'09•SRK-DB-087D CONTENTS 1 SPECIFICATIONS ....................................................................................2 2 EXTERIOR DIMENSIONS ........................................................................5 3 ELECTRICAL WIRING .............................................................................7 4 NOISE LEVEL ..........................................................................................9 5 PIPING SYSTEM .................................................................
'09•SRK-DB-087D 1 SPECIFICATIONS Adapted to RoHS directive SRK20ZJ-S Model Item Indoor unit Cooling capacity (1) Heating capacity (1) Power supply Power consumption Operation data (1) Running current Inrush current W W Cooling Heating Cooling Heating Cooling Heating Sound level Cooling Power level Noise level Sound level Heating Power level Exterior dimensions (Height x Width x Depth) A COP dB (A) dB dB (A) dB mm kg Net weight Compressor type & Q'ty Motor (Starting method) Refrigerant oil Refr
'09•SRK-DB-087D Adapted to RoHS directive SRK25ZJ-S Model Item Indoor unit Cooling capacity (1) Heating capacity (1) Power supply W W Power consumption Running current Cooling Heating Cooling Heating Cooling Heating Sound level Cooling Power level Noise level Sound level Heating Power level Exterior dimensions (Height x Width x Depth) kW A COP dB (A) dB dB (A) dB mm Exterior appearance ( Munsell color ) kg Net weight Compressor type & Q'ty Motor (Starting method) Refrigerant oil Refrigerant Ref
'09•SRK-DB-087D Adapted to RoHS directive SRK35ZJ-S Model Item Indoor unit Cooling capacity (1) Heating capacity (1) Power supply W W Power consumption Running current Cooling Heating Cooling Heating Cooling Heating Sound level Cooling Power level Noise level Sound level Heating Power level Exterior dimensions (Height x Width x Depth) kW A COP dB (A) dB dB (A) dB mm Exterior appearance ( Munsell color ) kg Net weight Compressor type & Q'ty Motor (Starting method) Refrigerant oil Refrigerant Ref
45 45 798 229 Content A Gas piping φ9.52(3/8") (Flare) B Liquid piping φ6.35(1/4") (Flare) C Hole on wall for right rear piping (φ65) D Hole on wall for left rear piping (φ65) E Drain hose VP16 F Outlet for wiring G Outlet for piping(on both side) 3 Wireless remote controller 9 60 150 294 G 45 Installation plate 106.5 Unit 106.5 585 450 209 60 F 17.3 Wired - remote controller (Option) 65 48.9 139 (Service space) 100 7.
Notes 50.6 (1) It must not be surrounded by walls on the four sides. E (2) The unit must be fixed with anchor bolts. An anchor bolt must not protrude more than 15mm. 24.3 63.4 D (3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction. (4) Leave 1m or more space above the unit. 351.6 (6) The model name label is attached on the lower right comer of the front panel. 14.8 69.4 312.
M M 5 Item CNE-CNY FMI SMI LM1,2 M 5 RD BK WH Y BL 5 FMI CNY CNX HD ThI Th2,3 1 3 4 5 6 CNM CNU G DS F T Va Y/G PRINTED CIRCUIT BOARD F HEAT EXCHANGER L Mark - 250V 3.
3 N ] POWER SOURCE 1〜220-240V 50Hz/1〜220V 60Hz (OR) SIGNAL WIRE 2 (Y) 1 PWB ASSY POWER TRANSISTOR T1 T2 250V 15A L 1 N 2 t° (BK) R.IN (WH) S.
'09•SRK-DB-087D 4 NOISE LEVEL Condition Model SRK20ZJ-S (Indoor Unit) Model SRK20ZJ-S Cooling 33 dB(A) Noise Level Heating 36 dB(A) ISO-T1, JIS C9612 × ...... Cooling Heating 70 70 N70 Sound Pressure Level (dB) (standard 2 x10-5Pa) 60 60 N60 50 50 N50 40 40 N40 30 30 N30 20 10 63 20 N20 125 250 500 1k 2k Mid Octave Band frequency(Hz) (Outdoor Unit) Model SRC20ZJ-S Cooling 47 dB(A) Noise Level Heating 46 dB(A) × ......
