MELSEC-Q
7 ONLINE MODULE CHANGE
(c) Click the [Close] button to close the System monitor screen.
(d) On the pass data screen of GX Configurator-DA, set the prerecorded
values and make a pass data write request. (Refer to Section 5.6.4, 5.6.5.)
(e) Set digital values to the digital values (buffer memory addresses 1 to 8:
Un\G1 to 8) and turn Operating condition setting request (Y9) from OFF to
ON. Turn ON the output enable/disable flag (Y1 to Y8) of the used channel
to check whether proper conversion has been made or not.
(Be careful since analog outputs are provided actually.)
(5) Resumption of control
(a) After choosing [Diagnosis] - [Online module change] on GX Developer to
redisplay the "Online module change" screen, click the [Execution] button to
resume control. The FROM/TO instruction for the module resumes.
(b) The "Online module change completed" screen appears.