Specifications

Q64AD-GH Channel Isolated High Resolution
Analog-Digital Converter Module
Thank you for buying the Mitsubishi programmable logic controller
MELSEC Q Series.
Prior to use, please read both this manual and detailed manual thoroughly
and familiarize yourself with the product.
User's Manual
(Hardware)
MODEL Q-A/D-GH-U-HW
MODEL
Code
13JT82
IB-0800223-B (0302) MEE
©2002 MITSUBISHI ELECTRIC CORPORATION
SAFETY PRECAUTIONS
(Read these precautions before using.)
When using Mitsubishi equipment, thoroughly read this manual and the related manuals
introduced in the manual. Also pay careful attention to safety and handle the module
correctly.
These precautions apply only to this product. Refer to the user’s manual of the CPU
module to use for the PLC system safety precautions.
These SAFETY PRECAUTIONS classify the safety precautions into two
categories: "DANGER" and "CAUTION".
DANGER
Procedures which may lead to a dangerous condition and
cause death or serious injury if not carried out correctly.
CAUTION
Procedures which may lead to a dangerous condition and
cause superficial to medium injury, or physical damage only,
if not carried out correctly.
Depending on circumstances, procedures indicated by
CAUTION
may also cause
serious accidents.
In any case, it is important to follow the directions for usage.
Store this manual in a safe place so that you can take it out and read it whenever
necessary. Always forward it to the end user.
1. Overview
This manual explains the specifications and part names for the type Q64AD-GH
Channel Isolated High Resolution Analog-Digital Converter Module (hereinafter
Q64AD-GH) to be used in combination with the MELSEC-Q Series CPU module.
2. Specifications
The specifications for the Q64AD-GH are shown in the following table. For
general specifications for the Q64AD-GH, refer to the operation manual for the
CPU module being used.
Model name
Item
Q64AD-GH
Number of analog input
points
4 points (4 channels)
Voltage -10 to 10VDC (Input resistance 1 M
)
Analog
input
Current 0 to 20mADC (Input resistance 250
)
Digital output
16-bit signed binary (-32768 to 32767)
32-bit signed binary (-65536 to 65535)
Maximum
resolution
Input
Analog input
range
32-bit 16-bit
Digital output
value (32-bit)
Digital output
value (16-bit)
0 to 10V 156.3
µ
V 312.6
µ
V
0 to 5V 78.2
µ
V 156.4
µ
V
1 to 5V 62.5
µ
V 125.0
µ
V
Users input range
(Uni-polar)
47.4
µ
V 94.8
µ
V
0 to 64000 0 to 32000
-10 to 10V 156.3
µ
V 312.6
µ
V
Voltage
Users input range
(Bi-polar)
47.4
µ
V 94.8
µ
V
-64000 to
64000
-32000 to
32000
0 to 20mA 312.5nA 625.0
µ
V
4 to 20mA 250.0nA 500.0
µ
V
Current
Users input range
(Uni-polar)
151.6nA 303.2
µ
V
0 to 64000 0 to 32000
I/O characteristics,
maximum resolution
Reference
accuracy
*1
±
0.05%
Digital output value (32-bit) :
±
32digit
*2
Digital output value (16-bit) :
±
16digit
*2
Accuracy
(Accuracy
relative to
full-scale)
Temperature
coefficient
*3
±
71.4ppm/
°
C (0.00714%/
°
C)
Common mode voltage Input-Common ground (input voltage 0V): 1780VAC
Common mode
characteristic
Common mode voltage rejection ratio (VCM < 1780V): 60Hz 105dB, 50Hz 107dB
Conversion speed 10ms/4 channels
Absolute maximum input Voltage: ± 15V Current: ± 30mA
Specific isolated area
Isolation
method
Dielectric withstand
voltage
Insulation
resistance
Between I/O terminal
and PLC power supply
Photocoupler
insulation
Between analog input
channels
Transformer
isolation
1780VAC rms/3 cycles
(elevation 2000m)
500VDC
10M
or
more
Isolation specifications
E
2
PROM write count Maximum 100,000
Number of I/O occupied
points
16 points
Connected terminal 18 points terminal block
Applicable wire size 0.3 to 0.75mm
2
Applicable solderless
terminals
R1.25 - 3 (A solderless terminals with sleeves cannot be used)
Internal current
consumption (5VDC)
0.89A
Weight 0.20kg
4. Precautions For Use
(1) Do not drop the module or subject it to strong impact.
