Engineering Manual

High-efciency Filter Element PAC-SH59KF-E
How to Use / How to Install
Part #,
Name
Q'ty
1
High-efficiency filter element
Shape
(The unit is provided with this manual and following parts in the box.)
1 Checking packed parts
In case that the High-efficiency filter element is installed,
it should be installed on the Multi-functional casement
which is option.
Be sure to purchase the Multi-functional casement.
NOTICE
Note:
1. When the High-efficiency filter element is attached for
the first time, the setting for increase in airflow rate must
be performed.
2. This setting is necessary only when the element is newly
attached: No setting is required when the filter is replaced.
1) If the main unit to be combined is a slim air conditioner
(combination with PLA):
●Setting must be performed from the remote control: See the pages of
"Function Selection" in the installation manual provided with the remote
control. (Set optional assembly to "Yes".)
2) If the main unit to be combined is a multi air conditioner
(combination with PLFY):
●For PLFY-NBMU: Set switch "SWC" on the address board in the
main unit to the "option" 2 side ("standard" at the factory).
●For PLFY-NEMU: Set switch SW21-5 on the control board in the
main unit to the “ON” side (“OFF” at the factory). For the location of
switch SW21 on the control board, see the wiring diagram of the main unit.
Set up for increasing air flow volume.
●If the set up is not done correctly, the air
flow volume will decrease and it can lower
the performance and cause dew drop.
CAUTION
The High-efficiency filter element is single-use (not recyclable).
The reference for operation time is 2,500 hours (depending on
the environment in which the air-conditioner is installed).
2
Installation of High-efficiency filter element (same procedure for replacement)
3
A
ir flow volume setting when High-efficiency filter element is installed
4 Replacement Period
Do not wash with water.
CAUTION
●Washing with water will degrade the
performance and could cause the
element to become unusable.
Remove the intake grille of the grille in advance. (See the "installation instructions of grille" for details.)
●Loosen the 4 screws (B type)/8 screws (E type) of the 2 plates (B type)/4 plates (E type) for installation of the
High-efficiency filter element of the Multi-functional casement as shown below. Then, slide them outward.
●Set the High-efficiency filter element in the Multi-functional casement, slide the plates inward, and then tighten the 4
screws (B type)/8 screws (E type) securely.
Note:
1. When the main unit is used with "2 ways" air outlet, the High-efficiency filter element is not available.
2. When the High-efficiency filter element is installed, the operation noise can be larger.
3. When attaching the High-efficiency filter element, check the direction of air flow, referring to the stamp on the side.
B
A
Main unit
Temporary
fixing hook
E type
Screw
Screw
Bracket for installation
of the High-efficiency
filter element “B
Bracket for installation
of the High-efficiency
filter element “A
B type
Main unit
Screw
Screw
Bracket for installation of the
High-efficiency filter element
Grille
Grille
12345678910
SW1
SW12
1s DIGIT
10s DIGIT
100s DIGIT
SWASWB
ON
OFF
3
2
1
2
3
4
0
SW11
0
SW14
BRANCH
No.
SWC
2
1
0
0
CN43
CN82
<Address board PLFY-NBMU>
Mr.Slim: PLA-BA
City Multi: PLFY-NBMU
Mr.Slim: PLA-EA
City Multi: PLFY-NEMU
157