OC129A-1.qxp 01.10.1 7:33 PM Page 1 1997 SPLIT-TYPE,AIR CONDITIONERS No. OC129 REVISED EDITION-A TECHNICAL & SERVICE MANUAL Series PK Wall Mounted Indoor unit [ Model names ] [ Service Ref. ] 1997, 1999, 2001 PK-2.5FLA 1997 1999 PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2 PK-3FLA PK-3FLA2 PK-4FLSA PK-4FLSA2 PK-1.6FLA PK-2FLA PK-3FLA3 2001 PK-2.5FLA3 PK-2.5FLA4 PK-3FLA4 PK-3FLA5 PK-4FLSA3 PK-4FLSA4 CONTENTS Indoor unit ˚C AM PM AM PM NOT AVAILABLE ON / OFF TEMP PK-1.6FLA3 PK-2.
OC129A-1.qxp 01.10.
OC129A-1.qxp 01.10.1 7:33 PM 1 Page 3 TECHNICAL CHANGES PK-3FLA2 ➔ PK-3FLA3 PK-2.5FLA3 ➔ PK-2.5FLA4 PK-3FLA4 ➔ PK-3FLA5 PK-4FLSA3 ➔ PK-4FLSA4 ● Outdoor units has changed. ● The parts No. of REMOTE CONTROLLER has changed. (The following parts numbers are interchangeable.) PK-2.5FLA2 ➔ PK-2.5FLA3 PK-3FLA3 ➔ PK-3FLA4 PK-4FLSA2 ➔ PK-4FLSA3 ● ● ● ● NOSE has changed by changing its shape. UNDER PLATE has changed. BOX ASSEMBLY has changed by changing its shape.
OC129A-1.qxp 01.10.1 7:33 PM Page 4 ●Remote controller ● When cover is closed. display PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2, PK-2.5FLA3 PK-3FLA2, PK-3FLA3, PK-3FLA4 PK-4FLSA2, PK-4FLSA3 Part No. [ T7W 570 200 ] display SET TEMP. display indicates desired temperature set. OPERATION MODE display Operation mode display indicates which operation mode is in effect. • CHECK • TEST RUN display CHECK&TEST RUN display indicates that the unit is being checked or test-run.
OC129A-1.qxp 01.10.1 7:33 PM Page 5 ●Wireless remote controller ● When cover is open. PK-2.5FLA4 PK-3FLA5 PK-4FLSA4 Part No. [ T7W E06 714 ] CHECK TEST RUN display CHECK&TEST RUN display indicates that the unit is being checked or test-run. MODEL SELECT display display Blinks when model is selected. Lights up while transmission to the indoor unit is mode using switches. display SET TEMP. display indicates desired temperature set. CLOCK display display Displays the current time.
OC129A-1.qxp 01.10.1 7:33 PM 4 Page 6 SPECIFICATIONS 1. STANDARD SPECIFICATION Service Ref. Item Indoor, Outdoor D.B./W.B.°C Condition Capacity w1 Btu/h W kW REFRIGERANT PIPING OUTDOOR UNIT INDOOR UNIT Total input w1 Service Ref. Power supply(phase, cycle,voltage) Input kW Running current (Power factor) A (%) Starting current A External finish Heat exchanger Fan(drive) o No.
OC129A-1.qxp 01.10.1 7:33 PM Page 7 Service Ref. PK-2.5FLA2 PK-2.5FLA3 PK-2.5FLA4 Item 27/19.0°C, 35/24°C Cooling (JIS B8616) Indoor, Outdoor D.B./W.B.°C Condition Capacity w1 Btu/h W kW OUTDOOR UNIT INDOOR UNIT Total input w1 Service Ref. Power supply(phase, cycle,voltage) Input kW Running current (Power factor) A(%) Starting current A External finish Heat exchanger Fan(drive) o No.
