Engineering Manual

83
9 CORRECTION FACTORS
PUZ-A12/18
PUZ-A24/30
PUZ-A36/42
Refrigerant piping length (one way)
30m (100ft) 40m (130ft) 50m (165ft)
20m (70ft)10m (33ft)5m (16ft)
30m (100ft) 40m (130ft) 50m (165ft)
20m (70ft)10m (33ft)5m (16ft)
Outdoor unit
PUZ-A36/42
PUZ-A24/30
PUZ-A12/18
Outdoor unit
Refrigerant piping length (one way)
1.00
1.00
1.00
0.985
0.988
0.985
0.948
0.964
0.948
0.916
0.938
0.916
0.915
0.886
0.893
0.859
1.00
1.00
1.00
0.997
0.997
0.997
0.991
0.991
0.991
0.985
0.985
0.985
0.979
0.979
0.973
0.973
COOLING CAPACITY CORRECTION FACTORS
9-1-1. PUZ-A series
HEATING CAPACITY CORRECTION FACTORS
CAPACITY CORRECTION
Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity
curves below.
Corrected pipe length (m) = actual pipe length (m) + number of bends x 0.3 (m)
Corrected pipe length (ft) = actual pipe length (ft) + number of bends x 1 (ft)
Cooling
Heating
100
95
90
85
80
75
70
5 10 15 20 25 30 35 40 45 50 55 60 65 69
<16> <33> <50> <70> <80> <100> <115> <130> <150> <165> <180> <195> <213> <225>
m
ft
Capacity ratio [%]
Corrected pipe length
Heating A12,18,24,30,36,42
models
(Up to 30m(100ft) for
A12,18 model)
Cooling A24,30 model
(Up to 50m(165ft) for PUZ)
Cooling A12,18,36,42 models
(Up to 30m (100ft) for
PUZ-A12/18 models,
up to 50m(165ft) for
PUY-A12/18, and PUZ-A36,42)
9-1. INVERTER