Digital-Analog Converter Module Mitsubishi General-Purpose PROGRAMMABLE LOGIC CONTROLLER User’s Manual (Hardware) Q62DAN Q64DAN Q68DAVN Q68DAIN Thank you for purchasing the Mitsubishi general-purpose programmable logic controller MELSEC-Q Series Prior to use, please read this manual thoroughly and familiarize yourself with the product.
z SAFETY PRECAUTIONS z (Read these precautions before using.) When using Mitsubishi equipment, thoroughly read this manual and the associated manuals introduced in the manual. Also pay careful attention to safety and handle the module properly. These precautions apply only to Mitsubishi equipment. Refer to the user’s manual of the CPU module to use for a description of the PLC system safety precautions. These "SAFETY PRECAUTIONS" classify the safety precautions into two categories: "DANGER" and "CAUTION".
[INSTALLATION PRECAUTIONS] CAUTION z Use the PLC in an environment that meets the general specifications given in the User's Manual of the CPU module being used. Using this PLC in an environment outside the range of the general specifications may cause electric shock, fire, malfunction, and damage to or deterioration of the product.
REVISIONS The manual number is given on the bottom right of the top cover. Print Date Aug.,2005 *Manual Number IB(NA)-0800321-A First edition Revision This manual confers no industrial property rights or any rights of any other kind, nor dose it confer any patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.
CONTENTS SAFETY PRECAUTIONS .............................................................................. A-1 REVISIONS ................................................................................................... A-3 CONTENTS ................................................................................................... A-4 About the Manuals ......................................................................................... A-4 Conformance to the EMC Directive/Low Voltage Directive........
1. Overview This manual explains specifications and the names of the components for the following modules which are used in combination with the MELSEC-Q Series CPU module. • the Q62DAN type D/A converter module (hereafter Q62DAN) • the Q64DAN type D/A converter module (hereafter Q64DAN) • the Q68DAVN type D/A converter module (hereafter Q68DAVN) • the Q68DAIN type D/A converter module (hereafter Q68DAIN) In this manual, the Q62DAN, Q64DAN, Q68DAVN and Q68DAIN are referred to as D/A converter modules.
2. Specifications The specifications for the D/A converter module are shown in the following table. For general specifications, refer to the operation manual for the CPU module being used.
Model name Item Insulation method Dielectric withstand voltage Insulation resistance I/O occupied points Connected terminals Applicable wire size Applicable solderless terminal External supply power Internal current consumption (5 V DC) Weight Q62DAN Q64DAN Q68DAVN Q68DAIN Between the I/O terminal and PLC power supply : Photocoupler isolation Between output channels : No isolation Between external supply power and analog output : Transformer isolation Between the I/O terminal and PLC power supply :
3. Part Names This section explains the names of the components for the D/A conversion module.
Number 1) Name RUN LED 2) ERROR LED 3) External power supply terminal FG terminal 4) Description Displays the operating status of the D/A converter module. On : Normal operation Flashing : During offset/gain setting mode Off : 5V power supply interrupted or watch dog timer error Displays the error status of the D/A converter module. On : Error Off : Normal operation Flashing : Error in switch settings Switch No. 5 of the intelligent function module has been set to a value other than "0".
4. Handling Precautions (1) Do not drop the module or cause it to receive strong impact. (2) Tighten the terminal screws for the module to the specified torque shown below. Insufficient tightening torque could result in shorts, failures or malfunction. Screw location Module mounting screw (M3 screw) Terminal block terminal screw (M3 screw) Terminal block mounting screw (M3.5 screw) FG terminal screw (M3 screw) * * Q68DAVN, Q68DAIN only Tightening torque 0.36 to 0.48 N·m 0.42 to 0.58 N·m 0.66 to 0.89 N·m 0.
5.2 External wiring (1) For Q62DAN and Q64DAN (a) For voltage output *1 D/A conversion *2 Motor drive module, etc. 1 kΩ to 1 MΩ V+ COM GND +15 V +24 V 24 V DC DC/DC converter A.G --15V Filter 24V 24G FG A.G (b) For current output *1 D/A conversion *2 Motor drive module, etc. 0Ω to 600Ω I+ COM GND +15V +24V 24 V DC DC/DC converter A.G –15V Filter 24V 24G FG A.G *1 Use a twisted two core shielded wire for the power wire.
(2) For Q68DAVN *1 D/A conversion *2 Motor drive module, etc. 1 kΩ to 1 MΩ V+ COM GND +15 V +24 V 24 V DC DC/DC converter A.G --15 V Filter 24V 24G FG A.G (3) For Q68DAIN *1 D/A conversion *2 Motor drive module, etc. 0Ω to 600Ω I+ COM GND +15V +24V 24 V DC DC/DC converter A.G –15V Filter 24V 24G FG A.G *1 Use a twisted two core shielded wire for the power wire. *2 If there is noise or ripples in the external wiring, connect a 0.1 to 0.
5.3 Switch setting for intelligent functional module The settings for the intelligent function module are performed using the I/O allocation settings for the GX Developer. When the intelligent function module switches are not set, the default value for switches 1 to 5 is 0.
Point (1) Depending on the type of module used, the settings for D/A module output range are shown below. • Q62DAN, Q64DAN .... 0H to 4H, FH • Q68DAVN .................. 0H, 2H to 4H, FH 1: When the setting is 0H, the output operating range swill be 1 to 5 V. • Q68DAIN.................... 0H, 1H, FH (2) For Q62DAN and Q64DAN, leave the switch2 vacant. (3) For Q68DAVN and Q68DAIN, the switch 3 will set in binary. Setting will be easy if the input format is changed to binary number.
6. External Dimensions (1) Q62DAN Q62DAN RUN ERROR 1 2 3 4 98 (3.86) 5 6 7 8 9 10 11 12 13 14 15 16 17 18 90 (3.54) 112 (4.41) 27.4 (1.08) Unit: mm (in.) (2) Q64DAN Q64DAN RUN ERROR 1 2 3 98 (3.86) 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 90 (3.54) 112 (4.41) 27.4 (1.08) Unit: mm (in.
(3) Q68DAVN Q68DAVN RUN ERROR 1 2 3 98 (3.86) 4 5 6 7 8 9 10 11 12 13 14 15 16 17 9.5 (0.37) 18 M3 screw (accessory) M3 screw (accessory) 63 (2.48) FG terminal L-Shaped metal fitting (accessory) 71.5 (2.81) 90 (3.54) 27.4 (1.08) 112 (4.41) Unit: mm (in.) (4) Q68DAIN Q68DAIN RUN 98 (3.86) ERROR I+ C H 1 COM 1 I+ C H 2 COM 3 I+ C H 3 COM 5 I+ 7 C H 4 COM 2 4 6 8 I+ C H 5 COM I+ C H 6 COM I+ C H 7 COM I+ C H 8 COM I N 24VDC 9 10 11 12 13 14 15 16 17 18 9.5 (0.
Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage, accident compensation caused by special factors unpredictable by Mitsubishi; damages to products other than Mitsubishi products; and to other duties.