. (1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the locking mechanism.
OPERATING PROCEDURE Photo 4 PHOTOS Photo 5 Screws of the conduit cover 2. Removing the inverter assembly, inverter P.C. board (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: CN721 (R.V.
OPERATING PROCEDURE PHOTOS 4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor Screw of the R.V. coil Photo 8 (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors:
PHOTOS OPERATING PROCEDURE 5. Removing outdoor fan motor Photo 11 Screws of the outdoor fan motor (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connectors: CN931, CN932 (Fan motor) (3) Remove the propeller fan nut. (4) Remove the propeller fan. (5) Remove the screws fixing the fan motor. (6) Remove the fan motor. Propeller fan 6.
11-2. MUZ-FH15NA MUZ-FH15NAH MUZ-FH18NA MUZ-FH18NAH MUZ-FH18NA2 MUZ-FH18NAH2 NOTE: Turn OFF the power supply before disassembly. OPERATING PROCEDURE PHOTOS 1. Removing the cabinet Photo 1 (1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the screws fixing the conduit cover. (6) Remove the conduit cover. (7) Remove the screw of fixing the conduit plate. (8) Remove the conduit plate.
OPERATING PROCEDURE PHOTOS 2. Removing the inverter assembly, inverter P.C. board and relay P.C. board (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: CN602 (R.V.
OPERATING PROCEDURE PHOTOS 4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor Photo 7 Outdoor heat exchanger temperature thermistor Ambient temperature thermistor (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors:
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN © Copyright 2014 MITSUBISHI ELECTRIC CORPORATION Issued: Jul. 2017. No. OBH684 REVISED EDITION-D Issued: Oct. 2015. No. OBH684 REVISED EDITION-C Issued: Dec. 2014. No. OBH684 REVISED EDITION-B Issued: Apr. 2014. No. OBH684 REVISED EDITION-A Published: Feb. 2014. No. OBH684 Made in Japan Specifications are subject to change without notice.