997 SPLIT-TYPE, HEAT PUMP, AIR CONDITIONERS No. OC147 TECHNICAL & SERVICE MANUAL Series PLH Ceiling Cassettes Indoor unit [Model names] PLH-1.6KKHB PLH-2KKHB PLH-2.5KKHB This manual does not cover the following outdoor units. When servicing them, please refer to the service manual No.OC150 and this manual in a set. [Service Ref.] PUH-1.6VKA3·UK PUH-2VKA2·UK PUH-2.5VKA2·UK [Service Ref.] PLH-1.6KKHB·UK PLH-2KKHB·UK PLH-2.
1 FEATURES Series PLH Ceiling Cassettes FILTER CHECK MODE TEST RUN Indoor unit Remote controller Cooling capacity/Heating capacity Service Ref. W Btu/h PLH-1.6KKHB.UK 4,400/4,650[6,050] 15,000/15,900[20,600] PLH-2KKHB.UK 5,400/5,800[7,200] 18,400/19,800[24,600] PLH-2.5KKHB.UK 6,300/[7,200/9,300] 21,500/24,600[31,700] 1.
6.COMPACT DIMENSIONS MEAN EASY INSTALLATION (1)Carefree suspension work with lightweight unit The new unit weighs in at 20kg (9kg lighter than the previous model) and is easy to handle and install. What's more, suspension work is facillitated by compact dimensions ensuring a snug fit. (2)Smooth installation with "one-direction"bolts Suspension bolts can be fixes consistently from one direction easing suspension work.
● Remote controller Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button. ● Operation buttons button button This sets or switches the current time. start time and stop time. This switches between continuous operation and the timer operation. button This sets the ventilation fan speed. ON/OFF button button This switches between the operation and stop modes each time it is pressed. The lamp on this butoon lights during operation.
● Display CENTRALLY CONTROLLED display This indicates when the unit is controlled by optional features such as central control type remote controller. display The current time , start time and stop time can be displayed in tensecond intervals by pressing the time switch button. The start time or stop time is always displayed during the timer operation.
SPECIFICATIONS 3 Service Ref. Item Function Btu/h W kW Capacity Total input Service Ref. Power supply(phase, cycle,voltage) Input Running current Starting current External finish Heat exchanger Fan(drive) x No. Fan motor output Airflow(Low-High) External static pressure Booster heater Operation control & Thermostat Noise level(Low-High) Cond. drain conn. O.D. INDOOR UNIT kW A A REEFRIGERANT PIPING OUTDOOR UNIT Dimensions 6 kW K/min(CFM) mmAq,Pa kW W D H dB(A) mm,(in.) mm,(in.) mm,(in.) mm,(in.
Service Ref. Item Function Btu/h W kW Capacity Total input Service Ref. Power supply(phase, cycle,voltage) Input Running current Starting current External finish Heat exchanger Fan(drive) x No. Fan motor output Airflow(Low-High) External static pressure Booster heater Operation control & Thermostat Noise level(Low-High) Cond. drain conn. O.D. INDOOR UNIT kW A A REEFRIGERANT PIPING OUTDOOR UNIT Dimensions kW K/min(CFM) mmAq,Pa kW W D H dB(A) mm,(in.) mm,(in.) mm,(in.) mm,(in.
Service Ref. Item Function Btu/h W kW Capacity Total input Service Ref. Power supply(phase, cycle,voltage) Input Running current Starting current External finish Heat exchanger Fan(drive) x No. Fan motor output Airflow(Low-High) External static pressure Booster heater Operation control & Thermostat Noise level(Low-High) Cond. drain conn. O.D. INDOOR UNIT kW A A REEFRIGERANT PIPING OUTDOOR UNIT Dimensions 8 kW K/min(CFM) mmAq,Pa kW W D H dB(A) mm,(in.) mm,(in.) mm,(in.) mm,(in.