(2) Always make sure to touch the grounded metal to discharge the electricity
charged in the body, etc., before touching the module.
Failure to do so may cause a failure or malfunctions of the module.
(3) Tighten the terminal screws for the module to the specified torque shown below.
Insufficient tightening torque could result in shorts, failures or malfunction.
Screw location Tightening torque range
Module mounting screw (M3 screw)
36 to 48 N · cm
Terminal block terminal screw (M3 screw)
42 to 58 N · cm
Terminal block mounting screw (M3.5 screw)
66 to 89 N · cm
5. Wiring
5.1 Wiring precautions
(1) Wire the external AC control circuit and the external input signal for Q64AD-
GH with the separate cables to prevent the influence of surge or induction
from AC side.
(2) Ground one point of the shield for shielded wires or shielded cables.
5.2 External wiring
(1) For voltage input
Signal source 0 to ±10V
V+
I+
V-
SLD
GND
*1
*4
*2
500k
500k
Shielded
+
-
(2) For current input
Signal source 0 to 20mA
V+
I+
V-
SLD
GND
*1
*4
*2
250
+
-
500k
500k
Shielded
*3
6. External Dimensions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
RUN
ERR.
A/D
-10~10V
0~ 20mA
Q64AD- GH
17
18
ALM
V+
C
H
2
C
H
3
C
H
4
V-
I+
SLD
V+
V-
I+
SLD
V+
V-
I+
SLD
V+
V-
I+
SLD
C
H
1
unit (mm (in.))
27.4 (1.08)90 (3.54)
98 (3.86)
22 (0.87)
[DESIGN PRECAUTIONS]
CAUTION
Do not bunch the control wires or communication cables with the main circuit or power wires, or
install them close to each other.
They should be installed 100 mm (3.94 inch) or more from each other.
Otherwise, noise may occur and result in malfunction.
[INSTALLATION PRECAUTIONS]
CAUTION
Use the PLC in an environment that meets the general specifications given in the User's Manual
of the CPU module being used.
Using this PLC in an environment outside the range of the general specifications may cause
electric shock, fire, malfunction, and damage to or deterioration of the product.
When installing the module, securely insert the module fixing tabs into the mounting holes of the
base unit while pressing the installation lever located at the bottom of the module downward.
Incorrect installation may result in malfunction or breakdown, or cause the module to loosen and
drop. Securely fix the module with screws if it is subject to vibration during use.
Tighten the screws within the range of specified torque.
If the screws are loose, it may cause the module to fallout, short circuits, or malfunction.
If the screws are tightened too much, it may cause damage to the screw and/or the module,
resulting in fallout, short circuits or malfunction.
Switch all phases of the external power supply off when mounting or removing the module.
Otherwise, the module may be damaged.
Do not directly touch the conductive area or electronic components of the module.
Otherwise, the module may malfunction or go down.
[WIRING PRECAUTIONS]
CAUTION
When turning on the power and operating the module after wiring is completed, always attach
the terminal cover included with the product.
There is a risk of electric shock if the terminal cover is not attached.
Tighten the terminal screws within the range of specified torque.
If the terminal screws are loose, it may result in short circuits or malfunction.
If the terminal screws are tightened too much, it may cause damage to the screw and/or the
module, resulting in short circuits or malfunction.
Be careful not to let foreign matters such as sawdust or wire chips get inside the module.
These may cause fires, failure or malfunction.
The top surface of the module is covered with protective film to prevent foreign objects such as
cable offcuts from entering the module when wiring.
Do not remove this film until the wiring is complete.
Before operating the system, be sure to remove the film to provide adequate heat ventilation.
Manual
The following manual is also related to this product. Order them if necessary.
