SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS No. OC153 TECHNICAL & SERVICE MANUAL Series PEH Ceiling Concealed Indoor unit [Models] PEH-2.5EKHA PEH-3EKHA PEH-4EKHSA PEH-5EKHSA [Service Ref.] PEH-2.5EKHA2.TH PEH-3EKHA2.TH PEH-4EKHSA2.TH PEH-5EKHSA2.TH This manual does not cover the following outdoor units. When servicing them, please refer to the service manual No.OC128,150 and this manual in a set. [Service Ref.] PUH-2.5VKA2 PUH-3VKA2,3YKA2 PUH-4YKSA3 PUH-5YKSA3 PUH-2.5VKA2.UK PUH-3VKA2.UK PUH-3YKA2.
1 FEATURES Series PEH Ceiling Concealed FILTER CHECK MODE TEST RUN Indoor unit Remote controller Outdoor unit Cooling capacity / Heating capacity (with Heater) Service Ref. W Btu / h PEH-2.5EKHA2.TH 6,400/6,700 (8,800) 21,800/22,900 (30,000) PEH-3EKHA2.TH 7,700/8,300 (10,400) 26,300/28,300 (35,500) PEH-4EKHSA2.TH 9,700/10,400(12,800) 33,100/35,500 (43,700) PEH-5EKHSA2.TH 12,400/13,000(16,000) 42,300/44,400 (54,600) 1.
(2) Non- polar two-wire remote controller cable The slim, non-polar, two-wire remote controller cable makes installation simple and troublefree. Also, the remote controller wire can be extended up to 500m. (3)Automatic cooling / heating changeover operation An automatic cooling and heating changeover operation system allows you to easily control comfortable year-round air conditioning.
● Remote controller ● Once the operation of the unit is set, subsequent operations can only be performed by pressing the ON/OFF button repeately. ● Operation buttons w button q button This switches between continuous operation and the timer operation. l button This sets of switches the current time. start time and stop time. This sets the ventilation fan speed. ON/OFF button a button This switches between the operation and stop modes each time it is pressed.
● Display CENTRALLY CONTROLLED display This indicates when the unit is controlled by optional features such as central control type remote controller. r display The current time , start time and stop time can be displayed in tensecond intervals by pressing the time switch button. The start time or stop time is always displayed during the timer operation.
3 SPECIFICATIONS Item Service Ref. Function PEH-2.5EKHA2 .TH PEH-3EKHA2 .TH Heating Cooling Heating Cooling Heating Cooling 22,900 28,300 28,300 26,300 (35,500) 26,300 (35,500) 21,800 (30,000) Capacity w1 6,700 8,300 8,300 7,700 (10,400) 7,700 (10,400) 6,400 (8,800) 2.62 3.33 3.33 Total input 3.54 (5.43) 3.54 (5.43) 2.85 (4.72) PEH-2.5EKHA2 .TH PEH-3EKHA2 .TH Service Ref. Single, 50Hz, 220-240V Single, 50Hz, 220-240V Power supply(phase, cycle,voltage) 0.39 0.39(2.49) 0.39 0.39(2.49) 0.39 0.39(2.
Item Service Ref. PEH-4EKHSA2.TH PEH-5EKHSA2.TH Heating Cooling Cooling Heating 35,500 44,400 33,100 42,300 (43,700) (54,600) Capacity w1 10,400 13,000 9,700 12,400 (12,800) (16,000) 3.63 4.81 3.64 4.86 Total input (6.03) (7.81) PEH-4EKHSA2.TH PEH-5EKHSA2.TH Service Ref. Single, 50Hz, 220-240V Power supply(phase, cycle,voltage) 0.44 0.44(2.84) 0.65 0.65(3.65) Input kW 1.87(11.87) 2.76 2.76(15.20) 1.87 Running current A 2.60(12.6) 3.20 3.20(15.7) 2.
4 DATA 1 PERFORMANCE DATA 1) COOLING CAPACITY Service Ref. PEH-2.5EKHA2.TH PEH-3EKHA2.TH Indoor Intake air W.B.°C Outdoor intake air D.B.°C CA PEH-5EKHSA2.TH CA CA P.C. P.C. CA P.C. CA P.C. CA P.C. 16 6,457 2.28 6,280 2.38 6,049 2.56 5,804 2.75 5,545 2.93 5,271 3.12 18 6,875 2.33 6,694 2.43 6,450 2.62 6,194 2.82 5,926 3.01 5,646 3.20 20 7,297 2.37 7,126 2.48 6,871 2.68 6,606 2.88 6,330 3.09 6,043 3.30 22 7,724 2.42 7,576 2.53 7,314 2.74 7,040 2.95 6,756 3.
