User`s manual

App - 7 App - 7
MELSEC-Q
APPENDIX
Control data
2
of Q64DA
Device Item Set data Setting range Set by
(S) System area
(S) + 1 Completion status
Stores the status when the instruction
is complete.
0 : Normal completion
Other than 0: Abnormal completion
—System
(S) + 2 Pass data classification setting
Specify the voltage/current of the
offset/gain values to be read.
0: Voltage specified
1: Current specified
0
0 CH.4 CH.3 CH.2 CH.1
b15 b4b3b2b1b0
0000
H
to 000F
H
User
(S) + 3 System area
(S) + 4 CH1 Industrial shipment settings offset value System
(S) + 5 CH1 Industrial shipment settings gain value System
(S) + 6 CH2 Industrial shipment settings offset value System
(S) + 7 CH2 Industrial shipment settings gain value System
(S) + 8 CH3 Industrial shipment settings offset value System
(S) + 9 CH3 Industrial shipment settings gain value System
(S) + 10 CH4 Industrial shipment settings offset value System
(S) + 11 CH4 Industrial shipment settings gain value System
(S) + 12 CH1 User range settings offset value System
(S) + 13 CH1 User range settings gain value System
(S) + 14 CH2 User range settings offset value System
(S) + 15 CH2 User range settings gain value System
(S) + 16 CH3 User range settings offset value System
(S) + 17 CH3 User range settings gain value System
(S) + 18 CH4 User range settings offset value System
(S) + 19 CH4 User range settings gain value System
2 Set only the pass data classification setting (S)+2. If data is written to the area set by the system, the offset/gain values
will not be read properly.