OC129A-1.qxp 01.10.1 7:33 PM Page 8 Service Ref. PK-3FLA2 Item Indoor, Outdoor D.B./W.B.°C 27/19.0°C, 35/24°C Cooling (JIS B8616) Condition Capacity w1 Btu/h W kW 24,600 7,200 27,300 8,000 3.54 REFRIGERANT PIPING OUTDOOR UNIT INDOOR UNIT 3.28 / 3.30 3.28 / 3.30 Total input w1 PK-3FLA2 Service Ref. Single, 50Hz, 220/240V Single, 60Hz, 220V Power supply(phase, cycle,voltage) 0.095 / 0.095 0.095 kW Input 0.44 / 0.44 (98/90) 0.44 (98) A(%) Running current (Power factor) 0.7 / 0.8 0.
OC129A-1.qxp 01.10.1 7:33 PM Page 9 Service Ref. PK-3FLA3 PK-3FLA4 PK-3FLA5 Item Indoor, Outdoor D.B./W.B.°C 27/19°C , 35/24°C Cooling (JIS B8616) Condition 27,300 8,000 3.28 / 3.30 3.28 / 3.30 3.54 Total input w1 PK-3FLA3 PK-3FLA4 PK-3FLA5 Service Ref. Single, 50Hz, 220/240V Single, 60Hz, 220V Power supply(phase, cycle,voltage) 0.095 / 0.095 0.095 Input kW 0.44 / 0.44 (98/90) 0.44 (98) Running current (Power factor) A(%) 0.7 / 0.8 0.7 Starting current A External finish Munsell 3.4Y 7.7/0.
OC129A-1.qxp 01.10.1 7:33 PM Page 10 Service Ref. Item Indoor, Outdoor D.B./W.B.°C Condition Capacity w1 Btu/h W kW 27/19°C , 35/24°C Cooling (JIS B8616) 25,600 7,500 2.75 PK-3FLA2 PK-3FLA3 PK-3FLA4 PK-3FLA5 Single, 50Hz, 220V 0.095 0.44 (98) 0.7 Munsell 3.4Y 7.7/0.8(White) Plate fin coil Line flow (direct) o 2 0.
OC129A-1.qxp 01.10.1 7:33 PM Page 11 Service Ref. PK-4FLSA2 PK-4FLSA3 PK-4FLSA4 Item 27/19.0°C, 35/24°C Cooling (JIS B8616) Indoor, Outdoor DB/WB°C Condition 37,500 11,000 3.46 / 3.63 3.40 / 3.47 4.38 Total input w1 PK-4FLSA2 PK-4FLSA3 PK-4FLSA4 Service Ref. Single, 50Hz, 220/240V Single, 60Hz, 220V Power supply(phase, cycle,voltage) 0.114 / 0.114 0.114 kW Input 0.53 / 0.53 (98/90) 0.53 (98) A(%) Running current (Power factor) 0.8 / 0.9 0.8 A Starting current Munsell 3.4Y 7.7/0.
OC129A-1.qxp 01.10.1 7:33 PM Page 12 2. POWER SUPPLY & MODEL NAMES Power supply 1ph 50Hz 60Hz Service Ref. (Outdoor unit) Service Ref. (Indoor unit) PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2 PK-3FLA2 PK-3FLA3 PK-2.5FLA3 PK-3FLA4 PK-2.5FLA4 PK-3FLA5 PU-3VJA2 PU-3VJC PU-1.6VLJA2 PU-2VJA2 PU-2.5VJA2 220,230,240V PU-3VJB PU-3VJB 3ph 380/220,400/230,415/240V — — 1ph 220V — PU-2NJA1 3ph 220V — — — (1) Rating conditions JIS B8615, 8616 Series PK Indoor Unit (Single Phase) PU-3YJC PU-3YJB PU-3YJB PU-2.