'09•SRK-DB-087D Model SRK25ZJ-S Condition (Indoor Unit) Model SRK25ZJ-S Cooling 34 dB(A) Noise Level Heating 39 dB(A) ISO-T1, JIS C9612 × ...... Cooling Heating 70 70 N70 Sound Pressure Level (dB) (standard 2×10-5Pa) 60 60 N60 50 50 N50 40 40 N40 30 30 N30 20 20 N20 10 63 125 250 500 1k 2k Mid Octave Band frequency(Hz) (Outdoor Unit) Model SRC25ZJ-S Cooling 48 dB(A) Noise Level Heating 49 dB(A) × ......
'09•SRK-DB-087D Model SRK35ZJ-S Condition (Indoor Unit) Model SRK35ZJ-S Cooling 42 dB(A) Noise Level Heating 43 dB(A) ISO-T1, JIS C9612 × ...... Cooling Heating 70 70 N70 Sound Pressure Level (dB) (standard 2 x10-5Pa) 60 60 N60 50 50 N50 40 40 N40 30 30 N30 20 20 N20 10 63 125 250 500 1k 2k Mid Octave Band frequency(Hz) (Outdoor Unit) Model SRC35ZJ-S Cooling 50 dB(A) Noise Level Heating 51 dB(A) × ......
'09•SRK-DB-087D 5 PIPING SYSTEM Models SRK20ZJ-S, 25ZJ-S Cooling cycle Indoor unit Flare connection Gas pipie Heat (φ9.52) exchanger sensor (Th22) Room temp. sensor (Th1) Heating cycle Outdoor unit Service valve (Gas) Discharge pipe temp. sensor (TH3) Check joint 4way valve Muff ler Muf fler Accumlator Heat exchanger Heat exchanger Heat exchanger sensor (Th21) Outdoor air temp. sensor (TH2) Compressor Liquid pipe (φ6.
6 APPLICATION DATA RLA012A012 (1) Installation of indoor unit • This instruction manual illustrates the method of installing an indoor unit. • For outdoor unit installation and refrigerant piping, please refer to page 17. • A wired remote control unit is supplied separately as an optional part.
SELECTION OF INSTALLATION LOCATION 5 cm m inim from the um wall (Install at location that meets the following conditions, after getting approval from the customer) Indoor unit 1 Installation board (Attached to the rear of the indoor unit) 1 2 Wireless remote control 1 3 Remote control holder 1 4 Tapping screws (for installation board ø4 X 25mm) 5 5 Wood screws (for remote control switch holder ø3.5 X 16mm) 2 6 Battery [R03 (AAA, Micro) 1.
Fixing of indoor unit Since this air conditioner has been designed to collect dew drops on the rear surface to the drain pan, do not attach the power cord above the gutter. Latch (2 locations) Installation Steps 1 Pass the pipe through the hole in the wall, and hook the upper part of the indoor unit to the installation board. Indoor unit Wall 1 Push up at the marked portion of the indoor unit base lower latch, and slightly pull it toward you.
illustration, hold the panel at both ends of lower part, lower it downward slowly, then push it slightly until the latch works. 4 Tighten the 2 set screws. 5 Fit the air filter. 6 Fit the air inlet panel. Set screws ELECTRICAL WIRING WORK Preparation of indoor unit Installing the air-cleaning filters Screw Lid CAUTION In case of faulty wiring connection, the indoor unit stops, and then the run lamp turns on and the timer lamp blinks. Mounting of connecting wires 1 2 3 4 Remove the lid.
RWC012A030A No Model 20·25·35 R410A REFRIGERANT USED (2) Installation of outdoor unit ●D A ●A T A ●D ● In ●A • This installation manual deals with outdoor units and general installation specifications only. For indoor units, refer to page 13. • When install the unit, be sure to check whether the selection of installation place, power supply specifications, usage limitation (piping length, height differences between indoor and outdoor units, power supply voltage and etc.) and installation spaces.
• Do not processing, splice the power cord, or share a socket with other power plugs. This may cause fire or electric shock due to defecting contact, defecting insulation and over-current etc. Touching rotating equipments, hot surfaces or high voltage parts can cause personal injury due to entrapment, burn or electric shocks. component can cause fire or burst. • Carry out the electrical work for ground lead with care.