Related Manual
Manual Name Manual No. (Model code)
Channel Isolated High Resolution Analog-Digital Converter
Module Channel Isolated High Resolution Analog-Digital
Converter Module (with signal conditioning function) User’s
Manual
SH-080277
(13JR51)
Conformation to the EMC Directive and Low Voltage Instruction
When com
p
l
y
in
g
with EMC Directives and Low-Volta
g
e Directives b
y
assemblin
g
a
Mitsubishi PLC compatible with EMC Directive and Low-Voltage Directives into the user
p
roduct, refer to Cha
p
ter 3 "EMC Directives and Low-Volta
g
e Directives" in the User's
Manual (Hardware Section) for the CPU module being used. The CE logo is printed on
the rating plate on the main body of the PLC that conforms to the EMC directive and low
voltage instruction.
*1: Accuracy of offset/gain setting at ambient temperature
*2: “digit” indicates a digital output value.
*3: Accuracy per temperature change of 1
°
C
Example: Accuracy when temperature changes from 25 to 30
°
C
0.05% (reference accuracy) + 0.00714 %/
°
C (temperature coefficient) x 5
°
C (temperature change
difference) = 0.0857%
3. Part Names
This section explains the Part names for the Q64AD-GH.
Terminal number Signal name
1Empty
2Empty
3V+
4V
5I+
6
CH1
SLD
7V+
8V
9I+
10
CH2
SLD
11 V+
12 V–
13 I+
14
CH3
SLD
15 V+
16 V–
17 I+
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
RUN
ERR.
A/D
-10~10V
0~20mA
Q64AD-GH
17
18
ALM
V+
C
H
2
C
H
3
C
H
4
1)
2)
3)
V-
I+
SLD
V+
V-
I+
SLD
V+
V-
I+
SLD
V+
V-
I+
SLD
C
H
1
18
CH4
SLD
Number Name Description
1) RUN LED Displays the operating status of the Q64AD-GH.
On : Normal operation
Flickering : During offset/gain setting mode
Off : 5V power supply interrupted, watch dog timer error or
module exchangeable status during online module
replacement
2) ERR. LED Displays the error status of the Q64AD-GH.
On : Error (A/D conversion continues.)
Flickering : Error (A/D conversion stops.)
Off : Normal operation
3) ALM LED Displays the alarm status of the Q64AD-GH.
On : An alarm (process alarm, rate alarm) is being generated.
Flickering : An input signal error is being generated.
Off : Normal operation
*1 Use a 2-core twisted shielded wire for the power wire.
*2 Shows input resistance.
*3 For current input, be sure to connect to (V+) and (I+) terminals.
*4 Be sure to ground the shield wire of each channel.
The SLD terminal can be used when grounding, however it has not been
wired inside the board. Ground it as shown in the diagram shown above or
below.
In addition, ground the FG of the power supply module.
V+
I+
V-
SLD
Shielded
5.3 Switch setting for intelligent functional module
The settings for the intelligent function module are performed using the I/O allocation
settings for the GX Developer.
It can be easy to set by inputting in hexadecimal-4 digits.
Data item
Analog input range Input range setting value
4 to 20mA 0
H
0 to 20mA 1
H
1 to 5V 2
H
0 to 5V 3
H
– 10 to 10V 4
H
0 to 10V 5
H
User range setting
(Uni-polar)
E
H
User range setting
(Bi-polar)
F
H
Switch 1
Input range setting
H
CH4CH3CH2
CH1
Switch 2
Empty
Switch 3 Empty
Switch 4
H
0
H
: Normal mode
(A/D conversion processing)
1 to F
H
(numeric value other than 0
H
)
: Offset/
g
ain settin
g
mode
000
H
Fixed
Switch 5 0 : Fixed
Warranty
Mitsubishi Electric shall not be liable for any loss caused by reasons for which Mitsubishi is not held
accountable, lost business opportunities or unrealized gain on the customer's side resulting from failure of
the product, or any other damage, secondary disaster, accident, damage to equipment other than the
product or disruption of other business operations arising out of special circumstances which may or may
not have been predicted at Mitsubishi.
For safe use of the product
z
This product is manufactured as a general-purpose product intended for general industrial use only. It is
not designed nor manufactured for use in an equipment or system affecting human lives.
z
If you are considering to use this product in equipment or systems for nuclear power generation, power
generation, aerospace, medical or passenger transport applications, consult our sales representatives.
z
This product is manufactured under our strict quality control system. However, if the product is used in the
intended facility in such a way that a failure of the product may lead to serious accident or loss,
incorporate backup or fail-safe functions into the system design.