OC129A-1.qxp 01.10.1 7:33 PM 5 Page 13 DATA 1. PERFORMANS DATA W Outdoor unit PU-3JB COOLING CAPACITY 50Hz Service Ref. Temperature Outdoor D.B. Indoor W.B. 16˚C (60.8˚ F) 18˚C (64.4˚ F) 21˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (69.8˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 25˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (77˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 30˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (86˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 32.
OC129A-1.qxp 01.10.1 7:33 PM Page 14 COOLING CAPACITY 60Hz Service Ref. Temperature Outdoor D.B. PK-2.5FLA3/4 T.C. C.F. (T.I.) 7.2 0.81 7.6 0.82 7.9 0.83 8.0 0.83 8.1 0.84 8.6 0.86 7.0 0.84 7.5 0.85 7.7 0.86 7.8 0.86 8.0 0.87 8.5 0.89 6.8 0.90 7.2 0.92 7.4 0.93 7.5 0.93 7.7 0.94 8.2 0.96 6.6 0.93 7.1 0.95 7.3 0.96 7.4 0.97 7.5 0.97 8.0 0.99 6.5 0.96 6.9 0.99 7.2 1.00 7.2 1.00 7.4 1.01 7.9 1.04 6.2 1.03 6.6 1.06 6.8 1.07 6.9 1.08 7.1 1.08 7.5 1.11 6.2 1.04 6.6 1.06 6.8 1.08 6.9 1.08 7.0 1.09 7.5 1.12 5.
OC129A-1.qxp 01.10.1 7:33 PM Page 15 2. STANDARD OPERATION DATA PK-1.6 FLA3 Service Ref. Outdoor Indoor side side Refrigerant circuit Electrical circuit Total MODE Capacity Input Indoor unit Service Ref. Cooling Cooling Cooling 3900 5600 4600 1.49 2.52 2.60 PK-1.6 PK-2FLA3 FLA3 W kW Phase , Hz Volts Amperes Outdoor unit Service Ref.
OC129A-1.qxp 6 01.10.1 7:33 PM Page 16 OUTLINES AND DIMENSIONS Unit : mm 1. REMOTE CONTROLLER 57 18 3 58 19 CHECK TEST RUN MODEL SELECT ˚C AMPM ˚C AM PM AMPM NOT AVAILABLE AM PM ON/OFF NOT AVAILABLE TEMP 162 153 ON / OFF TEMP 55 PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2, PK-2.5FLA3 PK-3FLA2, PK-3FLA3, PK-3FLA4 PK-4FLSA2, PK-4FLSA3 PK-2.
Front (Height ut unit) 68- 5 hole 53 491 476 450 405 Gas pipe position Liquid pipe position 2 X5 - 2.9 hole for tapping screw Knock out hole for left-rear piping Tapping screw 277 300 0 45 85 80 5 2.
37 74 A 30 32-ø12 hole for bolt 66-ø6 hole for tapping screw Wall fixture 100 4 39 225 18 39 990 180 12-ø6 hole for tapping screw 240 on left-hand side C 30 455 39 610 91 314 285 19 245 90 25 Drain hose for left-hand side piping Knock out hole for left piping Left side Range for left rear piping opening 280 Drainage range on right-hand side 37 74 Unit center 10 91=(910) 900 18 Drainage range 98 32 B 37 65 Knock out hole for piping A 100 4 340 30 10 184 30 30 80 29 280
295 225 39 180 314 285 19 245 90 Range for left rear piping opening 280 750 Drainage range 91 on right-hand side 595 12-ø6 hole for tapping screw 240 25 Knock out hole for left piping 340 Drain hose for left-hand side piping 37 74 C 30 13 91=(1183) 900 Drainage range on left-hand side 18 Range for left rear piping opening 41-ø12 hole for bolt 18 1270 Unit center 98 32 Wall fixture 39 B 37 65 Knock out hole for wiring Unit out line 37 74 A 30 84-ø6 hole for tapping screw
OC129A-1.qxp 01.10.1 7:33 PM 7 Page 20 WIRING DIAGRAM L N PK-1.6FLA3 PK-2FLA3 POWER SUPPLY ~(1 PHASE) AC220-240V 50Hz AC220V 60Hz GRN/YLW 10.6VAC 220V TB2 YLW RED 240V 14.5VAC T MV 7 W.B SW1 LS ORN 230V 7 MF LD1 CNB W.R 1 3 5 FAN CNV VANE POWER 12345678 12345 CN28 1 2 3 4 5 6 WHT 2 1 ON OFF L.TEST CN70 WIRELESS TO OUTDOOR UNIT CONNECTING WIRES DC12V RT1 VANE TWIN.1 SW2 CN2 TWIN.
