3.3.2 Sensor correction
3 - 13
3.3 Temperature Control Module
1
OVERVIEW
2
COMMON OPERATIONS
FOR INTELLIGENT
FUNCTION MODULES
3
OPERATING
INTELLIGENT
FUNCTION MODULES
4
PREDEFINED
PROTOCOL SUPPORT
FUNCTION
A
APPENDIX
I
INDEX
5. Enter a correction value on "(4) Normal Sensor Correction (One-point Correction)"
or "(4) Sensor Two-point Correction", and click the / /
button.
The set values are written to the buffer memory of the module.
6. For "(4) Sensor Two-point Correction", click the button.
7. Click the button.
The correction value is registered to the module.
Screen button
For details of screen buttons, refer to Section 3.1.1.
Precautions when initial settings are set on PLC parameter
When the initial settings are set on the PLC parameter, if the power is turned OFF to ON, or the CPU module is
reset and then canceled after the execution of sensor correction on the Sensor
Correction screen, the value of
"Sensor correction value setting" set on the PLC parameter is given priority at the start of the module.
When using the value set on the Sensor
Correction screen after the power is turned OFF to ON, or the CPU
module is reset and then canceled, correct the setting value of "Sensor correction value setting" on the PLC
parameter, and execute Write to PLC.