U.S.A Mitsubishi Electric Automation Inc.
500 Corporate Woods Parkway Vernon
Hills, IL 60061
Tel : +1-847-478-2100
Brazil MELCO-TEC Rep. Com.e Assessoria
Tecnica Ltda.
AV. Paulista 1471, Conj. 308,
Sao Paulo City, Sao Paulo State,
Brazil
Tel : +55-11-283-2423
Germany Mitsubishi Electric Europe B.V. German
Branch
Gothaer Strasse 8 D-40880 Ratingen,
GERMANY
Tel : +49-2102-486-0
U.K Mitsubishi Electric Europe B.V. UK
Branch
Travellers Lane, Hatfield, Herts., AL10
8XB,UK
Tel : +44-1707-276100
Italy Mitsubishi Electric Europe B.V. Italian
Branch
Centro Dir. Colleoni, Pal. Perseo-Ingr.2
Via Paracelso 12, 20041 Agrate B.,
Milano, Italy
Tel : +39-039-6053344
Spain Mitsubishi Electric Europe B.V. Spanish
Branch
Carretera de Rubi 76-80
08190 - Sant Cugat del Valles,
Barcelona, Spain
Tel : +34-93-565-3131
France Mitsubishi Electric Europe B.V. French
Branch
25 Boulevard des Bouvets, F-92741
Nanterre Cedex, France
TEL: +33-1-5568-5568
South Africa Circuit Breaker Industries LTD.
Tripswitch Drive, Elandsfontein Gauteng,
South Africa
Tel : +27-11-928-2000
Hong Kong Ryoden Automation Ltd.
10th Floor, Manulife Tower, 169 Electric
Road, North Point, HongKong
Tel : +852-2887-8870
China Ryoden Automation Shanghai Ltd.
3F Block5 Building Automation
Instrumentation Plaza 103 Cao Bao Rd.
Shanghai 200233 China
Tel : +86-21-6475-3228
Taiwan Setsuyo Enterprise Co., Ltd.
6F., No.105 Wu-Kung 3rd.RD, Wu-Ku
Hsiang, Taipei Hsine, Taiwan
Tel : +886-2-2299-2499
Korea HAN NEUNG TECHNO CO.,LTD.
1F Dong Seo Game Channel Bldg.,
660-11, Deungchon-dong Kangsec-ku,
Seoul, Korea
Tel : +82-2-3660-9552
Singapore Mitsubishi Electric Asia Pte, Ltd.
307 ALEXANDRA ROAD #05-01/02,
MITSUBISHI ELECTRIC BUILDING
SINGAPORE 159943
Tel : +65-6473-2308
Thailand F. A. Tech Co.,Ltd.
898/28,29,30 S.V.City Building,Office
Tower 2,Floor 17-18 Rama 3 Road,
Bangkpongpang, Yannawa,
Bangkok 10120
Tel : +66-2-682-6522
Indonesia P.T. Autoteknindo SUMBER MAKMUR
Jl. Muara Karang Selatan Block A Utara
No.1 Kav. No.11 Kawasan Industri/
Pergudangan Jakarta - Utara 14440
Tel : +62-21-663-0833
India Messung Systems Put,Ltd.
Electronic Sadan NO:111 Unit No15,
M.I.D.C BHOSARI,PUNE-411026
Tel : +91-20-712-2807
Australia Mitsubishi Electric Australia Pty. Ltd.
348 Victoria Road, PostalBag, No 2,
Rydalmere, N.S.W 2116, Australia
Tel : +61-2-9684-7777
Country/Region Sales office/Tel
When exported from Japan, this manual does not require application to the Ministry
of Economy, Trade and Industry for service transaction permission.
Specifications subject to change without notice.
Printed in Japan on recycled paper.
HEAD OFFICE : 1-8-12, OFFICE TOWER Z 14F HARUMI CHUO-KU 104-6212, JAPAN
NAGOYA WORKS : 1-14, YADA-MINAMI5, HIGASHI-KU, NAGOYA, JAPAN
Country/Region Sales office/Tel

Summary of content (1 pages)