Specifications

78
Control modes RemarksControl details
2. Frequency
2-1. Frequency is restricted by the compressor electrical current (CT1).
Frequency control such as Hz-down and no more Hz-up will be conducted
according to the compressor electrical current (CT1).
4. Power supply to
locked compressor
4-1. Compressor energizing method
• Compressor ON/OFF pattern when power is supplied;
• Compressor ON/OFF pattern when power is cut off;
5. 52C
ON/OFF method
52C will turn ON/OFF in the following conditions.
• 52C turns ON when power is supplied, and remains ON regardless of the
compressor’s ON/OFF.
• 52C turns OFF when power is cut off.
W Hz-down amount:
-5Hz per minute
“08” will be displayed
on the LED1 of “A-
Control Service Tool”
while power is
supplied to the
compressor.
w Outdoor temp.
[ 21:
Outdoor temp.
>21:
Cycle :
15 min. ON
30 min. OFF
Models
No more Hz-up Hz-down
12.5 A
24.5A
12.6 A
20.9A
13 A
26A
14 A
22.6A
PUHZ-RP1.6, 2, 2.5, 3VHA
PUHZ-RP4~6VHA
PUHZ-RP4~6YHA
PUHZ-RP8, 10YHA
Models
Correction of
starting current [A]
16
8
15
Correction of
max current [A]
24
13
20
OFF
ON
4hrs
30 min. 30 min. 30 min.
Power supply
30 min.w 30 min. W Repeated
OFF
ON
30 min.
OFF
30 min. 30 min. 30 min.
Comp. stopped
30 min.w
1
111
111
30 min. 30 min.
W Repeated
1 Energized the outside
temperature is 21 or less
PUHZ-RP4~6VHA
PUHZ-RP4~6YHA
PUHZ-RP8, 10YHA
3. Voltage correction
3-1. Voltage is corrected by bus voltage.
Inverter voltage will be corrected by dc bus voltage.
Even though the power supply voltage varies within i10%, the voltage should
be corrected in order to make the output voltage of inverter stable.
3-2.
Voltage correction by compressor’s electric current (CT1). (PUHZ-RP4 to 6V only)
Output voltage of inverter is corrected by compressor’s electric current (CT1).
W2. Actual values of V/F will be almost the same as the V/F line on the graphic
chart because the inverter control is based on voltage and frequency.
However, they may not exactly match the V/F line on the graphic chart
because voltage correction control makes an effect on the performance.
500
400
300
200
100
0
050
Operating frequency (Hz)
PUHZ-RP4~6YHA
Voltage (V)
100 150
W2
500
400
300
200
100
0
050
Operating frequency (Hz)
PUHZ-RP8, 10YHA
Voltage (V)
100 150
W 2
From the previous page.