4 DATA 1. PERFORMANCE DATA 1) COOLING CAPACITY Service Ref. PLH-1.6KKHB.UK PLH-2KKHB.UK PLH-2.5KKHB.UK Outdoor intake air DB°C Indoor intake air WB°C CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. 16 4,439 1.27 4,317 1.33 4,159 1.43 3,990 1.53 3,812 1.64 3,624 1.74 18 4,726 1.30 4,602 1.36 4,434 1.46 4,258 1.57 4,074 1.68 3,882 1.79 20 5,017 1.32 4,899 1.38 4,724 1.50 4,542 1.61 4,352 1.72 4,154 1.84 22 5,310 1.35 5,209 1.41 5,028 1.
2) HEATING CAPACITY Service Ref. PLH-1.6KKHB.UK PLH-2KKHB.UK PLH-2.5KKHB.UK Outdoor intake air WB°C Indoor intake air DB°C CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. 15 3,184 1.03 3,650 1.14 4,160 1.25 4,714 1.38 5,312 1.51 5,952 1.64 20 3,049 1.11 3,506 1.23 4,003 1.35 4,538 1.48 5,112 1.62 5,724 1.77 25 2,930 1.18 3,364 1.31 3,844 1.44 4,370 1.59 4,942 1.74 5,560 1.90 15 3,972 1.58 4,552 1.75 5,188 1.93 5,880 2.11 6,625 2.
2. ELECTRICAL DATA Indoor unit…… 220V 50Hz 1phase Outdoor unit… 220V 50Hz 1phase Indoor unit PLH-1.6KKHB.UK PLH-2KKHB.UK PLH-2.5KKHB.UK Outdoor unit PUH-1.6VKA3.UK PUH-2VKA2.UK PUH-2.5VKA2.UK Service Ref. Cool Heat Cool Heat Cool Heat Capacity (W) 4,300 4,550[5,720] 5,300 5,700[6,870] 6,200 6,900[8,660] Total Input (kW) 1.48 1.40[2.57] 2.24 2.22[3.39] 2.53 2.25[4.01] Input (kW) 0.12 0.08[1.25] 0.12 0.08[1.25] 0.12 0.09[1.85] Current (A) 0.60 0.41[5.75] 0.61 0.42[5.
3. STANDARD OPERATION DATA Service Ref. PLH-1.6KKHB.UK Total Mode Cooling Heating Cooling Heating Cooling Heating W 4,400 4,650 5,400 5,800 6,300 7,200 Input kW 1.59 1.51 2.34 2.32 2.60 2.33 PLH-1.6KKHB.UK PLH-2KKHB.UK PLH-2.5KKHB.UK 1,50 1,50 1,50 240 240 240 Electrical circuit Phase,Hz Volts V Amperes A Outdoor unit Service Ref. 0.45 0.65 0.45 0.61 0.45 PUH-1.6VKA3.UK PUH-2VKA2.UK PUH-2.5VKA2.UK 1,50 1,50 1,50 240 240 240 V A 6.74 6.60 9.86 9.
65~80 Suspension bolt lower edge 25~35 Ceiling hole 690~710 25~35 507 41 25 466 760 Air outlet hole 460 Air intake hole Feeding hole (Drain pump) Drain hole VP-25 connection 66 4-Auto vanes Vane motor Decorative panel Ceiling surface 117 Suspension bolt M10 or W3/8 660 Terminal block for power supply Drain hole Terminal block for remote controller 25~35 35 Intake grill opening/closing side 1.6/2/2.
Unit : mm (inch) 2. REMOTE CONTROLLER FILTER CHECK MODE TEST RUN TEST RUN 120 FILTER CHECK MODE 18 130 83.5 Rear side wiring arrangement opening.
6 WIRING DIAGRAM PLH-1.6KKHB·UK/PLH-2KKHB·UK/PLH-2.5KKHB·UK SYMBOL NAME SYMBOL NAME SYMBOL NAME R.B REMOTE CONTROLLER BOARD CN2L LOSSNAY CONNECTOR X3 VANE MOTOR RELAY SW17 ADDRESS SELECTOR CN51 CENTRALLY CONTROL CONNECTOR X4 FAN MOTOR RELAY SW18 FUNCTION SELECTOR FAN2 EMERGENCY OPERATION CONNECTOR F1 FUSE (6.3A) CN1 PROGRAM TIMER CONNECTOR F.C FAN PHASE CONTROL LED1 DC 12V POWER LED CN2
7 REFRIGERANT SYSTEM DIAGRAM PLH-1.6KKHB·UK/PUH-1.6VKA3·UK PLH-2KKHB·UK/PUH-2VKA2·UK PLH-2.5KKHB·UK/PUH-2.5VKA2·UK Unit : mm Flow of refrigerant (cooling) Flow of refrigerant (heating) High pressure control switch Oil separator Refrigerant pipe (option) 15.
