Engineering Manual

Air Outlet Guide
PAC-SH96SG-E
A part to change air direction from outdoor unit.
Can also be used to prevent short cycles.
Figure
Specications
MXZ-3C24/3C30/4C36/5C42NA2
MXZ-8C48NA
MXZ-2C20/3C24/3C30NAHZ2
MXZ-4C36/5C42/8C48NAHZ
PUZ-HA42NKA
PUY-A36/42NKA7(-BS)
PUZ-A36/42NKA7(-BS)
Descriptions
Applicable Models
Air outlet guide
Dimensions
Unit: inch [mm]
Air outlet grille: Alloy hot-dip zinc-
coated carbon steel sheet
Ivory (3.0Y 7.8/1.1)
Air outlet direction
Washer faced screw (M5x15) x 12 (Iron
wire (SWCH18A)/Zinc nickel plated)
Washer x 12, Spring washer x 12
Color (Munsell)
Material
Weight
7kg
Changeable between up, down or sideways
Accessory name x Qty.
<Material/Surface treatment>
Exterior
* Air Guide prevents reverse rotation of outdoor unit fan when it enters low speed rotation mode with fan controller
being operated. It is also used for protection of fan when strong winds, such as a typhoon, wind blowing through tall
buildings, etc., directly strike the air outlet. In addition, installation of this product is necessary when cooling operation
is to be performed in outdoor temperature of -5 or lower (down to -15).
Note the followings when installing this guide:
1) Be sure not to use "upward discharge" in a place where snowing is possible. Snow may accumulate in the
guard, which could damage the fan, etc.
2) Attaching this unit will decrease the performance (by 2-3%) and increase noise from outdoor unit (by approx. 1-2 dB).
3) Do not use "upward discharge" when there are any obstacles at the back and on both sides of outdoor unit
(air is taken in from top of unit): This could cause a short cycle.
4) To eliminate the influence of external wind, be sure to install the unit with its back facing to wall.
5) Do not install this unit in a place where wind directly blows to the back of the unit.
CAUTION
Air outlet grile Support
23-35/64 [598]
5-7/8 [150]
24-5/8 [625]
25-1/8 [638]
24-41/64 [626]
11-1/4 [285]11-1/4 [285]
6×3-11/32 [85] (=20-5/64 [510])
3-11/32 [85]
45°