2.1.7 Checking/changing the number of settable intelligent function module parameters
2 COMMON OPERATIONS FOR INTELLIGENT FUNCTION MODULES
GX Works2
■ Number of parameter settings for intelligent function modules
The number of parameter settings for intelligent function modules (initial setting and auto refresh) are
limited depending on the programmable controller CPUs or MELSECNET/H Remote I/O modules. In
addition, the number of parameter settings are also limited depending on the type of intelligent function
modules.
Be sure to set the total number of parameter settings of the intelligent function modules, not exceeding
the maximum number of parameter settings of the programmable controller CPUs or MELSECNET/H
Remote I/O modules.
● Limit for the number of parameter settings of the programmable controller CPUs or
MELSECNET/H Remote I/O modules
The following table shows the number of parameter settings for the initial setting and the auto
refresh that can be set on the programmable controller CPUs or MELSECNET/H Remote I/O
modules.
Application target of intelligent function module
Maximum number of parameter settings
Initial setting Auto refresh
QCPU (Q mode)
Basic model QCPU,
High Performance model QCPU,
MELSECNET/H Remote I/O module
512 256
Q00UJ, Q00U, Q01U, Q02U 2048 1024
Q03UD, Q03UDE, Q04UDH, Q04UDEH,
Q06UDH, Q06UDEH, Q10UDH, Q10UDEH,
Q13UDH, Q13UDEH, Q20UDH, Q20UDEH,
Q26UDH, Q26UDEH, Q50UDEH,
Q100UDEH
4096 2048
LCPU
L02, L02-P 2048 1024
L26-BT, L26-PBT 4096 2048