8 OPERATION FLOW-CHART MAIN OPERATION START Power circuit breaker 1 NO YES YES Check SW ON twice NO Operation SW ON w1 YES NO “OFF” timer YES NO NO Set time complete “ON” timer NO YES YES YES Set time complete w2 NO NO Trouble YES STOP Trouble STOP PROTECTION DEVICE SELF HOLD RELEASE PROTECTION DEVICE SELF HOLD Remote controller indicator lamp OFF w3 Remote controller trouble display Remote controller operation display Operating mode (COOL) NO Operating mode (DRY) NO Operating mod
COOLING OPERATION COOL operation Four-way valve/OFF NO Initial COOLING w8 YES Vane initial setting Vane 55 deg downward angle 70 deg downward angle NO YES NO Fan speed LOW YES NO Vane setting notch Downward discharge 1 hour YES Vane horizontal airflow NO w9 Compressor thermostat ON YES NO Allowance cancel NO YES 3-minute time delay YES 6-minute time delay NO 3-minute compressor operation NO Allowance period NO 6 minute time delay NO YES Allowance set w10 Coil frost protection YES YE
HEATING OPERATION A Heat operation NO Initial HEATING w11 w15 NO Defrost release Outdoor unit trouble NO Indoor coil thermstor is 60°C or higher NO FAN speed Low notti NO Four-way valve ON 1 YES Hor adjust in process YES Airflow 10% up NO FAN setting notch YES Compressor ON YES NO 10-minute compressor operation YES NO YES Compressor thermostat ON 3 min.
DRY OPERATION DRY operation Four-way valve / OFF NO Initial dry operation w8 YES Vane setting notch Vane initial setting YES Room tempereature is 18°C or lower w12 NO NO During compressor ON YES 3-minute compressor operation NO NO YES NO w9 Compressor & thermostat ON YES Compressor & thermostat ON NO Compressor ON time completes 10-minute compressor OFF NO YES YES w13 10-minute compressor OFF timer start Compressor ON time set Compressor OFF Compressor ON w14 w14 Fan speed LOW
9 MICROPROCESSOR CONTROL 1.OUTLINE OF MICROPROCESSOR CONTROL Remote controller board INPUT to remote controller ● OFF-ON switching. ● COOL/DRY-AUTO-HEAT selector switching. ● Thermostat setting. ● TIMER mode selector-switching and Timer setting. ● HIGH-LOW fan speed switching. ● AUTO Vane selector (AIR DISCHARGE) switching. ● TEST RUN switching. ● CHECK mode switching. (Self diagnostic trouble shooting) OUTPUT to remote controller ● Processes and transmits orders.
2. INDOOR UNIT CONTROL 2-1COOL operation 1 Press POWER ON/OFF button. 2 Press the button to display “ ” TEMP button to set the desired temperature. 3 Press the NOTE: Set temperature changes 1°C when the or button is pressed one time. Cooling 19 to 30°C FILTER CHECK MODE TEST RUN 240KA Operation starts by POWER button ON. Room temperature becomes equal to set temperature. Room temperature rises above set temperature. Operation stops by POWER button OFF.
5 Coil frost protection When indoor coil temperatuer becomes -15°C or below,coil frost protection will proceed as follows. After the compressor has been continuously operated for 3 minutes or more,and the indoor coil temperature has been 15° or below for 3 minutes,the coil frost protection will start. Compressor stops for 6 minutes,and then restarts.
(3) Auto vane control Auto vane position is set to 35degrees airflow at the start-up of COOL operation. It can then be changed by the remote controller. (a) Stop mode (fixed operation) ( i ) At start-up of COOL operation, the auto vane is set to 10 degrees air flow direction. ( ii ) Airflow direction can be changed with botton.