OC129A-1.qxp 01.10.1 7:33 PM Page 21 PK-2.5FLA2, PK-2.5FLA3, PK-2.5FLA4 PK-3FLA2, PK-3FLA3, PK-3FLA4 , PK-3FLA5 PK-4FLSA2, PK-4FLSA3, PK-4FLSA4 L N POWER SUPPLY ~(1 PHASE) AC220-240V 50Hz AC220V 60Hz GRN/YLW 10.6VAC 220V MF TB2 RED ORN YLW 230V C 14.5VAC BRN RED BRN RED LD1 SW1 7 FAN1 CND 1 3 1 3 5 F2 4 3 2 1 CN4T TRANS 1 3 CNT TRANS POWER F1 6 X4 6 1 SW3 7 MODELS PK-2.5FLA PK-3FLA ON OFF NAME FAN MOTOR CAPACITOR TIMER ADAPTOR CONNECTOR TRANSMISSION WIRES No.
OC129A-1.qxp 8 01.10.1 7:33 PM Page 22 REFRIGERANT SYSTEM DIAGRAM PK-1.6FLA3 / PU-1.6VLJA2 PK-2FLA3 / PU-2VJA2, PU-2NJA1 INDOOR UNIT PK-1.6 PK-2 Low pressure switch Refrigerant pipe [15.88(5/8) (with insulator) option Charge pIug Flexible tube Ball valve Distributor Indoor heat exchanger Check plug OUTDOOR UNIT PU-1.
OC129A-1.qxp 01.10.1 7:33 PM Page 23 PK-3FLA3, PK-3FLA4, PK-3FLA5 / PU-3VJC , PU-3YJC Refrigerant pipe [15.88(5/8") (with insulator) option Low pressure Flexible tube strainer switch Indoor heat exchanger Ball valve strainer Charge pIug High pressure switch Outdoor heat exchanger Check pIug Flared connection strainer Flared connection Indoor coil thermistor RT2 Accumulator Compressor Capillary tube Distributor with strainer (O.D.3.2 o I.D.1.8 o L800) o2pcs Ball valve (with service port) D.
OC129A-1.qxp 9 01.10.1 7:33 PM Page 24 OPERATION FLOW-CHART 1. Main operation START 1 NO POWER SUPPLY Live YES NO NO ON/OFF button ON YES Protection device Self hold reset STOP YES Abnormal operation mode Protection device Self hold NO POWER lamp ON Self-diagnostic function Indicate & Memory EMERGENCY ALL STOP MODE SELECT button DRY COOL COOL OPERATION DRY OPERATION Note1. The unit starts operation by pressing the ON/OFF switch when unit is OFF.
OC129A-1.qxp 01.10.1 7:33 PM Page 25 2. COOL operation YES COOL operation 3 min.
OC129A-1.qxp 01.10.1 7:33 PM Page 26 3. DRY operation Dry operation YES Room temperature 18°C or below NO Compressor ON NO YES Compressor ON 3 min. elapse NO NO Compressor ON 3 min.
