User`s manual

Mitsubishi General-Purpose Programmable Controller
Renewal Tool
Conversion Adaptor
Models:
ERNT-ASQT62DA ERNT-ASQT68DA
Base Adaptor
Models:
ERNT-ASQB38 ERNT-ASQB35 ERNT-ASQB33
ERNT-ASQB00J ERNT-ASQB68 ERNT-ASQB65
ERNT-ASQB55
User’s Manual
50CM-D180090-A (1104) MEE
ERNT-ASQT62DA
ERNT-ASQT68DA
ERNT-ASQB38
ERNT-ASQB35
ERNT-ASQB33
ERNT-ASQB00J
ERNT-ASQB68
ERNT-ASQB65
ERNT-ASQB55
ERNT-ASQT62DA
ERNT-ASQT68DA
ERNT-ASQB38
ERNT-ASQB35
ERNT-ASQB33
ERNT-ASQB00J
ERNT-ASQB68
ERNT-ASQB65
ERNT-ASQB55
A-2
[Installation Precautions]
CAUTION
When installing the converter adaptor, take care not to get your hand snagged on the fittings or the
like. Injury may result.
When installing or removing the MELSEC-Q Series Module complete with a converter adaptor, be
sure to hold it with both hands. Dropping may lead to breakage.
[Wiring Precautions]
WARNING
Before attempting to install the Unit or carry out the necessary wiring, make certain that the external
power supply, used in the system, is shut off on all three phases. Failure to do so may result in
electric shock or damage to the product.
When energizing the Products or putting them into operation after the completion of installation or
wiring work, always have a cover placed over the terminal block for the MELSEC-AnS Series
components. Without the cover placed in position, electric shock can result.
CAUTION
Ground the FG terminals to the protective ground conductor dedicated to the programmable
controller. Failure to do so may result in electric shock or malfunction.
Carry out wiring for the Conversion Adaptor correctly after checking the specification and terminal
arrangement for the module used. Connecting a power supply with a different voltage rating or
incorrect wiring may cause a fire or failure.
Tighten the MELSEC-AnS Series terminal attaching screws and terminal screw secirely by
applying torque within the specified limits. Loose screws will cause short circuit, fire or malfunction.
Excessive tightening will damage the screws or the Conversion Adaptor which in turn will cause
dropping of parts, short circuit or malfunction.
Use care to prevent foreign materials including cuttings and wiring debris from entering the
Conversion Adaptor or the MELSEC-Q Series module. These will be cause for fire, failure or
malfunction.
[Startup and Maintenance Precautions]
WARNING
Do not touch live terminals. There is a danger of electric shock or malfunction.
Shut off the external power supply for the system in all phases before cleaning or retightening the
terminal screws. Failure to do so may result in electric shock or cause the MELSEC-Q Series
module to fail or malfunction. Loose screws can lead to dropping, shorting, and malfunction.
Excessive tightness of the screws can lead to breakage of the screws, converter adaptor, fittings,
base adaptor, or MELSEC-Q Series Module, possibly causing the dropping, shorting, and
malfunction thereof.
CAUTION
Do not modify the Conversion Adaptor or take it apart. Doing so will cause failure, malfunction,
personal injury, or fire.
The Conversion Adaptor comes in a resin case. Do not drop the Adaptor or give a strong impact to
it. This will cause damage to the Adaptor.
[Disposal Precautions]
CAUTION
When you dispose of the Products, handle them as industrial waste.
1
1. General Description
This manual provides information about the Conversion Adaptor (ERNT-ASQT62DA/-ASQT68DA) and the
Base Adaptor (ERNT-ASQB38/-ASQB35/-ASQB33/-ASQB00J/-ASQB68/-ASQB65/-ASQB55) available as
Renewal Tools for the Mitsubishi General-Purpose Programmable Controller.
The Conversion Adaptor is a product for effecting conversion to transcend difference in pin assignment
between the MELSEC-AnS Series and the MELSEC-Q Series. The Base Adaptor is a product which
enables a MELSEC-Q Series base module to be installed by utilizing the mounting holes in the
MELSEC-AnS Series base module. (No additional drilling is needed.)
Before attempting to make a switch from MELSEC-AnS Series to MELSEC-Q Series in your installation,
consult the user's manual supplied with individual module under the latter series to learn about how they
differ in various aspects including performance and function.
