Model number
Indoor unit PVA-A30AA7
Outdoor unit
PUZ-A30NHA7
PUZ-A30NHA7-BS
Charge Lbs, oz 7 lbs, 11 oz
Piping
Gas Pipe Size O.D. (Flared) In.(mm) 5/8 (15.88)
Liquid Pipe Size O.D. (Flared) In.(mm) 3/8 (9.52)
Maximum Piping Length Ft. (m) 165 (50)
Maximum Height Difference Ft. (m) 100 (30)
Maximum Number of Bends 15
Notes
AHRI Rated Conditions
(Rated data is
determined at a fixed
compressor speed)
1
Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB
2
Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB
3
Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB
*Wind baffles required to operate below 23°F DB in cooling mode. PUZ with wind baffle: 0°F - 115°F.
**System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.
SEACOAST PROTECTION
External Outer Panel: Phosphate coating + Acrylic-Enamel coating
Fan Motor Support: Epoxy resin coating (at edge face)
Separator Assembly; Valve Bed: Epoxy resin coating (at edge face)
“Blue Fin” treatment is an anti-corrosion treatment that is applied to the condenser coil to protect it against airborne contaminants.
SPECIFICATIONS: PVA-A30AA7 & PUZ-A30NHA7(-BS)