2) HEATING CAPACITY Service Ref. PEH-2.5EKHA2.TH PEH-3EKHA2.TH PEH-4EKHSA2.TH PEH-5EKHSA2.TH Indoor Intake air W.B.°C Outdoor intake air D.B.°C CA P.C. CA P.C. CA P.C. CA 15 10 5 0 -5 -10 P.C. CA P.C. CA P.C. 15 4,588 1.79 5,259 1.98 5,994 2.18 6,792 2.39 7,653 2.61 8,576 2.85 20 4,393 1.93 5,052 2.13 5,768 2.34 6,539 2.57 7,366 2.81 8,247 3.07 25 4,222 2.04 4,847 2.27 5,539 2.51 6,297 2.75 7,121 3.02 8,011 3.29 15 5,684 2.27 6,514 2.51 7,425 2.76 8,414 3.
2. PERFORMANCE CURVE Cooling Heating 1.4 1.2 1.0 22 20 18 16 0.8 TOTAL INPUT (RATIO) 1.2 1.0 0.8 1.4 22 20 18 16 1.2 1.0 0.8 0.6 0.4 -5 15 20 25 INDOOR D.B. (°C) 0.6 0.6 1.4 10 CAPACITY (RATIO) INDOOR W.B.(°C) 5 15 25 35 46 OUTDOOR D.B.(°C) INDOOR W.B.(°C) TOTAL INPUT (RATIO) CAPACITY (RATIO) 1.4 25 20 15 1.2 1.0 0.8 0.6 0.4 -12-10 -5 0 5 10 15 OUTDOOR W.B.(°C) INDOOR D.B.
3. FAN PERFORMANCE AND CORRECTED AIR FLOW (1) PEH-2.5EKHA2.TH PEH-3EKHA2.TH Corrected Air flow Capacity Input Cooling 1.05 Correction factor Fan Performance Recommended range Hi 150 0.95 0.9 17 20 1.2 100 50 0 15 17 20 25 30 Air flow (CMM) Lo Correction factor External static pressure(Pa) (1Pa = 0.1mmAq) 200 1.0 25 30 35 Heating 1.15 1.1 1.05 1.0 Air flow (CMM) 0.95 17 20 25 30 Air flow (CMM) (2) PEH-4EKHSA2.TH Corrected Airflow Cooling Fan Performance Correction factor 1.
4. ELECTRICAL DATA Indoor unit ········220V 50Hz 1phase Outdoor unit ·····220V 50Hz 1phase / 380V 50Hz 3phase Service Ref. Indoor unit Outdoor unit Mode PEH-2.5EKHA2.TH PUH-2.5VKA2(.UK) PUH-3VKA2(.UK) Heat Capacity (W) 6,300 Total Input (kW) 2.76 Outdoor unit Indoor unit Cool Input (kW) 0.35 Current (A) 1.62 Starting current (A) 2.1 6,600 (8,400) 2.51 (4.31) 0.35 (2.15) 1.62 (9.80) 2.1 (10.3) Input (kW) 2.41 Current (A) Starting current (A) PEH-3EKHA2.TH Cool Heat 2.
5. STANDARD OPERATION DATA PEH-2.5EKHA2.TH Service Ref. Total Mode Capacity W 6,400 6,700 (8,800) Input kW 2.85 2.62 (4.72) Electrical circuit Volts V Amperes A Outdoor unit Service Ref. Electrical circuit 10,400 13,000 3.33 (5.43) 3.54 3.33 (5.43) 3.54 3.63 (6.03) 3.64 4.81 (7.81) 4.86 1.50 1.50 1.50 1.50 240 240 240 240 1.66 (10.41) 1.66 1.66 (10.41) 1.66 PEH-4EKHSA2.TH PEH-5EKHSA2.TH 1.66 (10.41) 1.66 1.87 (11.87) 1.87 2.76 (15.20) 2.76 PUH-2.