OC129A-1.qxp 01.10.1 7:33 PM 10 Page 27 MICROPROCESSOR CONTROL 1. OUTLINE OF MICROPROCESSOR CONTROL REMOTE CONTROLLER INPUT to remote controller ●Processes and transmits orders. OUTPUT to remote controller ● Indication LCD lights. ● OFF-ON switching. ● COOL • DRY • FAN selector switching. ● HIGH-LOW fan speed switching. ● TIMER mode selector-switching ● Timer setting. ● Self diagnostic troubleshooting. ● TEST RUN switching. ● CHECK mode switching. ● AUTO Vane setting.
OC129A-1.qxp 01.10.1 7:33 PM Page 28 2. INDOOR UNIT CONTROL 2-1COOL operation 1 Press [ ON/OFF button. 2 Press MODE button to set operation mode to COOL ˚C . / / 3 Set desired temperature with or button. button. NOTE: 1. Set temperature changes by 1 °C in the range 19-30 °C AM PM AM PM NOT AVAILABLE ON / OFF / / each TEMP or button is pressed. 2. Set temperature is displayed on the LCD. TEMP PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2/3 PK-3FLA2/3/4 PK-4FLSA2/3 PK-2.
OC129A-1.qxp 01.10.1 7:33 PM Page 29 5 Coil frost protection When the indoor coil temperature becomes - 15°C or below, coil frost protection will proceed as follows. After the compressor has been continuously operated for 3 minutes or more, and the indoor coil temperature has been 15°C or below for 3 minutes, the coil frost protection will start. Compressor stops for 6 minutes, and then restarts.
OC129A-1.qxp 01.10.1 7:33 PM Page 30 2-2 DRY operation 1 Press [ ON/OFF button. ˚C 2 Press MODE button to set operation mode to DRY AM PM . / / 3 Set desired temperature with or button. NOTE: 1. Set temperature changes by 1 °C in the range 19-30 °C AM PM NOT AVAILABLE ON / OFF / / each TEMP or button is pressed. 2. Set temperature is displayed on the LCD. TEMP PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2/3 PK-3FLA2/3/4 PK-4FLSA2/3 PK-2.
OC129A-2.qxp 01.10.1 7:33 PM Page 31 (2) Indoor fan control The indoor fan runs on LOW speed during compressor operation. The fan speed cannot be changed with the remote controller. Also, the indoor fan does not run during compressor OFF. (3)Auto vane control Same as in COOL operation. (4)Detecting abnormalities in the outdoor unit An abnormality in the outdoor unit can not be detected in DRY operation. 2-3 FAN operation 1 Press POWER ON/OFF button.
OC129A-2.qxp 01.10.1 7:33 PM Page 32 Measure an impedance between the power supply terminal block and ground with a 500V Megger and check that it is equal to or greater than 1.0M". 2-5 Test run PK-1.6FLA3, PK-2FLA3 PK-2.5FLA2/3, PK-3FLA2/3/4 PK-4FLSA2/3 (1) Turn on the main power of unit. (2) Turn the adjusting switch on the back of the wireless remote controller to “SET” CHECK and TEST RUN will start flashing. Wireless remote controller with backside battery cover removed Display will start finishing.
OC129A-2.qxp 01.10.1 7:33 PM Page 33 2-6 Emergency operation When the remote controller or microprocessor malfunctions and no other trouble exists, emergency operation is available by setting the dip switch on the controller board. [Check items] (1) Make sure the compressor and the fans are running normally. (2) Locate the trouble with the self-diagnostic function.
OC129A-2.qxp 01.10.1 7:33 PM Page 34 SW1-4 ~ SW1-6) Switch for capacity of each model PK-1.6 PK-2.5 PK-3 PK-2 ON OFF PK-4 ON OFF 4 5 6 ON OFF 4 5 6 4 5 6 SW1-7 ~ SW1-8) Switch for the pair number of wireless remote controller 0 1 ON OFF 2 ON OFF 7 8 ON OFF 7 8 3 ON OFF 7 8 7 8 The pair number setting of the wireless remote controller is needed. (Refer to the next page for the details.
