Specifications

4
PUHZ-RP8, 10YHA
PUHZ-RP8, 10YHA-A
Outdoor unit
Power supply
Phase
Frequency & Voltage
Outdoor unit (A)
Wire No.
32
4
32
4
Models (Outdoor unit)
3N~(3ph 4wires)
50Hz, 380-400-415V
Outdoor unit
Power supply
Input capacity
Main switch/Breaker
Indoor unit/Outdoor unit connecting
Wire No. o size (e)
Remote controller-indoor unit connecting
Wire No. o size (e)
Control circuit rating
Wiring
Cable 2C o 0.69
This wire is accessory of remote controller
(Wire length: 10m, Non-polar)
Indoor unit-Outdoor unit: S1-S2 AC220V-230V-240V
S2-S3 DC24V
Remote controller-Indoor unit: DC14V
RP8 RP10
Cable length 50 m : 3 o 4 (Polar)
Cable length 80 m : 3 o 6 (Polar)
Check items
1. Wiring size must comply with the applicable local and national code.
2. Be careful about choosing the installation location for the earth leakage breaker and how it is installed as the initial electric
current may cause it to malfunction.
3. Power supply cords and indoor unit / Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flex-
ible cord. (design 254 IEC 57)
1
2
S1
S2
S3
S1
S2
S3
Indoor/outdoor
unit connection
cable
Indoor
unit
Unit
power
supply
Outdoor
unit
Remote
controller
L1
L2
L3
N
Grounding
L1
L2
L3
N
1
2
1
2
S1
Indoor
unit
S2
S3
S1
S2
S3
S1
S2
S3
Unit
power
supply
Indoor/outdoor
unit connection
cable
Indoor
unit
Outdoor
unit
Remote
controller
Grounding
1
2
1
2
1
2
S1
S2
S3
S1
S2
S3
S1
S2
S3
S1
S2
S3
Indoor/outdoor
connection cable
Indoor
unit
Unit
power
supply
Indoor
unit
Indoor
unit
Outdoor
unit
Remote
controller
L1
L2
L3
N
Grounding
1:1 system
Synchronized twin, triple and quadruple system
Electrical wiring
Synchronized twin
Synchronized triple
1
2
1
2
S1
S2
S3
S1
S2
S3
S1
S2
S3
1
2
S1
S2
S3
1
2
S1
S2
S3
Indoor/outdoor
connection cable
Indoor
unit
Unit
power
supply
Indoor
unit
Indoor
unit
Outdoor
unit
Remote
controller
L1
L2
L3
N
Grounding
Indoor
unit
Synchronized quadruple
OCT04B-1.qxp 05.11.29 11:23 AM Page 4