Upon unpacking your Adaptors, check to see that the following items are included in their shipping carton.
(1) Conversion Adaptor
Item name Quantity
Adaptor 1
Fittings 1
Fittings attaching screws (M3.5 x 6) 2
Terminal block cover 1
(2) Base Adaptor
Item name Quantity
Base adaptor 1
Q base module attaching screws (M4 X 10) 4
Base Adaptor attaching screws (M5 X 12) 4
3
<Specification Comparison Chart>
Voltage
Current
Voltage
Current
Voltage
Current
-
32 points
20-points terminal block
0.80 A
18-points terminal block
0.33 A
Transformer insulation
Voltage±1.0%(±100V)
Current
±1.0%(±200μA)
Maximum 25 ms/2 channels
(same for 1 channel)
±12 V
80 μs/channel
±12 V
Maximum resolution
Overall accuracy
Maximum
conversion time
Ambient temperature 25±5
℃:
Within ±0.1%
(Voltage±10mVCurrent±20μA)
Ambient temperature 0 to 55
℃:
Within ±0.3%
(Voltage±30mVCurrent±60μA)
Digital input
Signed 16-bit binary
normal resolution mode-4096 to 4095
high resolution mode
-12288 to 12287
-16384 to 16383
I/O characteristics
-10 to 10V DC
(External load resistance
1kΩ to 1MΩ)
0 to 20mA DC
(External load resistance
0Ω to 600Ω)
Current consumption
Between external
supply power and
analog output
External supply
power
21 mA28 mA
24V DC +20%
-15%
2 channels/module
Photocoupler insulation
Non-insulation
16 points
Analog output points
Insulation
method
No. of occupied points
Connected terminal block
A1S62DA
Signed 16-bit binary
-10 to 0 to 10V DC
(External load resistance
2kΩ to 1MΩ)
0 to 20mA DC
(External load resistance
0Ω to 600Ω)
0.15A
Q62DANItem
2 channels/module
Photocoupler insulation
Non-insulation
Analog output
Absolute maximun
output
Between the
output terminal
and
programmable
controller power
Between channels
Voltage Output Current Output
1/4000
-4000 to
4000
0 to
4000
1/8000
-8000 to
8000
0 to
8000
1/12000
-12000 to
12000
0 to
12000
1/4000 1/8000
1/12000
Analog
output
value
4000 8000 12000 10V
2000 4000 6000 5V
0 0 0 0V
-2000 -4000 -6000 -5V
-4000 -8000 -12000 -10V
4000 8000 12000 20mA
2000 4000 6000 12mA
0 0 0 4mA
Resolution
Digital
input
value
Digital
input
value
VoltageCurrent
Voltage Output Current Output
1/4000 2.5mV(10V) 5μA(20mA)
1/8000 1.25mV(10V) 2.5μA(20mA)
1/12000 0.83mV(10V) 1.7μA(20mA)
Digital input
value
Maximum
Digital input
value
Maximum
0 to 5V 1.25mV 0.416mV
1 to
5V
1.0mV
0.333mV
-10 to
10V
2.5mV
-16000 to
16000
0.625mV
User range
setting
0.75mV -12000 to 12000 0.333mV
0 to
20mA
5μA
1.66μA
4 to
20mA
4μA
1.33μA
User range
setting
-4000 to 4000 1.5μA -12000 to 12000 0.83μA
Analog output
range
Current
Voltage
-4000 to 4000
0 to 4000 0 to 12000
Normal resolution mode High resolution mode
0 to 4000 0 to 12000
POINT
1. A1S62DA and Q62DAN differ from each other in the way input/output signals (X, Y)
and buffer memory addresses are allocated. Therefore, you need make necessary
changes to the sequence program that is used.
A-1
SAFETY INSTRUCTIONS
(Always read these precautions prior to use.)
Before attempting to use the Conversion Adaptor and the Base Adaptor (or the Products), read all
instructions contained in this manual carefully to ensure safe and correct operation.
The safety instructions appearing in this manual are limited to those that apply to the Products. For safety
instructions to be heeded in regard to your programmable controller system as a whole, refer to the user's
manual supplied with the MELSEC-Q Series CPU module you use.
In this manual, the safety precautions are ranked as “Warning” and “Caution”.
WARNING
Indicates an immediately hazardous situation which, if not
properly dealt with, will result in death or serious injury.