5 OUTLINES AND DIMENSIONS Unit : mm (inch) 1. INDOOR UNITS PEH-2.5EKHA2.TH PEH-3EKHA2.TH 4 672(26 1/2) 600(24) 11 5 710(27 15/16) (11 13/16) 300 1 3 900(36) 345(13 5/8) 2 155 155 59 (3 9/16) 15 22.5 145 562(22 1/8) 130 175 187 125 125 25 21 25 35 85 85 381(15) 730(28 3/4) 40 650(25 5/8) 300(11 13/16) 235(9 1/4) 25 10(3/8) 40 14 220 (8 11/16) 128 (5 1/16) 3.2 286 15 25 171 15 25.
Unit : mm (inch) PEH-4EKHSA2.TH 600(24) (11 13/16) 300 4 942(37 1 16) 980(38 9 16) 11 1 3 35 118 175 200(7 7/8) 187 250 200(7 7/8) 4✕65(=260) 286 65 27.5 3✕65(=195) 27.5 381(15) 1000(3 15 16) 920(36 1 4) 500(19 11 16) 40 Refrigerant-pipe flared connection [9.52 (3/8) Refrigerant-pipe flared connection [19.
Unit : mm (inch) PEH-5EKHSA2.TH 600(24) (11 13/16) 300 1180(46 7 16) 4 1142(44 15 16) 11 11 1 (2 3/4) 530(7 7/8) 70 900(36) 20 11 4✕65(=260) 118 187 27.5 35 110(4 5 16) 1200(47 1 4) 1120(44 1 8) 900(35 7 16) 21 65 27.5 27.5 3✕65(=195) 27.5 381(15) 40 14 250(9 13/16) 98 (3 7/8) 3.2 40 13✕65(=855) 15 65 65 65 65 65 65 65 65 65 65 65 65 65 286 (2 3/4) 70 8 171 15 25.5 130 1160(45 11 16) 65 562(22 1/8) 20 10(3/8) 339(13 3/8) 39.5 39.
Unit : mm (inch) 2. REMOTE CONTROLLER FILTER CHECK MODE TEST RUN TEST RUN 120 FILTER CHECK MODE 050 18 130 83.5 Rear side wiring arrangement opening.
6 WIRING DIAGRAM PEH-2.5/3/4/5EKH(S)A2.TH SYMBOL C CN1 CN2 CN2L CN51 F FS H I.B LCD MF R.B SW1 SW2 SW3 SW5 SW6 NAME FAN MOTOR CAPACITOR PROGRAM TIMER CONNECTOR REMOTE SWITCH CONNECTOR LOSSNAY CONNECTOR CENTRALLY CONTROL CONNECTOR FUSE 16.
7 REFRIGERANT SYSTEM DIAGRAM Unit : mm PEH-2.5EKHA2.TH/PUH-2.5 VKA2(.UK) PEH-3EKHA2.TH/PUH-3 VKA2(.UK) PUH-3 YKA2(.UK) Refrigerant flow in cooling Refrigerant flow in heating R.V.coil Heating:ON Cooling:OFF High pressure control switch Oil separator Refrigerant pipe (option) 15.
8 OPERATION FLOW-CHART MAIN OPERATION START NO Power circuit breaker 1 YES YES Check SW ON twice NO Operation SW ON w1 YES NO “OFF” timer YES NO NO Set time complete “ON” timer YES YES Set time complete NO YES w2 NO Trouble NO Remote controller operation display YES STOP Trouble STOP Operating mode YES (COOL) PROTECTION DEVICE SELF HOLD RELEASE PROTECTION DEVICE SELF HOLD NO Remote controller indicator lamp OFF w3 Remote controller trouble display NO w4 Auxiliary heater OFF w6
COOLING OPERATION COOL operation Four-way valve/OFF w9 NO Compressor thermostat ON YES NO Allowance cancel NO YES 3-minute time delay YES 6-minute time delay NO NO 6 minute time delay NO NO 3-minute compressor operation w10 YES Aliowance period Allowance set Coil frost protection YES YES Coil frost prevention NO w11 NO Cooling area YES NO 10-minute compressor operation NO YES YES Allowance cancel FAN speed LOW YES Coil frost protection NO NO NO Indoor coil temperature is 10°C
DRY OPERATION DRY operation Four-way valve / OFF YES Room tempereature is 18°C or lower w12 NO NO During compressor ON YES 3-minute compressor operation NO NO YES NO w11 Compressor & thermostat ON YES Compressor & thermostat ON NO Compressor ON time completes 10-minute compressor OFF w13 10-minute compressor OFF timer start Compressor ON time set Compressor OFF Compressor ON w14 w14 Fan speed LOW 1 w13 w14 22 NO YES YES w11 w12 w11 NO YES Fan STOP YES 3-minute time delay
HEATING OPERATION w11 Heat operation Heating area YES NO Defrpsting Defrost release NO Defrost 30 min. elapse YES 2 YES Outdoor unit trouble NO Four-way valve ON 1 YES Hor adjust in process NO YES Compressor ON NO w9 YES Compressor thermostat ON 3 min.restart prevention YES Indoor piping 35°C or higher 10-minute compressor operation YES NO Allowance cancel YES Allowance cancel YES 6 min.