(a) The auto vane is driven by a 2.5 rpm motor. (b) Airflow direction can be selected between the No.1 and No.2 setting. (Initial setting is No.1) 1 2 3 4 30° 45° 55° 70° (c) Vane motor drive time Airflow direction change Unit : sec 50Hz Downward C → Horizontal 4→1 Rise Horizontal → Downward A 1→2 2.4 Downward A → Downward B 2→3 1.3 Downward B → Downward C 3→4 2.3 (d) Airfiow direction is based on the horizontal position detected by the vane motor limit switch.
2-2 DRY operation 1 Press POWER ON/OFF button. 2 Press the FILTER button to display “ ” CHECK MODE TEST RUN 3 Press the TEMP button to set the desired temperature. NOTE: The set temperature changes 1°C when the or button is pressed one time. Heat 19 to 30°C 240KA Operation starts by POWER button ON. Room temperature becomes equal to set temperature. Room temperature rises above set temperature. Operation stops by POWER button OFF.
4The compressor will not start when the room temperature is below 18°C. The compressor starts intermittent operation when the power is turned ON with room temperature above 18°C. The compressor ON/OFF time depends on the thermostat ON/OFF and the following room temperatures.After 3-minute compressor operation, ● If the room temperature thermistor reads above 28°C with thermostat ON, the compressor will operate for 6 more minutes and then stop for 3 minutes.
2-3 HEAT operation 1 Press POWER ON/OFF button. 2 Press the button to display “ FILTER CHECK MODE 3 Press the TEST RUN ” TEMP button to set the desired temperature. NOTE: The set temperature changes 1°C when the button is pressed one time. Heat 17 to 28°C or [DEFROST] 240KA The [DEFROST] symbol is displayed during the defrost operation.
(1) Compressor control 13-minute time delay To prevent overload, the compressor will not start within 3 minutes after stop. 2The compressor runs when the room temperature is lower than the set temperature. The compressor stops when the room temperature is equal to or higher than the set temperature. 3The compressor stops in check mode or during protective functions. 4Overheat protection When the indoor coil thermistor reads 70°C or above, the overheat protection will start.
(4) Booster heater control When the room temperature is 3 degrees below the set temperature, the booster heater will turn ON. When the room temperature is equal to the set temperature, booster heater will turn OFF. During the hot adjustment, the booster heater will not work. When the indoor coil thermistor rises to 60°C or above, the booster heater cannot work. When the indoor coil thermistor falls to 55°C or below, the booster heater can work.
2-4 AUTO operation (Automatic COOL/HEAT change over operation) 1 Press POWER ON/OFF button. 2 Press the FILTER button to display “ ” CHECK MODE TEST RUN 3 Press the TEMP button to set the desired temperature. NOTE: The set temperature changes 1°C when the or button is pressed one time. Automatic 19 to 28°C ●“AUTOMATIC” works to change by itself the operation mode either to cooling or heating according to the room temparature.
2-5 Auto vane control To change the air flow direction, press FILTER CHECK MODE button. NOTE: Airfiow direction can be set by the indoor dipswitch SW5-1. TEST RUN 240KA Changes by pressing the 1 30° 2 45° 3 55° 4 60° 5 swing Available in COOL operation with fan speed on HIGH or in HEAT operation. Unavailable in DRY operation. If fan speed changes from LOW to HIGH during 45° downward discharge in COOL mode, the direction automatically changes to 30°. button.
2-6 TIMER operation AUTO STOP ·········The air conditioner stops after the set time lapses. AUTO START ········The air conditioner starts after the set time lapses. TIMER OFF ··········Timer is not active. 1. Press POWER ON/OFF button. FILTER CHECK MODE TEST RUN 2. Press “ ” button to select AUTO STOP or AUTO START. 3. Press “ ” button to set desired time. Time setting is in 1 hour units for up to 24 hours. Each time HOURS button is pressed, set time increases by 1 hour.
(1) Indoor coil temperature code During the test run, the indoor coil temperature code from 1 to 15 is displayed on the remote controller instead of room temperature. The code should fall with the lapse of time in normal COOL operation, and should rise in normal HEAT operation.