CAUTION
Indicates a hazardous situation which, if not properly deal with,
will result in moderate or mild injury, or property damage alone.
Even a safety instruction marked with " Caution" could have serious consequences under certain
conditions. All the safety instructions, regardless of their classification of criticality, carry important points to
be noted. Observe them without fail.
Save this manual for reference when needed while at the same time ensuring that it is always passed on to
the ultimate user.
[Precautions: Prior to use]
CAUTION
When making a switch from the MELSEC-AnS Series to the MELSEC-Q Series, be sure to
consult user's manual supplied with individual module under the MELSEC-Q Series to confirm
differences in various aspects including performance and function between the two series.
[Installation Precautions]
CAUTION
Use the Conversion Adaptor and the Base Adaptor in the environmental conditions that are
specified in the general specification contained in the user's manual supplied with the MELSEC-Q
Series CPU Module. If the Products are used in any environment beyond the bounds of the general
specification, electric shock, fire, malfunction, or damage to or degradation of the Products will
result.
Do not touch live uninsulated part directly. Contact will cause malfunction or failure in the system.
Fasten the Conversion Adaptor and the Fittings and the Base Adaptor securely with retaining
screws, and tighten the screws by applying torque within specified limits. Loose screws can lead to
the dropping of the converter adaptor, fittings, or base adaptor, possibly causing breakage thereof.
Excessive tightness of the screws can lead to breakage of the screws, converter adaptor, fittings,
base adaptor, or MELSEC-Q Series Module, possibly causing the dropping, shorting, and
malfunction thereof.
Always check for correct match between MELSEC-Q Series and the Conversion Adaptor. Incorrect
match can cause damage to the MELSEC-Q Series module.
A-3
EMC AND LOW VOLTAGE DIRECTIVES
Compliance to the EMC Directive, which is one of the EU Directives, has been a legal obligation for the
products sold in European countries since 1996 as well as the Low Voltage Directive since 1997.
Manufacturers who recognize their products are compliant to the EMC and Low Voltage Directives are
required to declare that print a "CE mark" on their products.
Authorized representative in Europe
Authorized representative in Europe is shown below.
Name: Mitsubishi Electric Europe B.V. (EMC C.C. Division)
Address: Gothaer strasse 8, 40880 Ratingen, Germany
REVISION HISTORY
Date of print * Number of User's Manual Description
Apr 2011 50CM-D180090-A The first version is printed.
Nothing herein shall be construed as Mitsubishi's guarantee for o
r endorsement of the implementation of
any industrial properties or other rights by any party or as granting any party a license for the use of such
properties or rights. Mitsubishi shall not be liable for any problems whatsoever which, pertaining to such
properties or rights, arise out of the use of what is described herein.
2011 MITSUBISHI ELECTRIC ENGINEERING COMPANY LIMITED
TABLE OF CONTENTS
SAFETY INSTRUCTIONS ······························································································································A-1
EMC AND LOW VOLTAGE DIRECTIVES······································································································A-3
REVISION HISTORY······································································································································A-3
TABLE OF CONTENTS ··································································································································A-3
1. General Description····································································································································· 1
2. Product Specification··································································································································· 2
3. Mounting and Installation····························································································································· 7
4. Part Names and Installation Procedure·······································································································8
5. Dimensional Outline Drawing···················································································································· 10
2
2. Product Specification
2.1 Conversion Adaptor
For detail specification and general specification which do not appear in the specification comparison
charts contained herein, see the user's manual supplied with the MELSEC-Q Series module you use.
Those parts of the specification that differ between the MELSEC-AnS Series and the MELSEC-Q
Series are where a switch from the first series to the second is subjected to specification-related
restrictions. Check the specification of the devices to be connected for more details.