9 MICROPROCESSOR CONTROL 1.OUTLINE OF MICROPROCESSOR CONTROL INPUT to remote controller ● OFF-ON switching. ● COOL/DRY-AUTO-HEAT selector switching. ● Thermostat setting. ● TIMER mode selector-switching and Timer setting. ● HIGH-LOW fan speed switching. ● TEST RUN switching. ● CHECK mode switching. (Self diagnostic trouble shooting) Remote controller board ● Processes and transmits orders.orders.
2. INDOOR UNIT CONTROL 2-1COOL operation 1 Press POWER ON/OFF button. 2 Press the button to display “ FILTER ” 3 Press the TEMP button to set the desired temperature. NOTE: Set temperature changes 1°C when the or button is pressed one time. Cooling 19 to 30°C CHECK MODE TEST RUN Operation starts by POWER button ON. Room temperature becomes equal to set temperature. Room temperature rises above set temperature. Operation stops by POWER button OFF.
2-2 DRY operation 1 Press POWER ON/OFF button. 2 Press the button to display “ FILTER 3 Press the CHECK MODE TEST RUN ” TEMP button to set the desired temperature. NOTE: The set temperature changes 1°C when the button is pressed one time. Dry 19 to 30°C Operation starts by POWER button ON. Room temperature becomes equal to set temperature. Room temperature rises above set temperature. Operation stops by POWER button OFF.
4The compressor will not start when the room temperature is below 18°C. The compressor starts intermittent operation when the power is turned ON with room temperature above 18°C. The compressor ON/OFF time depends on the thermostat ON/OFF and the following room temperatures.After 3-minute compressor operation, ● If the room temperature thermistor reads above 28°C with thermostat ON, the compressor will operate for 6 more minutes and then stop for 3 minutes.
2-3 HEAT operation 1 Press POWER ON/OFF button. 2 Press the button to display “ ” FILTER 3 Press the CHECK MODE TEST RUN TEMP button to set the desired temperature. NOTE: The set temperature changes 1°C when the button is pressed one time. Heating 17°C to 28°C or [DEFROST] The [DEFROST] symbol is only displayed during the defrost operation.
(1) Compressor control 13-minute time delay To prevent overload, the compressor will not start within 3, minutes after stop. 2The compressor runs when the room temperature is lower than the set temperature. The compressor stops when the room temperature is equal to or higher than the set temperature. 3The compressor stops in check mode or during protective functions. 4Overheat protection When the indoor coil thermistor reads 70°C or above, the overheat protection will start.
(5) Indoor coil thermistor abnormality detection An abnormality can be detected during compressor ON, except for the following. ●For the first 20 minutes after the temperature difference between the indoor coil temperature and room temperature enters the RANGE C. ●When the temperature difference enters the RANGE C until it moves to the RANGE B.
2-4 AUTO operation (Automatic COOL/HEAT change over operation) 1 Press POWER ON/OFF button. 2 Press the button to display “ FILTER 3 Press the CHECK MODE TEST RUN ” TEMP button to set the desired temperature. NOTE: The set temperature changes 1°C when the or button is pressed one time. Automatic 19 to 28°C ●“AUTOMATIC” works to change by itself the operation mode either to cooling or heating according to the room temperature.
2-6 TIMER operation AUTO STOP ·········The air conditioner stops after the set time lapses. AUTO START ········The air conditioner starts after the set time lapses. AUTO OFF ············Timer is not active. 1. Press POWER ON/OFF button. FILTER CHECK MODE TEST RUN 2. Press “ ” button to select AUTO STOP or AUTO START. 3. Press “ ” button to set desired time. Time setting is in 1 hour units for up to 24 hours. Each time HOURS button is pressed, set time increases by 1 hour.