OC129A-2.qxp 01.10.1 7:33 PM Page 35 2-8 Wireless remote controller pair number setting operation PK-1.6FLA3, PK-2FLA3 PK-2.5FLA2/3, PK-3FLA2/3/4 PK-4FLSA2/3 Switches are located on the indoor unit PC board and inside the remote controller as shown. • Setting the SW1 (PC board inside indoor unit) Sub-switches 7 or 8 of SW1 can be used as follows to assign a pair No.
OC129A-2.qxp 01.10.1 7:33 PM 11 Page 36 TROUBLESHOOTING 1. Self-diagnostic function [for PK-1.6FLA3, PK-2FLA3, PK-2.5FLD2/3, PK-3FLD2/3/4, PK-4FLSD2/3 ] (1) Turn on the main power of the unit. (2) Set the adjusting switch on the back of the wireless remote controller to “Set” CHECK and TEST RUN will start lighting. Remove the battery cover on the back side of the wireless remote controller, display will start flashing when the “Set” switch is turned on.
OC129A-2.qxp 01.10.1 7:33 PM Page 37 1. Self-diagnostic function [for PK-2.5FLA4, PK-3FLA5, PK-4FLSA4] 1 Turn on the main power to the unit. CHECK 2 Press the button twice continuously. • begins to light and refrigerant address display “00” begins to blink.
OC129A-2.qxp 01.10.1 7:33 PM Page 38 3. How to check the parts PK-1.6FLA3, PK-2FLA3, PK-2.5FLA2/3/4, PK-3FLA2/3/4/5, PK-4FLSA2/3/4 Parts name Check points Room temperature thermistor (RT1) Pipe temperature thermistor (RT2) Disconnect the connector, then measure the resistance using a tester. (Surrounding temperature 10°C~30°C) Transformer Disconnect the connector and measure the resistance using a tester. Normal 4.3k'~9.
OC129A-2.qxp 01.10.1 7:33 PM 12 Page 39 DISASSEMBLY PROCEDURE PK-1.6FLA3, PK-2FLA3, PK-2.5FLA2/3/4, PK-3FLA2/3/4/5, PK-4FLSA2/3/4 OPERATING PROCEDURE PHOTOS&ILLUSTRATION 1. Removing the lower side of the indoor unit from the installation plate (1) Remove the 2 screws. Hang the indoor unit hangers to the catches on the installation plate. Figure 1 Hanger of indoor unit Catch of installation plate Metal fixture Screws 2.
OC129A-2.qxp 01.10.1 7:33 PM Page 40 OPERATING PROCEDURE PHOTOS&ILLUSTRATION (9) Remove the screws of the indoor controller board case, and pull out the indoor controller board case. Then the transformer and the capacitor and relay can be serviced. Photo 3 Relay Transformer Capacitor Indoor controller board case 5. Removing the vane motor (1) Remove the right side panel. (2) Remove the screw of the electrical parts box cover, and remove the cover.
OC129A-2.qxp 01.10.1 7:33 PM Page 41 OPERATING PROCEDURE PHOTOS 8. Removing the lineflow fan and the fan motor (1) Remove the left and right side panels. (2) Remove the grills. (3) Remove the electrical parts box. (4) Remove the drain pan. (5) Loosen the screw that fixes the lineflow fan to the fan motor. (See Photo 7. ) (6) Remove the 4 screws of the motor fixture, and remove the fan motor and the motor fixture at a time (See Photo 8.
OC129A-2.qxp 13 01.10.1 7:33 PM Page 42 PARTS LIST STRUCTURAL PARTS PK-1.6FLA, PK-1.6FLA1, PK-1.6FLA2, PK-1.6FLA3 PK-2FLA, PK-2FLA1, PK-2FLA2, PK-2FLA3 Q'ty/set No. 1 Part No. Part name R01 KV5 651 FRONT PANEL Specification PK-1.
