User`s manual

7 - 28 7 - 28
MELSEC-Q
7 ONLINE MODULE CHANGE
(c) Click the [Close] button to close the System monitor screen.
(d) Choose [Online] - [Debug] - [Device test] on GX Developer and set the
prerecorded values to the buffer memory.
(e) Turn the user range write request (YA) from OFF to ON to restore the user
set values to the module.
(f) Referring to (1), enable the conversion of the channels to be used, set
digital values to the digital values (buffer memory addresses 1 to 8: Un\G1
to 8), and turn Operating condition setting request (Y9) from OFF to ON.
Turn ON the output enable/disable flag (Y1 to Y8) of the used channel to
check whether proper conversion has been made or not.
(Be careful since analog outputs are provided actually.)
(g) Executing module control resumption resumes control according to the
contents of the initial setting program. Make sure that the contents of the
initial setting program are correct.
(5) Resumption of control
(a) After choosing [Diagnosis] - [Online module change] on GX Developer to
redisplay the "Online module change" screen, click the [Execution] button to
resume control. The FROM/TO instruction for the module resumes.