(1) Indoor coil temperature code During the test run, the indoor coil temperature code from 1 to 15 is displayed on the remote controller instead of room temperature. The code should fall with the lapse of time in normal COOL operation, and should rise in normal HEAT operation.
2-9 Interlock with ventilation system (LOSSNAY) Mr. SLIM/LOSSNAY interlock operation is available by using the optional parts listed below. (1) System organization Relay box (PZ-12RB-E) Relay box Mr. SLIM LOSSNAY LOSSNAY Power supply Mr. SLIM Power supply Remote controller Remote display adapter (PAC-SA88HA-E) LOSSNAY control switch (PZ-05SLB2-E) Remote controller LOSSNAY control switch (PZ-05SLB2-E) (2) LOSSNAY models connectable to Mr.
2-10 Dip switch functions Each figure shows the initial factory setting. 1 On remote controller board (1) SW17(Address selector) 1 2 3 4 5 6 7 8 ON OFF SW17-1~6) For address setting SW17-7) When two remote controllers are used,this switch sets the controller function. OFF:The remote controller is set as a main controller. ON :The remote controller is set as a sub controller. SW17-8) Switch for system back-up (This switch is unavailable for PEH-EKHA.Keep this switch at OFF.
(2) SW2 (Address selector) OFF ON SW2-1 0 2 0 (1) SW2-2 0 2 1 (2) SW2-3 0 2 2 (4) SW2-4 0 2 3 (8) SW2-5 0 2 4 (16) SW2-6 0 2 5 (32) 1 2 3 4 5 6 ON OFF Used in setting the unit-address for group control.
3. OUTDOOR UNIT CONTROL 3-1 Outdoor fan control The rotational frequency of outdoor fan is phase-controlled according to the outdoor coil temperature. This control allows the cooling operation even with the low outside-air temperature and the heating operation even with the high outside-air temperature. 3-2 Outdoor unit control The outdoor unit turns ON/OFF the cooling/heating operation according to orders given from the indoor unit.
3-5 Defrosting in HEAT mode Defrosting starts. Indoor unit Defrosting stops. ON Indoor fan OFF Auto vane 35degrees(SW5-3 OFF)or 20degrees(SW5-3:ON)discharge direction ON OFF Set direction (Remote controller still displays set direction.) Set direction Outdoor unit ON 4-way valve OFF Bypass valve ON OFF Outdoor fan ON OFF Compressor ON OFF (1) Start conditions A. When all of the following conditions are satisfied, defrosting will start.
(3) Defrost interval The defrost interval time is determined as follows. ● Initial defrost interval is 50 minutes. ● The defrost interval after defrosting depends on the preceding defrosting time as shown below. Defrosting operation time 3 minutes or below Next defrost interval 120 minutes 3 to 7 minutes 80 minutes 7 to 10 minutes 60 minutes 10 to 15 minutes 40 minutes 15 minutes (Maximum) 30 minutes NOTE1:If the unit stops during defrosting , the next defrost interval will be 50 minutes.
3-7 Service functions (1) Compulsory defrosting 1When all of the following conditions are satisfied, pressing SW2 starts the compulsory defrosting. ● During HEAT mode ● The compressor is ON. ● The outdoor coil temperature is being displayed by LED. (Outdoor controller board dip switch SW3-1 : OFF, SW3-2 : ON) ● The outdoor coil thermistor reads 8°C or below. 2The operation state and the termination conditions of the compulsory defrosting are the same as those of the normal defrosting.
10 TROUBLESHOOTING 1.TROUBLES IN TEST RUN Symptom Cause Check points The display “CENTRALLY CONTROLLED” on remote controller dose not disappear. 1) Wrong address setting of remote controller/indoor controller board. 2) Timer adapter is connected to the remote controller. 3) Singnal transmission error between indoor unit and remote controller. 1) Check the address setting of remote controller and indoor controller. 2) Make sure the timer adapter is used correctly.
2. SELF DIAGNOSTIC FUNCTION WITH REMOTE CONTROLLER 2-1 When malfunction occurs during operation When a malfunction occurs, the indoor and outdoor units stop and the malfunction is displayed on the LCD of the remote controller. (1) ON the set temperature display part, “CHECK” appears, and the unit address and the check code are diplayed alternately at one-second intervals.