2-9 Interlock with ventilation system (LOSSNAY) Mr. SLIM/LOSSNAY interlock operation is available by using the optional parts listed below. (1) System organization Relay box (PZ-12RB-E) Relay box Mr. SLIM LOSSNAY LOSSNAY Power supply Mr. SLIM Power supply Remote controller LOSSNAY control switch (PZ-05SLB2-E) Remote display adapter (PAC-SA88HA-E) Remote controller LOSSNAY control switch (PZ-05SLB2-E) (2) LOSSNAY models connectable to Mr.
2-10 Dip switch functions Each figure shows the initial factory setting. 1 On remote controller board (1) SW17(Address selector) 1 2 3 4 5 6 7 8 ON OFF SW17-1~6) For address setting SW17-7) When two remote controllers are used,this switch sets the controller function. OFF:The remote controller is set as a main controller. ON:The remote controller is set as a sub controller.
(2) SW2 (Address selector) 1 2 3 4 5 6 ON OFF Used in setting the unit-address for group control. For further information,refer to page 53. (3) SW3 (Emergency operation switch) Normal operation For emergency cooling 1 2 ON OFF For emergency heating 1 2 1 2 ON OFF ON OFF (4) SW5 (Model selector) 1 2 3 4 ON OFF SW5-1) Not for use. SW5-2) OFF:For models with heat pump ON:For models without heat pump SW5-3) Not for use. SW5-4) This switch is unavailable for PLH-KK(H)V. Keep this switch at OFF.
2-11. INDOOR FAN CONTROL (1)Fan motor max. rotational frequency for PLH-KKHB Service Ref. PLH-1.6KKHB·UK PLH-2KKHB·UK PLH-2.5KKHB·UK Voltage 100% rotational frequency (rpm) [V] 50Hz 220 586 230 608 240 629 220 586 230 608 240 629 220 611 230 634 240 657 (2)Indoor fan relay output (a)During fan ON The indoor fan relay turns ON. One second later, the phase control will start. (b)During fan OFF The phase control turns OFF. One second later, the indoor fan relay will turn OFF.
3. OUTDOOR UNIT CONTROL 3-1 Outdoor fan control The rotational frequency of outdoor fan is phase-controlled according to the outdoor coil temperature. This control allows the cooling operation even with the low outside-air temperature and the heating operation even with the high outside-air temperature. 3-2 Outdoor unit control The outdoor unit turns ON/OFF the cooling/heating operation according to orders given from the indoor unit.
3-5 Defrosting in HEAT mode Defrosting stops. Defrosting starts. Indoor unit ON Indoor fan OFF Auto vane 35degrees (SW5-3 OFF) or 20degrees (SW5-3:ON) airflow direction ON OFF Set direction (Remote controller still displays set direction.) Set direction Outdoor unit ON 4-way valve OFF Bypass valve ON OFF Outdoor fan ON OFF Compressor ON OFF (1) Start conditions A. When all of the following conditions are satisfied, defrosting will start.
(3) Defrost interval The defrost interval time is determined as follows. ● Initial defrost interval is 50 minutes. ● The defrost interval after defrosting depends on the preceding defrosting time as shown below. Defrosting operation time 3 minutes or below Next defrost interval 120 minutes 3 to 7 minutes 80 minutes 7 to 10 minutes 60 minutes 10 to 15 minutes 40 minutes 15 minutes (Maximum) 30 minutes NOTE1:If the unit stops during defrosting , the next defrost interval will be 50 minutes.
3-7 Service functions (1) Compulsory defrositng 1When all of the following conditions are satisfied, pressing SW2 starts the compulsory defrosting. ● During HEAT mode ● The compressor is ON. ● The outdoor coil temperature is being displayed by LED. (Outdoor controller board dip switch SW3-1 : OFF, SW3-2 : ON) ● The outdoor coil thermistor reads 8°C or below. 2The operation state and the termination conditions of the compulsory defrosting are the same as those of the normal defrosting.
10 TROUBLESHOOTING 1.TROUBLE IN TEST RUN Symptom Cause Check points The display “CENTRALLY CONTROLLED” on remote controller dose not disappear. 1) Wrong address setting of remote controller/indoor controller board. 2) Timer adapter is connected to the remote controller. 3) Singnal transmission error between indoor unit and remote controller. 1) Check the address setting of remote controller and indoor controller. 2) Make sure the timer adapter is used correctly.
