NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7°C(80°F), W.B. 19.4°C(67°F) Outdoor : D.B. 35°C(95°F), W.B. 23.9°C(75°F)
(heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. 8.3°C(47°F), W.B. 6.1°C(43°F)
*2.Conditions (heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. -8.3°C(17°F), W.B. -9.4°C(15°F)
*3.Conditions (heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. -15°C(5°F), W.B. -15°C(5°F)
Operating range
Indoor intake air temperature
D.B. 32°C(90°F), W.B. 23°C(73°F)
Outdoor intake air temperature
D.B. 46°C(115°F)
Cooling
Heating
Maximum
Maximum
Minimum
Minimum
* In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5°C(23°F)DB.)
D.B. 19°C(66°F), W.B. 15°C(59°F)
D.B. 28°C(83°F)
D.B. 10°C(50°F)
D.B. -5°C(23°F)
D.B. -18°C(0°F)*
D.B. -25°C(-13°F), W.B. -25°C(-13°F)
D.B. 21.1°C(70°F), W.B. 15°C(59°F)
Model name Indoor unit PKA-A30EA7 PKA-A36EA7
Outdoor unit PUZ-HA30NHA5 PUZ-HA36NHA5
Cooling Max. Capacity Btu/h 30,000 34,200
Rated Capacity Btu/h 30,000 33,500
Min. Capacity Btu/h 18,000 18,000
Total Input W 2,500 2,790
EER Btu/h/W 12.0 12.0
SEER Btu/h/W 16.5 16.2
Moisture Removal Pints/h 8.1 8.7
SHF 0.70 0.71
*1 Power factor % 96.2 96.3
Heating Max. Capacity Btu/h 34,000 40,000
Rated Capacity Btu/h 32,000 38,000
Min. Capacity Btu/h 18,000 18,000
Total Input W 2,930 3,410
COP W/W 3.20 3.27
HSPF (IV/V) Btu/h/W 9.5/7.3 10.0/7.8
*1 Power factor % 96.5 96.3
Heating at 17°F
(-8.3°C)
Max. Capacity Btu/h 32,000 38,000
Total Input W 5,080 6,010
*2 COP W/W 1.85 1.85
Heating at 5°F
(-15°C)
Max. Capacity Btu/h 32,000 38,000
Total Input W 5,770 6,760
*3 COP W/W 1.63 1.65
Power supply Phase, Cycle, Voltage 1phase, 60Hz, 208/230V
Breaker size A 30
Voltage Indoor - Outdoor S1-S2 AC208/230V
Indoor - Outdoor S2-S3 DC24V
Indoor - Remote Controller DC12V
Indoor unit MCA A 1
MOCP A 15
Fan motor F.L.A. 0.36 0.57
Fan motor output W 56
Air ow DRY(Lo-Mid-Hi) CMM 18.0-20.0-22.0 20.0-23.0-26.0
Air ow WET(Lo-Mid-Hi) CMM 16.0-18.0-20.0 18.0-21.0-23.0
Air ow DRY(Lo-Mid-Hi) CFM 635-705-775 705-810-920
Air ow WET(Lo-Mid-Hi) CFM 570-635-700 635-730-830
External pressure in.WG [Pa] 0
Sound level
(Lo-Mid-Hi)
dB(A) 39-42-45 43-46-49
External nish White Munsell 1.0Y 9.2/0.2
Dimension Unit W: mm [inch] 1,170 [46-1/16]
D: mm [inch] 295 [11-5/8]
H: mm [inch] 365 [14-3/8]
Weight Unit kg[lbs] 21 [46]
Field drain pipe size O.D. mm[inch] 16 [5/8]
Remote Controller Attached in indoor unit
Outdoor unit MCA A 28
MOCP A 40
Fan motor F.L.A. 0.4 + 0.4
Fan motor output W 86 + 86
Compressor Type ANB33FJEMT
R.L.A. 18.0
L.R.A. 27.5
Air ow CMM [CFM] 100 [3,530]
Refrigerant Control Electronic Expansion Valve
Defrost Method Reverse cycle
Sound level at cooling dB(A) 52
Sound level at heating dB(A) 53
External nish Munsell 3Y 7.8/1.1
Dimension Unit W: mm [inch] 950 [37-3/8]
D: mm [inch] 300+30 [13 + 1-3/16]
H: mm [inch] 1,350 [53-1/8]
Weight Unit kg[lbs] 120 [265]
Refrigerant Type R410A
Charge kg [lbs,oz] 5.5 [12lbs 2oz]
Oil L [oz] 1.4(FV50S) [45]
Refrigerant pipe
size
Gas side O.D. mm [inch] 15.88 [5/8]
Liquid side O.D. mm [inch] 9.52 [3/8]
Refrigerant pipe
length
Height difference IU-OU Max. 30m [Max.100ft]
Length Max. 75m [Max.245ft]
Refrigerant Piping Not Supplied
Connection Method Flared