OC129A-2.qxp 01.10.1 7:33 PM Page 43 STRUCTURAL PARTS PK-2.5FLA, PK-2.5FLA1, PK-2.5FLA2, PK-2.5FLA3, PK-2.5FLA4 9 10 8 1 12 2 3 7 6 4 5 Part number that is circled is not shown in the figure. Q'ty/set No. Part No. Part name Specification PK-2.5 PK-2.
OC129A-2.qxp 01.10.1 7:34 PM Page 44 STRUCTURAL PARTS PK-3FLA, PK-3FLA1, PK-3FLA2, PK-3FLA3, PK-3FLA4 , PK-3FLA5 10 9 8 1 12 2 3 7 6 4 5 Part number that is circled is not shown in the figure. Q'ty/set PK-3 PK-3 PK-3 FLA FLA1 FLA2 FLA3 FLA4 FLA5 1 R01 12G 662 LEFT SIDE PANEL 1 1 1 R01 12G 812 UNDER PLATE 1 1 No. 2 3 Part No.
OC129A-2.qxp 01.10.1 7:34 PM Page 45 STRUCTURAL PARTS PK-4FLSA, PK-4FLSA1, PK-4FLSA2, PK-4FLSA3, PK-4FLSA4 10 9 8 1 12 2 3 7 6 4 5 Part number that is circled is not shown in the figure. Q'ty/set No. Part No.
OC129A-2.qxp 01.10.1 7:34 PM Page 46 ELECTRICAL PARTS PK-1.6FLA, PK-1.6FLA1, PK-1.6FLA2, PK-1.
OC129A-2.qxp 01.10.1 7:34 PM Page 47 Parts number that is circled is not shown in the figure. Q'ty/set No. Part No. Part name Specification PK-1.
OC129A-2.qxp 01.10.1 7:34 PM Page 48 ELECTRICAL PARTS PK-2.5FLA, PK-2.5FLA1, PK-2.5FLA2, PK-2.5FLA3, PK-2.5FLA4 PK-2.5FLA PK-2.5FLA1 PK-2.5FLA2 PK-2.5FLA3 37 1 32 2 35 38 36 34 3 33 4 PK-2.5FLA4 32 31 26 5 30 29 25 28 24 27 6 23 22 7 8 21 20 9 11 19 16 10 12 17 13 14 Q'ty/set No. Part No. Part name Price Wiring RecomPK-2.5 Remarks. Diagram mended Specification (Drawing No.
OC129A-2.qxp 01.10.1 7:34 PM Page 49 Q'ty/set No. Part No. Part name Price Wiring RecomRemarks. Diagram mended Specification (Drawing No.) 1 Symbol Q'ty Unit Amount FLA FLA FLA 3 FLA4 FLA2 PK-2.
OC129A-2.qxp 01.10.1 7:34 PM Page 50 ELECTRICAL PARTS PK-3FLA, PK-3FLA1, PK-3FLA2, PK-3FLA3, PK-3FLA4 , PK-3FLA5 PK-3FLA PK-3FLA1 PK-3FLA2 PK-3FLA3 PK-3FLA4 37 1 32 2 35 38 36 34 3 33 4 PK-3FLA5 32 31 26 5 30 29 25 28 24 27 6 23 22 7 8 21 20 9 11 19 16 10 12 17 13 14 Q'ty/set No. Part No. Part name Price Wiring RecomPK-3 Remarks. Diagram mended Specification (Drawing No.
OC129A-2.qxp 01.10.1 7:34 PM Page 51 Q'ty/set No. Part No. Part name Price Wiring RecomRemarks. Diagram mended Specification (Drawing No.