2. SELF DIAGNOSTIC FUNCTION WITH REMOTE CONTROLLER 2-1 When malfunction occurs during operation When a malfunction occurs, the indoor and outdoor units stop and the malfunction is displayed on the LCD of the remote controller. (A) ON the set temperature display part, “CHECK” appears, and the unit address and the check code are diplayed alternately at one-second intervals.
Check Diagnosis of malfunction Cause Check points code EO Signal transmitting/receiving During individual unit control 1) Check the transmission wire. error 1) Bad contact of transmission 2) Check with another remote controller. If “EO” is (Indoor controller does not wire still indicated, replace the indoor controller respond to remote controller 2) Signal transmitting/receiving cirboard. signal.) cuit is abnormal. If other check code appears. replace the original remote controller.
3.SERVICE DATA INDICATION BY SWITCHES ON OUTDOOR CONTROLLER BOARD Setting dip switchs SW2 and SW3 on the outdoor controller board enables LED to show the output state and check code. Output state is shown by LED lighting, and check code by blinking. SW1 : Turning SW1 ON clears the check code. If SW1 is turned ON while the check code is blinking , the indication changes to output state indication. NOTE : SW1 is usually available independant of SW3 setting.
3-1 Outdoor coil temperature To obtain data on the outdoor coil temperature, add the number of bits of lighting LEDs, and see the graph below to find the temperature. C 100 (Short 238 bits) 80 60 Temperature 40 20 0 -20 -40 (Open 8 bits) 0 50 100 150 200 255 Number of bits 3-2 Fan output step To obtain data on the fan output step, add the number of bits of lighting LEDs, and see the graph below to find the fan rotational frequency. ➀PUH-1.6/2KA type ➁PUH-2.
4. TROUBLESHOOTING ACCORDING TO CHECK CODE Blinking Diagnosis of malfunction LED LD1 Reversed phase Cause Check point Phases A1, A2, and A3 are con- Check the power supply connection. nected improperly. LD2 Open phase LD3 Outdoor coil thermistor is ● Outdoor coil thermistor is abnormal. (Open circuit or short broken. circuit) ● Thermistor was connected incorrectly. LD4 High pressure switch (63H2) function ● 62H2 was badly connected. ● 63H2 was working. ● Check 63H2 and the outdoor fan motor.
6. WRONG WIRING ON SITE 6-1 Between remote controller and indoor unit If the wire is disconnected between the remote controller and the indoor unit, nothing is displayed on the remote controller when the POWER button is pressed. The beep sound will also not be heard.
7. OTHER TROUBLES AND CAUSES Vanes do not work. Unit stops after 5 to 20 seconds operation Air discharge display is OFF and button does not operate. In this case, remote controller is normal. Power ON/OFF button is not available. Vane motor does not work. Limit swtich does not work. Connector is poorly connected. Vane motor is poorly assembled. Indoor controller board is damaged. Beep sound is heard, but display is turned OFF. Beep sound is not heard, and display remains OFF. Limit switch is damaged.
11 4-WAY AIR FLOW SYSTEM 1.Placement of the air outlets ●For this grill, the air flow direction comes in 5 patterns. Also, by setting the dipswitches (SWA and SWB)on the indoor board to the appropriate settings, you can adjust the air flow and speed. Select the settings that are needed from those in Tables 2 and 3 according to the place where you want to install the unit. 1) Decide on the pattern of the airflow direction.
12 SYSTEM CONTROL 1. VARIETY OF SYSTEM CONTROL FUNCTIONS 1 Group control with a single remote controller (See page 53.) Unit Unit Unit Remote controller 2 Both remote ON/OFF and individual controls (See page 54.) w Timer adapter (PAC-SA89TA-E) is needed. Optional adapter Relay box Unit Remote ON/OFF switch 3 Individual control by grouping remote controllers (See page 55.) Remote controller Unit Unit Unit Remote controller 4 Multiple remote control display (See page 55.
2. GROUP CONTROL WITH A SINGLE REMOTE CONTROLLER A maximum of 50 units can be started in order according to the dip switch settings 2-1 How to wire (1) Connect the remote controller to the double terminal block on the indoor controller board of the master unit (No.0 unit). (See Figure 1.) (2) Connect the double terminal block of the master unit to the double terminal block of No.1 unit. (3) Connect the double terminal block of No.1 unit to the double terminal block of No.2 unit.
