Specifications

141
1st speed
¡ Values of a, b
ab
At 0 Hz command 22 25
Other than 0 Hz
17 19
command
Note (1) Refer to the table shown above right for the values a and b.
¡Hot keep M mode [During HI POWER operation (for 15 min.)]
Indoor blower
Indoor heat exchanger temp. (˚C)
2nd speed
3rd speed
4th speed
5th speed
6th speed
7th speed
1st speed
Indoor blower
Indoor heat exchanger temp. (˚C)
2nd speed
3rd speed
4th speed
5th speed
6th speed
7th speed
Note (1) Refer to the table shown above right for the values a and b.
SKM50 model
¡Normal mode (Normal heating operation, operation after HI POWER completion)
1st speed
¡ Values of a, b
ab
At 0 Hz command 22 25
Other than 0 Hz
17 19
command
Note (1) Refer to the table shown above right for the values a and b.
Indoor blower
Indoor heat exchanger temp. (˚C)
2nd speed
3rd speed
4th speed
5th speed
6th speed
7th speed
8th speed
OFF
a b 27.5 28 29.5 31.5 34 36 37.5 39 40
(iii) Finishing conditions
When at least one of the hot stand-by cut conditions described below is met during the hot stand-by
function is activated, the hot stand-by function becomes inoperable.
1) When the hot stand-by function is activated during the above-mentioned condition which was
described in article 1 :
1 After 20 minutes elapsed since the power ON.
2 When the operation mode was changed from "STOP" to "COOLING" or "HEATING".
2) When the hot stand-by function is activated during the above-mentioned condition which was
described in article 2 :
1 When the outer air temperature thermister entered the OFF range.
2 When the operation mode was changed from "STOP" to "COOLING " or "HEATING".
(e) Hot keep operation
If the hot keep operation is selected during the heating operation, the indoor blower is controlled based on the temperature of the
indoor unit heat exchanger (detected with Th2, indoor unit heat exchanger thermistor) to prevent blowing of cool wind.
SKM22, 25, 28, 32, 40 models
¡ Normal mode (Normal heating operation, operation after HI POWER completion)