Check Diagnosis of malfunction Cause Check points code EO Signal transmitting/receiving During individual unit control 1) Check the transmission wire. error 1) Bad contact of transmission 2) Check with another remote controller. If “EO” is (Indoor controller does not wire still indicated, replace the indoor controller respond to remote controller 2) Signal transmitting/receiving cirboard. signal.) cuit is abnormal. If other check code appears. replace the original remote controller.
3. SERVICE DATA INDICATION BY SWITCHES ON OUTDOOR CONTROLLER BOARD Setting dip switchs SW2 and SW3 on the outdoor controller board enables LED to show the output state and check code. Output state is shown by LED lighting, and check code by blinking. SW1 : Turning SW1 ON clears the check code. If SW1 is turned ON while the check code is blinking , the indication changes to output state indication. NOTE : SW1 is usually available independant of SW3 setting.
3-1 Outdoor coil temperature To obtain data on the outdoor coil temperature, add the number of bits of lighting LEDs, and see the graph below to find the temperature. C 100 (Short 238 bits) 80 60 Temperature 40 20 0 -20 -40 (Open 8 bits) 0 50 100 150 200 255 Number of bits 3-2 Fan output step To obtain data on the fan output step, add the number of bits of lighting LEDs, and see the graph below to find the fan rotational frequency.
4. TROUBLESHOOTING ACCORDING TO CHECK CODE Blinking Diagnosis of malfunction LED LD1 Reversed phase Cause Check point Phases A1, A2, and A3 are con- Check the power supply connection. nected improperly. LD2 Open phase LD3 Outdoor coil thermistor is ● Outdoor coil thermistor is abnormal. (Open circuit or short broken. circuit) ● Thermistor was connected incorrectly. LD4 High pressure switch (63H2) function ● 62H2 was badly connected. ● 63H2 was working. ● Check 63H2 and the outdoor fan motor.
6. WRONG WIRING ON SITE 6-1 Between remote controller and indoor unit If the wire is disconnected between the remote controller and the indoor unit, nothing is displayed on the remote controller when the POWER button is pressed. The beep sound will also not be heard.
7. OTHER TROUBLES AND CAUSES Unit stops after 5 to 20 seconds operation Power ON/OFF button is not available. Refer to check code on remote controller display. See page 43. Protection function is working. Beep sound is heard, but display is turned OFF. Beep sound is not heard, and display remains OFF. Indoor/outdoor connecting wire is connected incorrectly. Indoor/outdoor connecting wire shorts. Compressor protector is damaged. Deicer is broken. Remote controller is damaged.
11 DISASSEMBLY PROCEDURE 1. INDOOR UNIT (PEH-3EKHA2.TH) OPERATING PROCEDURE 1. Removing the drain pan (1) Unscrew each set screw on the right and left, and remove the drain pan pushing it toward the back. (See Photo 1.) PHOTOS Photo 1 Room temperature thermistor Drain pan 2. Removing the electrical parts (1) Remove the 2 screws and the electrical parts cover. (See Photo 2.
OPERATING PROCEDURE PHOTOS 4. Removing the fan Note : Perform the following with the indoor unit lowered down to the floor. (1) Remove the drain pan. (See Photo 1.) (2) Disconnect the connector for the fan motor. (See Photo 3.) (3) Take out the fan assembly after removing the 7 set screws of the fan plate. (See Photo 5 or 6.) (4) Unscrew four set screws of the bell mouth and remove it. (See Photo 7.) (5) Loosen the set screw of the fan to pull out the sirocco fan. (See Photo 7.
12 PARTS LIST STRUCTURAL PARTS PEH-2.5EKHA1.TH 4 PEH-2.5EKHA2.TH PEH-3EKHA1.TH 3 PEH-3EKHA2.TH 5 7 2 5 6 8 11 10 12 16 17 18 15 9 14 13 1 Q'ty/set No. Part No. Part name 1 E07 035 300 INDOOR FAN MOTOR Price Wiring RecomSpecification PEH-2.5 Remarks Diagram mended PEH-3 Unit Amount (Drawing No.) Symbol Q'ty EKHA 2 .TH EKHA1.