Conversion Adaptor
model name
MELSEC-AnS
Series
Number of
analog input
points
MELSEC-Q
Series
Mass of Conversion
Adaptor (g)
ERNT-ASQT62DA A1S62DA 2 Q62DAN 75
*1
Internal circuit diagram of ERNT-ASQT62DA
*2
TB1
TB2
TB7
TB8
TB11
TB12
TB13
TB14
TB15
TB16
TB17
TB18
TB19
TB20
TEST
HLD/CLR
TB3
TB4
TB5
TB6
TB9
TB10
TEST
HLD/CLR
Open
Open
Open
Opne
C
H
1
V+
V-
I+
I-
V+
V-
I+
I-
C
H
2
Open
Open24G
OpenFG
Open24V
TB2
TB4
TB6
TB8
TB10
TB12
TB14
TB16
TB18
TB20
TB1
TB3
TB5
TB7
TB9
TB11
TB13
TB15
TB17
TB19
TB2
TB4
TB6
TB8
TB10
TB12
TB14
TB16
TB18
TB1
TB3
TB5
TB7
TB9
TB11
TB13
TB15
TB17
TB1
TB2
TB4
TB5
TB6
TB7
TB3
TB8
TB9
TB10
TB11
TB12
TB13
TB14
TB15
TB16
TB17
TB18
CH1
V+
COM
I+
Open
V+
COM
I+
24G
FG
CH2
Open
Open
Open
Open
Open
Open
Open
Open
24V
24V DC
A1S62DA
terminal block
Terminal
number
Signal
name
Signal
name
Terminal
number
Q62DAN
terminal block
*3
POINT
Q62DAN is not provided with a terminal for Offset/Gain setting or Output
Hold/Clear setting purposes.
Make Output Hold/Clear setting by choosing an appropriate Q62DAN intelligent
function module switch setting.
For more details about the Offset/Gain setting and Output Hold/Clear setting, see
the Q62DAN User's Manual.
Q62DAN requires power supply. Therefore, use the opened terminals (TB18,
TB19) of A1S62DA to provide 24VDC power supply to Q62DAN.
Be sure to establish a ground for the FG terminal (TB18) of Q62DAN using the
open terminal (TB20) of A1S62DA.
*1
*2
*3
4
Conversion Adaptor
model name
MELSEC-AnS
Series
Number of
analog input
points
MELSEC-Q
Series
Mass of Conversion
Adaptor (g)
A1S68DAV 8 Q68DAVN
ERNT-ASQT68DA
A1S68DAI 8 Q68DAIN
75
*1
Internal circuit diagram of ERNT-ASQT68DA
*2
*3
Q68DAVN
Q68DAIN
TB2
TB4
TB6
TB8
TB10
TB12
TB14
TB16
TB18
TB20
TB1
TB3
TB5
TB7
TB9
TB11
TB13
TB15
TB17
TB19
TB2
TB4
TB6
TB8
TB10
TB12
TB14
TB16
TB18
TB1
TB3
TB5
TB7
TB9
TB11
TB13
TB15
TB17
TB1
TB2
TB4
TB5
TB6
TB7
TB3
TB8
TB9
TB10
TB11
TB12
TB13
TB14
TB15
TB16
TB17
TB18
CH1
V+/I+
COM
V+/I+
COM
V+/I+
COM
V+/I+
COM
V+/I+
COM
V+/I+
COM
V+/I+
COM
V+/I+
COM
CH2
CH3
CH4
CH5
CH6
CH7
CH8
HLD/CLR
HLD/CLR
TB19
TB20
Open(24V
FG24G
24VDC
TB1
TB2
TB4
TB5
TB6
TB7
TB3
TB8
TB9
TB10
TB11
TB12
TB13
TB14
TB15
TB16
CH1
V+/I+
COM
V+/I+
COM
V+/I+
COM
V+/I+
COM
V+/I+
COM
V+/I+
COM
V+/I+
COM
V+/I+
COM
24V
24G
CH2
CH3
CH4
CH5
CH6
CH7
CH8
TB17
TB18
FG terminal
MELSEC-AnS
Series
terminal block
Terminal
number
Signal
name
Signal
name
Terminal
number
MELSEC-Q
Series
terminal block
POINT
Q68DAVN and Q68DAIN are not provided with a terminal for Output Hold/Clear
setting purposes.
Make Output Hold/Clear setting by choosing an appropriate Q68DAVN/Q68DAIN
intelligent function module switch setting.
For details about Output Hold/Clear setting, see the Q68DAVN/Q68DAIN User's
Manuals.
Disconnect the FG wire from the FG terminal (TB20) of A1S68DAV/A1S68DAI
and reconnect it to the FG terminal at the bottom of Q68DAVN/Q68DAIN.
Q68DAVN/Q68DAIN requires power supply. Therefore, use the opened terminal
(TB19) and the FG terminal (TB20) of A1S68DAV/A1S68DAI to provide 24VDC
power supply to Q68DAVN/Q68DAIN.
*1
*2
*3