Job Name:
System Reference: Date:
SUBMITTAL DATA: MSZ-FH18NA2 & MUZ-FH18NA2
18,000 BTU/H WALL-MOUNTED HEAT PUMP SYSTEM
Indoor Unit: MSZ-FH18NA2
Outdoor Unit: MUZ-FH18NA2
Wireless Remote Controller
ACCESSORIES:
Indoor Unit
□ Condensate Pump (BlueDiamond X87-711/721; 115/230V)
□ Condensate Pump (Sauermann SI30-115/230; 115/230V)
□ Replacement Platinum Deodorizing Filter (MAC-3000FT-E)
□ Replacement Anti-allergy Enzyme Filter (MAC-2330FT-E)
Outdoor Unit
□ Air Discharge Guide (MAC-886SG-E)
□ Base Pan Heater (MAC-642BH-U)
□ Drain Socket (MAC-851DS)
Controls
□ Wireless Controller (MHK1)
□ Wired Remote Controller PAR-31MAA (Requires MAC-333IF-E)
□ Wireless Interface for kumo cloud™ (PAC-WHS01WF-E)
□ Thermostat Interface (PAC-US444CN-1)
SPECIFICATIONS:
Rated Conditions (Capacity / Input)
Cooling
1
Btu/h / W
17,200 / 1,375
Heating at 47º F
2
Btu/h / W
20,300 / 1,720
Capacity Range Minimum Maximum
Cooling
1
Btu/h
6,450 21,000
Heating at 47º F
2
Btu/h
5,150 30,000
Heating at 17º F
3
Btu/h
- 20,300
Heating at 5º F
4
Btu/h
- 20,300
1
Cooling | Indoor: 80º F(27º C)DB / 67º F(19º C)WB; Outdoor: 95º F(35º C)DB / 75º F(24º C)WB
*
2
Heating at 47ºF | Indoor: 70º F (21º C)DB / 60º F (16º C)WB; Outdoor: 47º F (8º C)DB / 43º F (6º C)WB
*
3
Heating at 17º F | Indoor: 70º F(21º C)DB / 60º F(16º C)WB; Outdoor: 17º F(-8º C)DB / 15º F(-9º C)WB
*
4
Heating at 5º F | Indoor: 70º F (21º C)DB / 60º F(16º C)WB; Outdoor: 5º F(-15º C) DB / 5º F(-15º C)WB
*
Rating Conditions per AHRI Standard:
Operating Conditons (Indoor Intake Air Temp.) (Max./ Min.)
Cooling
5
90º F (32º C) DB / 67º F (19º C) DB
Heating
80º F (27º C) DB / 70º F (21º C) DB
Operating Conditons (Outdoor Intake Air Temp.) (Max./ Min.)
Cooling
5
115º F (46º C) DB / 14º F (-10º C) DB
Heating
75º F (24º C) DB / -13º F (-25º C) DB**
5
Applications should be restricted to comfort cooling only; equipment cooling applications are not
recommended for low ambient temperature conditions.
**
System cuts out at -9º F (-27º C) to avoid thermistor error and automatically restarts at -4º F (-20º C).
AHRI Efciency Ratings
SEER / HSPF
21 / 12
COP at 47
o
F / 17
o
F
3.46 / 3.04
Energy Star
®
Yes
ENERGY STAR products are third-party certied by an EPA-recognized Certication Body.
Electrical Power
Requirements
208 / 230V, 1-Phase, 60 Hz
Minimum Circuit Ampacity (MCA)
Indoor / Outdoor
A
1 / 15
Indoor Unit
Blower Motor (ECM)
F.L.A.
0.67
Blower Motor Output
W
30
SHF / Moisture Removal
0.69 / 4.8 pt./h
Field Drainpipe Size O.D.
In.(mm)
5/8 (15)
Outdoor Unit
Compressor
DC INVERTER-driven Twin Rotary
Fan Motor (ECM)
F.L.A.
0.93
Airow Rate (Lo - Med - Hi - Super Hi - Powerful)
Indoor
(Cooling)
DRY
CFM
225-262-304-355-459
WET
194-225-261-305-395
Indoor
(Heating)
DRY
201-254-317-394-514
Outdoor
1,692 / 1,634
Sound Pressure Level (Lo - Med - Hi - Super Hi - Powerful)
Indoor
Cooling
dB(A)
27-31-35-39-47
Heating
25-29-34-39-46
Outdoor
Cooling
52
Heating
55
External Dimensions
Indoor (H x W x D)
In.(mm)
12 + 11/16 x 36-7/16 x 9-3/16
(305 +17 x 925 x 234)
Outdoor (H x W x D)
34-5/8 x 33-1/16 x 13
(880 x 840 x 330)
Net Weight
Indoor
Lbs.(kg)
29 (12)
Outdoor
124 (56)
External Finish
Indoor
Munsell 1.0Y 9.2 / 0.2
Outdoor
Munsell No. 3Y 7.8 / 1.1
Refrigerant
R410A; 3 lb. 7 oz.
Refrigerant Piping (Flared)
Liquid (High Pressure)
In.(mm)
1/4 (6.35)
Gas (Low Pressure)
1/2 (12.7)
Max. Total Refrigerant
Pipe Length (Height Diff.)
Ft. (m)
50 (15)
Max. Total Refrigerant
Pipe Length (Length.)
100 (30)