Submittal

Specications are subject to change without notice. © 2022 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
PZ-62DR-EA
LOSSNAY
®
ERV REMOTE CONTROLLER
Job Name:
System Reference: Date:
SPECIFICATIONS
Power supply requirement 12V DC (Supplied from Lossnay unit)
Power consumption 0.3W
Transmission cable
Non polarized 2-wire (2 (AWG22) sheathed
cable)
Total wiring length 219yd (200m) maximum
Number of controllable Lossnay units
15 Lossnay units maximum (Max 2 remote
controllers installable)
Environmental condition
Temperature: 32 to 104°F (0 to 40°C)
Humidity:30% to 90% relative humidity (no
condensation)
Size 4.75 x 4.75 x 3/4 in (120 x 120 x 19 mm)
Weight 0.55lbs (0.25kg)
Color Munsell 1.0Y9.2/0.2
Compatible with Lossnay RVX2 series ERV
Controls group operation for up to 15 ERV units and 2 RC’s in a single group
Not for use with Lossnay RX5 or RVX series ERV
FUNCTIONS
Function (Communicating mode) PZ-62DR-EA
Fan speed selection 4 fan speeds
Ventilation mode selection Energy recovery/Bypass/Auto
Night-purge (time) Any time selectable
Night-purge (fan speed) Selectable from 4 fan speeds
Dip-switch setting and function setting from RC Yes
Bypass temp. free setting Yes
Heater-On temp. free setting Yes
Fan power up after installation Yes
0 - 10VDC external input Yes
ON/OFF timer Yes
Auto-Off timer Yes
Weekly timer Yes
Operation restrictions (ON/OFF, Ventilation
mode, fan speed)
Yes
Operation restrictions (Fan speed skip setting) Yes
Screen contrast adjustment Yes
Language selection Yes (11 languages)
Initializing remote controller Yes
Filter cleaning sign Yes
Lossnay core cleaning sign Yes
Error indication Yes
Error history Yes
OA/RA/SA temp. display Yes