Submittal
P-SERIES
Specications are subject to change without notice. © 2015 Mitsubishi Electric US, Inc.
Job Name:
System Reference: Date:
Indoor Unit: PLA-A42BA6
Outdoor Unit: PUZ-A42NHA6 (-BS)
UNIT OPTION:
□ Standard Model......................................................................PUZ-A42NHA6
□ Seacoast (BS) Model.......................................................PUZ-A42NHA6-BS
ACCESSORIES:
Indoor Unit
□ Condensate Pump (BlueDiamond X87-711/721; 115/230V)
□ Condensate Pump (Sauermann SI30-115/230; 115/230V)
□ iSee Corner Panel (PAC-SA1ME-E)
□ Multifunction Casement / MERV 10 Filter (PAC-SH53TM-E / PAC-SH59KF)
□ Air Outlet Plates (PAC-SH51SP-E)
Outdoor Unit
□ Wind Bafe (WB-PA2 [x2])*
*Allows operation to 0º F (-18º C).
□ Air Outlet Guide (PAC-SG59SG-E [x2])
□ Mounting Base (QSMS1202)
□ Wall Bracket (QSWB2000M-1)
Controls
□ Wireless Controller (MHK1)
□ Advanced Wired Controller (PAR-31MAA)
□ Simple Wired Controller (PAC-YT53CRAU)
□ M-NET Adapter (PAC-SF83MA-E)
□ Temperature Sensor (PAC-SE41TS)
SPECIFICATIONS:
Rated Conditions (Capacity / Input)*
Cooling
Btu/h / W
42,000 / 4,600
Heating at 47
o
F
Btu/h / W
45,000 / 4,450
Heating at 17
o
F
Btu/h / W
30,000 / 4,300
* Rating Conditions per AHRI Standard:
Cooling | Indoor: 80º F (27º C)DB / 67º F (19º C)WB; Outdoor: 95º F (35º C)DB / 75º F (24º C)WB
Heating at 47ºF | Indoor: 70º F (21º C)DB / 60º F (16º C)WB; Outdoor: 47º F (8º C)DB / 43º F (6º C)WB
Heating at 17º F | Indoor: 70º F (21º C)DB / 60º F (16º C)WB; Outdoor: 17º F (-8º C)DB / 15º F (-9º C)WB
Capacity Range
Cooling
Btu/h
18,000 - 42,000
Heating at 47
o
F
Btu/h
18,000 - 48,000
Operating Range
Cooling
0º F** to 115º F (-18º C to 46º C) DB
Heating
12º F to 70º F (-11º C to 21º C) DB
** The minimum temperature will be 23º F (-5º C) DB if optional wind bafe accessory is not installed.
AHRI Efciency Ratings
EER
9.1
SEER
14.4
HSPF
9.3
COP at 47
o
F
2.96
COP at 17
o
F
2.05
Electrical Power
Requirements
208 / 230V, 1-Phase, 60 Hz
Minimum Circuit Ampacity (MCA)
Indoor / Outdoor
A
2 / 26
Indoor Unit
Fan Motor (ECM)
F.L.A.
1.00
Fan Motor Output
W
120
SHF / Moisture Removal
0.71 / 10.9 pt./h
Drain Lift Mechanism
(Included)
H: In.
33-7/16
Outdoor Unit
Compressor
DC INVERTER-driven Twin Rotary
Fan Motor (ECM)
F.L.A.
0.4+0.4
MOCP
A
40
Airow Rate (Low-M1-M2-Hi)
Indoor
(Cooling)
DRY
CFM
780-880-990-1,090
WET
740-850-950-1,060
Outdoor DRY
3,530
Sound Pressure Level
Indoor (Low-M1-M2-Hi)
dB(A)
34-36-39-41
Outdoor
Cooling
51
Heating
55
External Dimensions
Indoor (H x W x D)
In.(mm)
11-3/4 x 33-1/16 x 33-1/16
(298 x 840 x 840)
Outdoor (H x W x D)
53-1/8 x 37-3/8 x 13 + 1-3/16
(1,350 x 950 x 330 + 30)
Net Weight
Indoor (Unit / Grille)
Lbs.(kg)
55 / 13 (25 / 6)
Outdoor
251 (114)
External Finish
Indoor
Munsel No. 6.4Y 8.9/0.4
Outdoor
Munsell No. 3Y 7.8 / 1.1
Refrigerant
R410A ; 10lbs.
Refrigerant Piping (Flared)
Liquid (High Pressure)
In.(mm)
3/8 (9.52)
Gas (Low Pressure)
5/8 (15.88)
Maximim Total
Refrigerant Pipe Length
Ft. (m)
165 (50)
Maximum Vertical
Separation
Ft. (m)
100 (30)
PLA-A42BA6 & PUZ-A42NHA6 (-BS)
42,000 BTU/H CEILING CASSETTE HEAT-PUMP SYSTEM