User`s manual
–23–
Self diagnosis function
■ We are constantly trying to do better service to our customers by installing such judges that show abnormality of each function as follows:
• Broken power transistor
TIMER light ON
RUN light keeps flashing
RUN light ON
2 time flash
3 time flash
1 time flash
RUN light
• Compressor locking, open phase on compressor output,
shortcircuit on power transistor, closed service valve
Outdoor heat exchanger fluid pipe sen-
sor error
Outdoor temperature sensor error
Trouble of outdoor unit
Over current
• Broken outdoor sensor wire, poor connector connection
Current cut
Description of trouble
Room temperature sensor error
Cause
• Broken heat exchanger sensor 1 wire, poor connector connection
Heat exchanger sensor 3 error
Heat exchanger sensor 1 error
Over heat of compressor
Error of signal transmission
• Broken room temperature sensor wire, poor connector connection
• Broken heat exchanger sensor 3 wire, poor connector connection
• Broken heat exchanger fluid pipe sensor wire, poor connector
connection
• Broken power transistor, broken compressor wire
• Broken discharge pipe sensor wire, poor connector connection
•
Compressor blockage
• Overload operation, overcharge
• Gas shortage, defective discharge pipe sensor, closed service
valve
• Defective power supply, Broken signal wire, defective in/outdoor
unit boards
Discharge pipe sensor error
• Broken discharge pipe sensor wire, poor connector connection.
Outdoor fan motor error • Defective fan motor, poor connector connection
Power transistor error
1 time flash
5 time flash
Active filter voltage error • Defective power supply
Cooling high pressure protection • Gas over charge, short circuit of outdoor unit
Suction pipe sensor error • Broken suction pipe sensor wire, poor connector connection.
2 time flash
4 time flash
5 time flash
1 time flash
2 time flash
3 time flash
4 time flash
5 time flash
6 time flash
7 time flash
Keep flashing
TIMER light
6 time flash
Indoor fan motor error • Defective fan motor, poor connector connection
Refrigerant is insufficient
Closed service valve
Heat exchanger sensor 1 error
• Refrigerant is insufficient, leaking
• Closed serice valve
• Broken heat exchanger sensor 1 wire, poor connector connection
7 time flash
Rotor lock
• Defective compressor
• Open phase on compressor
•
Defective outdoor unit boards
2 time flash
RUN light 2 time flash