Engineering Manual
83
9 CORRECTION FACTORS
PUZ-A12/18
PUZ-A24/30
PUZ-A36/42
Refrigerant piping length (one way)
30m (100ft) 40m (130ft) 50m (165ft)
20m (70ft)10m (33ft)5m (16ft)
30m (100ft) 40m (130ft) 50m (165ft)
20m (70ft)10m (33ft)5m (16ft)
Outdoor unit
PUZ-A36/42
PUZ-A24/30
PUZ-A12/18
Outdoor unit
Refrigerant piping length (one way)
1.00
1.00
1.00
0.985
0.988
0.985
0.948
0.964
0.948
0.916
0.938
0.916
–
0.915
0.886
–
0.893
0.859
1.00
1.00
1.00
0.997
0.997
0.997
0.991
0.991
0.991
0.985
0.985
0.985
–
0.979
0.979
–
0.973
0.973
■
COOLING CAPACITY CORRECTION FACTORS
9-1-1. PUZ-A series
■
HEATING CAPACITY CORRECTION FACTORS
■
CAPACITY CORRECTION
Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity
curves below.
Corrected pipe length (m) = actual pipe length (m) + number of bends x 0.3 (m)
Corrected pipe length (ft) = actual pipe length (ft) + number of bends x 1 (ft)
Cooling
Heating
100
95
90
85
80
75
70
5 10 15 20 25 30 35 40 45 50 55 60 65 69
<16> <33> <50> <70> <80> <100> <115> <130> <150> <165> <180> <195> <213> <225>
m
ft
Capacity ratio [%]
Corrected pipe length
Heating A12,18,24,30,36,42
models
(Up to 30m(100ft) for
A12,18 model)
Cooling A24,30 model
(Up to 50m(165ft) for PUZ)
Cooling A12,18,36,42 models
(Up to 30m (100ft) for
PUZ-A12/18 models,
up to 50m(165ft) for
PUY-A12/18, and PUZ-A36,42)
9-1. INVERTER