6 DATA
6-1. REFILLING REFRIGERANT CHARGE (R410A : kg)
6-2. COMPRESSOR TECHNICAL DATA
Piping length (one way)
10m
20m
30m
40m
50m
Factory
charged
2.1
2.1
3.1
3.1
5.1
5.1
5.1
4.6
4.6
4.6
2.3
2.3
3.3
3.3
5.3
5.3
5.3
4.8
4.8
4.8
2.5
2.5
3.5
3.5
5.5
5.5
5.5
5.0
5.0
5.0
2.7
2.7
4.1
4.1
6.1
6.1
6.1
5.6
5.6
5.6
2.9
2.9
4.7
4.7
6.7
6.7
6.7
6.2
6.2
6.2
60m
7.3
7.3
7.3
6.8
6.8
6.8
75m
7.9
7.9
7.9
7.4
7.4
7.4
2.5
2.5
3.5
3.5
5.5
5.5
5.5
5.0
5.0
5.0
Service Ref.
PUHZ-RP4VHA
PUHZ-RP5VHA
PUHZ-RP1.6VHA
PUHZ-RP2VHA
PUHZ-RP2.5VHA
PUHZ-RP2.5VHA
1
PUHZ-RP3VHA
PUHZ-RP3VHA
1
PUHZ-RP4VHA1
PUHZ-RP4YHA
PUHZ-RP5VHA
1
PUHZ-RP5YHA
PUHZ-RP6VHA1
PUHZ-RP6YHA
PUHZ-RP6VHA
U-V
U-W
W-V
Unit
Compressor model
Winding
Resistance
( " )
ANV33FDAMT
(at 20°C)
0.266
0.266
0.266
SNB130FLBH
0.300 ~ 0.340
0.300 ~ 0.340
0.300 ~ 0.340
PUHZ-RP4,5,6VHA
ANV33FDBMT
1.064
1.064
1.064
PUHZ-RP4,5,6YHA
PUHZ-RP1.6,2VHA
TNB220FMBH
0.865 ~ 0.895
0.865 ~ 0.895
0.865 ~ 0.895
PUHZ-RP2.5,3VHA
Longer pipe than 30m, additional charge is
required.
OC294-D-1.qxp 05.3.9 11:01 AM Page 12