3. REMOTE ON-OFF AND INDIVIDUAL REMOTE CONTROLS This method is available to control one unit or any number of units. The following operations are available by connecting a relay, a timer adapter (PAC-SA89TA-E), and a remote ON/OFF switch to the system. Timer adapter is an optional part. Other parts are available on the market.
4. INDIVIDUAL CONTROL BY GROUPING THE REMOTE CONTROLLERS ● Grouping the remote controllers allows individual control and centralized monitoring of units installed in different places without a special control board. ● Remote control cables are extendable up to 500m. When the cable length exceeds 12m, use the double-insulated two-care cable such as Belden 9407. Also, the cable thickness must be No. 22 AWG or above.
6. AUTO RESTART FUNCTION By setting the dipswitch SW1-10 to ON, the air conditioner can be started/stopped by power supply ON/OFF. If the air conditioner is OFF before the power failure, it will not start operation by power restore.
13 DISASSEMBLY PROCEDURE 1. INDOOR UNIT OPERATING PROCEDURE Be careful on removing heavy parts. PHOTOS&ILLUSTRATIONS Shaft 1. Removing the air intake grill (1) (2) (3) (4) Press the PUSH button. Open the intake grill 90°. Remove the chip. Slide the shaft in the hinge to the left and remove the intake grill. Figure 1 PUSH button 2. Removing the fan guard. (1) Open the intake grill. (2) Remove the 4 screws of the fan guard. Intake grill Photo 1 Fan guard 3.
OPERATING PROCEDURE 5. Removing the room temperature thermistor (1) Remove the fan guard. (2) Remove the electrical box cover (3) Remove the holder and the room temperature thermistor by pulling the catch. (4) Disconnect the red connector, CN20, on the indoor controller board. 6. Removing the indoor coil thermistor (1) Remove the fan guard. (2) Remove the electrical box cover. (3) Remove the electrical box. (4) Remove the turbo fan. (5) Remove the screw of the service panel. (6) Remove the service panel.
OPERATING PROCEDURE 9. Removing the drain pump and drain sensor (1) Remove the panel. (2) Remove the fan guard. (3) Remove the electrical parts cover. (4) Remove the electrical parts box. (5) Remove the drain pan. (6) Remove 4 screws of the drain pump. (7) Pulling the clip of the drain hose, pull out the drain hose from the drain pump. (8) Remove the drain senser and the holder. (9) Pull out the drain pump. PHOTOS&ILLUSTRATIONS Photo 9 Drain hose Drain sensor holder Clip Screws Drain pump 10.
14 PARTS LIST PANEL PARTS PLH-1.6KKHB·UK PLH-2KKHB·UK PLH-2.5KKHB·UK 1 4 2 5 6 3 7 Q’ty/set No. Part No. Part Name Specification PLH-1.6/2/2.5 KKHB.UK 1 T7W 560 003 AIR OUTLET GRILLE 1 2 R01 29H 500 AIR FILTER 1 3 R01 29H 691 INTAKE GRILLE 1 4 R01 29H 061 HINGE 2 5 — GRILLE HANGER 1 1 6 T7W 14K 200 REMOTE CONTROLLER 7 T7W 556 305 REMOTE CONTROLLER CABLE 60 12m 1 Price Wiring RecomRemarks Diagram mended (Drawing No.) Symbol Q’ty Unit Amount (BG88H096H01) R.
PANEL PARTS PLH-1.6KKHB·UK PLH-2KKHB·UK PLH-2.5KKHB·UK 1 4 1 4 5 3 1 1 2 7 7 4 10 6 7 7 8 7 9 Q’ty/set No. Part No. Part Name Specification PLH-1.6/2/2.5 Remarks KKHB.
FUNCTIONAL PARTS PLH-1.6KKHB·UK PLH-2KKHB·UK PLH-2.
Part numbers that are cicled are not shown in the figure. Q’ty/set No. Part No. Part Name Specification PLH-1.6 PLH-2 PLH-2.5 KKHB.UK Price Wiring RecomRemarks Diagram mended (Drawing No.
