User`s manual

4 - 28
4.7.3 Changing element types
4 PREDEFINED PROTOCOL SUPPORT FUNCTION
GX Works2
LCPU
4.7.3 Changing element types
Change a type of an element to another.
Screen display
Select a cell of an element to be changed on the Packet Setting screen and click the button.
Category Device type Symbol
Device range
L02/L02-P L26-BT/L26-PBT
Internal
user
*1,*2
Input X 0 to 1FFFH
Output Y 0 to 1FFFH
Internal relay M 0 to 61439
Latch relay L 0 to 32767
Link relay B 0 to EFFF
H
Data register D 0 to 94207 0 to 421887
Link register W 0 to 16FFF
H 0 to 66FFFH
File register File register
R
*2
0 to 32767
ZR 0 to 65535 0 to 393215
Buffer
memory
Intelligent
function module
device
U\G
1024 to 6911, 9728 to 16383, 20480 to 24575
*1 : Do not specify a local device.
*2 : Specify devices within the range specified in the Device setting of the PLC parameter.
CPU device
When a CPU device is specified as the data storage area, the Q series C24N/L series C24 module performs the
read/write CPU device process.
If the total length of variables used in a packet exceeds 1920 bytes, 'read CPU device process'/'write CPU device
process' of the Q series C24N/L series C24 module needs to be performed more than once, and the processing
time might be longer.
Intelligent function module device (buffer memory)
High-speed protocol processing is available because a Intelligent function module device (buffer memory) is not
affected by the sequence scan of a programmable controller CPU.
Execution of a protocol including a Non-conversion Variable or Conversion Variable
When executing a protocol including a Non-conversion Variable or Conversion Variable, do not change the value
of a CPU device specified as a variable during execution of the dedicated instruction.