OC129A-2.qxp 01.10.1 7:34 PM Page 52 ELECTRICAL PARTS PK-4FLSA, PK-4FLSA1, PK-4FLSA2, PK-4FLSA3, PK-4FLSA4 PK-4FLSA PK-4FLSA1 PK-4FLSA2 PK-4FLSA3 37 1 32 2 35 38 36 34 3 33 4 PK-4FLSA4 32 31 26 5 30 29 25 28 24 27 6 23 22 7 8 21 20 9 11 19 16 10 12 17 13 14 Q'ty/set No. Part No. Part name Price Wiring RecomPK-4 Remarks. Diagram mended Specification (Drawing No.
OC129A-2.qxp 01.10.1 7:34 PM Page 53 Q'ty/set No. Part No. Part name Price Wiring RecomPK-4 Remarks. Diagram mended Specification (Drawing No.
OC129A-2.qxp 14 01.10.1 7:34 PM Page 54 OPTIONAL PARTS 1. REFRIGERANT PIPES Service Ref. : PK-1.6FLA3, PK-2FLA3, PK-2.5FLA2, PK-2.5FLA3, PK-2.5FLA4, PK-3FLA2, PK-3FLA3, PK-3FLA4, PK-3FLA5, Part No. Pipe lenght PAC-05FFS-E PAC-07FFS-E PAC-10FFS-E PAC-15FFS-E 5m 7m 10m 15m Liquid:{9.52 Gas:{15.88 Pipe size O.D. Indoor unit:Flared Outdoor unit:Flared Pipe size O.D. Service Ref. : PK-4FLSA2, PK-4FLSA3, PK-4FLSA4 PAC-SC51PI-E Part No.
OC129A-2.qxp 01.10.1 7:34 PM Page 55 4. CENTRALIZED REMOTE CONTROLLER Allows individual or combined control of up to 16 units. PAC-805RC Part No. Unit : mm 4-1. Dimensions 113 56.3 12 23.
OC129A-2.qxp 01.10.1 7:34 PM Page 56 4-3 Connection method (1) Connections in the power supply cord. 1. Connect the power supply cord to the power supply terminal-block and fix it in-place with a tie-wrap. Connect a single phase 200V AV (220, 230, 240V) to A N . As E is the GND terminal, be sure to ground the earth wire. 2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap. Use a Ω1.6 (AWG 14) or above two-wire cable for the transmission line.
OC129A-2.qxp 01.10.1 7:34 PM Page 57 5. PROGRAM TIMER ADAPTER This adapter is needed when a program timer(PAC-815PT)or a centralized remote controller(PAC-805RC)is used.
OC129A-2.qxp 01.10.1 7:34 PM Page 58 2. Set the address number (from SW1-1 to SW1-6) in the dip switch when a centralized remote controller is being used. The address is the control number of each unit in the centralized control system. As the address serves as a time-delay device as well, sequential starts (all units are triggered collectively by one single ON instruction) must be set with different address numbers (greater than O) for each adapter.
OC129A-2.qxp 01.10.1 7:34 PM Page 59 6. TIMER Model Name Product Name PAC-SK65PT Program timer (The PAC-SK65PT can only be used together with the PAC-825AD) 6-1 Program timer specifications Program Timer PAC-SK65PT Wall mount Quarts clock +50 second/month Liquid crystal display Liquid crystal display 24 hours 30 minutes 48/day — — 5V DC Not provided Product name Model name. Mounting method Clock system Clock accuracy Time Week Display Program cycle Timer setting unit Number.
OC129A-2.qxp 01.10.1 7:34 PM Page 60 6-4. Name and functions (PAC-SK65PT) MODE selector button : Used to select \MONITOR" or "SET" mode. "MONITOR" : Indicates the current timer setting. All buttons except SET/MONITOR will not work.This is the normal status. "SET" : "SET" is used to set the time, change the day of the week, and program the daily and weekly timer. Mode display Current time display Current day display Weekly timer display Clock adjustment button : Used to adjust the current time.