15 OPTIONAL PARTS 1. REFRIGERANT PIPES Service Ref. : PLH-1.6KKHB.UK/PLH-2KKHB.UK/PLH-2.5KKHB.UK Part No. Pipe length Pipe size O.D. Connection method PAC-05FFS PAC-07FFS PAC-10FFS PAC-15FFS 5m 7m Liquid:{9.52 Indoor unit: Flared 10m Gas:{15.88 Outdoor unit: Flared 15m Note 1. How to connect refrigerant pipes. Factory supplied optional refrigerant pipings contain refrigerant at the above atmospheric pressures.
2-3. How to connect program timer (1) Install the program timer next to the remote controller the same way as the remote controller is installed. (2) Connect the program timer and the remote controller with a 6-wire cable as shown in the figure below 2-wire cable NOTE:While the program timer is connected to the remote controller, the 24hour ON/OFF timer on the remote controller will not operate.
4. MULTIPLE REMOTE CONTROLLER ADAPTER This adapter is needed for remote indication (operation/check). Part No. PAC-SA88HA-E BRN RED ORN YLW GRN 1 2 3 4 5 5. CENTRALIZED REMOTE CONTROLLER Allows individual or combined control of up to 16 units. When using the PAC-805RC, the program timer adapter (PAC825AD)is also needed. See page 68. Part No. PAC-805RC 113 5-1. Dimensions 23.5 POWER ON/OFF ENGAGED Unit : mm 56.
5-3 Connection method (1) Connections in the power supply cord. 1. Connect the power supply cord to the power supply terminal-block and fix it in-place with a tie-wrap. Connect a single phase 200V AV (220, 230, 240V) to A N . As E is the GND terminal, be sure to ground the earth wire. 2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap. Use a {1.6 (AWG 14) or above two-wire cable for the transmission line.
6. PROGRAM TIMER ADAPTER This adapter is needed when a centralized remote controller(PAC-805RC)is used. Part No.
(3) Connections from adaptor Fig.3 To program timer or centralized remote controller Adaptor 200~240V AC CN30 CN50 3-core cable 2 5-core cable 5 CN51 Remote controller Indoor unit Max. length of each calbe is 10m. (Unit : mm) 6-3 Dimecsions 3holes 27 22 86 220 22 95 4Fixing screw holes 5.5 35 35 12 120 2 2holes 2.9 7 74 230 65 18 15 40 27 ho 15 le 80 70 40 15 Fig.
7. SPACE PANEL Part No. PAC-SE01AS-E Applied Service Ref. PLH-1.6KKHB.UK/PLH-2KKHB.UK/PLH-2.5KKHB.UK 750 6 R2 750 R7.8 Hole 16 R2 6 8 R7. 8. WIDE PANEL Part No. PAC-SE06WP-E Applied Service Ref. PLH-1.6KKHB.UK/PLH-2KKHB.UK/PLH-2.5KKHB.UK 965 R2 R18047.5 Hole 7 R31 965 R6 R3 5 R18102.5 R6 7 R31 R2 5 R3 9. AIR OUTLET SHUTTER PLATE Part No. PAC-SF38SP-E Applied Service Ref. PLH-1.6KKHB.UK/PLH-2KKHB.UK/PLH-2.5KKHB.
10. MULTI-FUNCTIONAL CASEMENT Part No. PAC-SE21TM-E Applied Service Ref. PLH-1.6KKHB.UK/PLH-2KKHB.UK/PLH-2.5KKHB.UK Parts included : Casement 1 pc Screw with washer 4 pcs M5✕0.8✕15 Duct flange 1 pc Tapping screw 6 pcs 4✕10 Hook Band 2 pcs 1 pc 11. HIGH-EFICIENCY FILTER ELEMENT Part No. PAC-SE13KF-E Applied Service Ref. PLH-1.6KKHB.UK/PLH-2KKHB.UK/PLH-2.5KKHB.
HEAD OFFICE MITSUBISHI DENKI BLDG.MARUNOUCHI TOKYO100 TELEX J24532 CABLE MELCO TOKYO CCopyright 1997 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD. Issued in Jun. 1997 No. OC147 560 New publication, effective Jun.