STRUCTURAL PARTS PEH-4EKHSA1.TH PEH-4EKHSA2.TH 9 6 3 8 7 9 10 5 16 17 18 15 12 14 13 1 2 4 Q'ty/set No. Part No. Part name Price Wiring RecomSpecification Remarks Diagram mended PEH-4 Unit Amount (Drawing No.) Symbol Q'ty EKHSA1.TH , EKHSA2.
STRUCTURAL PARTS PEH-5EKHSA1.TH PEH-5EKHSA2.TH 5 6 12 2 13 8 1 3 10 9 11 4 12 17 14 18 19 16 20 15 7 5 Q'ty/set No. Part No. Part name Specification 1 E07 038 300 INDOOR FAN MOTOR PA4V400-EC Price Wiring RecomRemarks Diagram mended Unit Amount (Drawing No.) Symbol Q'ty EKHSA1.TH , EKHSA2.
ELECTRICAL PARTS PEH-2.5EKHA1.TH/PEH-2.5EKHA2.TH PEH-3EKHA1.TH/PEH-3EKHA2.TH PEH-4EKHSA1.TH/PEH-4EKHSA2.TH PEH-5EKHSA1.TH/PEH-5EKHSA2.TH 10 11 13 6 9 5 12 4 1 3 2 7 8 Q'ty/set No. Part No. Part name Specification 1 E07 018 447 INDOOR CONTROLLER BOARD 2 E07 006 382 FUSE 3 — 250V 6.3A CONTROLLER CASE Price Wiring RecomRemarks Diagram mended Unit Amount (Drawing No.) Symbol Q'ty EKH(S)A1.TH , EKH(S)A2.TH PEH-2.5,3,4,5 1 I.B 1 F
13 OPTIONAL PARTS 1. REFRIGERANT PIPES Service Ref. : PEH-2.5EKHA2.TH,PEH-3EKHA2.TH Part No. PAC-05FFS-E PAC-07FFS-E PAC-10FFS-E Pipe length 5m 7m 10m Pipe size O.D. Liquid : {9.52 Gas : {15.88 Connection method Indoor unit : Flared Outdoor unit : Flared Service Ref .: PEH-4EKHSA2.TH,PEH-5EKHSA2.TH Part No. PAC-SC51PI-E PAC-SC52PI-E PAC-SC53PI-E Pipe length 5m 7m 10m Pipe size O.D. Liquid : {9.52 Gas : {19.
2-3. How to connect program timer 2-4. Names and functions WEEKLY TIMER SETTING DISPLAY CURRENT TIME DISPLAY Used for selection of if or not the day operation pattern set by PATTERN SETTING is to be applied in weekly day unit, setting. During MONITOR status, current time is display. During Daily timer setting,a time desire for timer setting is displayed. SET BACK DISPLAY DAILY TIMER SETTING DISPLAY Indicates the setting set back range.
4. MULTIPLE REMOTE CONTROLLER ADAPTER This adapter is needed for remote indication (operation/check). Adapter connection is described on No. OCT01. Part No. PAC-SA88HA-E BRN RED ORN YLW GRN 1 2 3 4 5 5. CENTRALIZED REMOTE CONTROLLER Allows individual or combined control of up to 16 units. When using the PAC-805RC, the program timer adapter (PAC825AD)is also needed. See page 59. Part No. PAC-805RC 5-1. Dimensions Unit : mm 113 56.3 12 23.
5-3 Connection method ! Connections in the power supply cord. 1. Connect the power supply cord to the power supply terminal-block and fix it in-place with a tie-lap. Connect a single phase 200V AC (220, 230, 240V) to AN. As E is the GND terminal, be sure to ground the earth wire. 2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-lap. Use a [1.6 (AWG 14) or above two-wire cable for the transmission line.
6. PROGRAM TIMER ADAPTER This adapter is needed when a program timer(PAC-SK65PT)or a centralized remote controller(PAC-805RC)is used. Part No.
# Connections from adaptor Fig. 3 To program timer or centralized remote controller Adaptor 200-240V AC CN30 CN50 3-core cable 2 5-core cable 5 CN51 Indoor unit Remote controller Maximum length of each cable is 10m. 6-3 Dimensions (Unit : mm) Fig. 4 86 200 95 4 Fixing screw holes 15 s e hol 3 holes 27 22 22 5.5 15 65 18 35 230 40 27 15 80 70 40 35 12 2✕ 2 holes 2.9 7 74 120 8 30 200 7. OPTIONAL REMOTE CONTROLLER This is for the control using two remote controllers.