30A Notabilia as a unit designed for R410A ● Do SED not use any refrigerant other than R410A. R410A will rise to pressure about 1.6 times higher than that of a conventional refrigerant. A cylinder containing R410A has a pink indication mark on the top. ● A unit designed for R410A has adopted a different size indoor unit operation valve charge port and a different size check joint provided in the unit to prevent the charging of a wrong refrigerant by mistake.
ying is ing or, s r, e erate or rate orso so e e 2. REFRIGERANT PIPING WORK 2. REFRIGERANT PIPING WORK 1) Restrictions on unit installation and use 1)●Restrictions unit installation and use and the installation site. Check the followingon points in light of the indoor unit specifications ● Check Observethethefollowing followingpoints restrictions onofunit andspecifications use. Improper can result ● in light theinstallation indoor unit andinstallation the installation site.
flare nut onto it. Flare dimensions for R410A are different from those for conventional R407C. Although we recommend the use of flaring tools designed specifically for R410A, conventional flaring tools can also be used by adjusting the measurement of protrusion B with a protrusion control gauge. Copper In the case of a rigid (clutch) type pipe outer diameter With an R410A tool With a conventional tool Ǿ6.35 0∼0.5 1.0∼1.5 Ǿ9.52 Screw Side cover ●Tighten a flare joint securely.
● ● Wrap indoor units’ flare joints with heat insulating parts (pipe cover) for heat insulation (both gas and liquid pipes). Give heat insulation to both gas and liquid side pipes. Bundle a heat insulating material and a pipe tightly together so that no gaps may be left between them and wrap them together with a connecting cable by a dressing tape. Both gas and liquid pipes need to be dressed with 20 mm or thicker heat insulation materials above the ceiling where relative humidity exceeds 70%.
● ● ● ● Power supply terminal block ○It holds cables in place and protect the terminal connection from external force. ○This clamp is for the cable in the outside diameter 9~15mm. Please adjust it when not suitable. Earth leakage breaker (Harmonic resistant type) perform grounding system installation work with the power cord unplugged. CAUTION Always use an earth leakage circuit breaker designed for inverter circuits to prevent a faulty operation.
'09•SRK-DB-087D 7 RANGE OF USAGE & LIMITATIONS Models SRK20ZJ-S, 25ZJ-S, 35ZJ-S Item Indoor return air temperature (Upper, lower limits) Cooling operation : Approximately 18 to 32℃ D.B. Heating operation : Approximately 10 to 27℃ D.B. (Refer to the selection chart) Outdoor air temperature (Upper, lower limits) Cooling operation : Approximately -15 to 46℃ D.B. Heating operation : Approximately -15 to 21℃ D.B. (Refer to the selection chart) Refrigerant line (one way) length Max.
'09•SRK-DB-087D (2) Correction of cooling and heating capacity in relation to one way length of refrigerant piping It is necessary to correct the cooling and heating capacity in relation to the one way piping length between the indoor and outdoor units. Piping length [m] 7 10 15 20 25 30 Cooling 1.0 0.99 0.975 0.965 0.95 0.935 Heating 1.0 1.0 1.0 1.0 1.0 1.
'09•SRK-DB-087D 8 CAPACITY TABLES Model SRK20ZJ-S Heat Mode Cool Mode Indoor air temp Air flow Hi 7.8 3 (m /min) Outdoor air temp. 21˚CDB 14˚CWB 23˚CDB 16˚CWB 26˚CDB 18˚CWB 27˚CDB 19˚CWB 28˚CDB 20˚CWB 31˚CDB 22˚CWB 33˚CDB 24˚CWB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 2.25 1.93 2.36 1.90 2.45 1.99 2.49 1.96 2.53 1.94 2.60 2.02 2.67 1.97 12 2.21 1.91 2.32 1.88 2.41 1.97 2.45 1.95 2.50 1.93 2.58 2.01 2.65 1.96 14 2.17 1.89 2.28 1.86 2.
'09•SRK-DB-087D Reference 1 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER 1. Operation control function by remote controller Operation section FAN SPEED button OPERATION MODE select button Each time the button is pressed, the display is switched over in turn. Each time the button pressed, the display is switched over in turn. ON/OFF (luminous) button HI POWER/ECONO button Press to start operation, press again to stop. This button changes the HIGH POWER/ ECONOMY mode.
'09•SRK-DB-087D 2. Unit ON/OFF button When the remote controller batteries become weak, or if the remote controller is lost or malfunctioning, this button may be used to turn the unit on and off. (1) Operation Push the button once to place the unit in the automatic mode. Push it once more to turn the unit off.
'09•SRK-DB-087D 5. Flap and louver control Control the flap and louver by AIR FLOW (LEFT/RIGHT) button on the wireless remote controller. (UP/DOWN) and (1) Flap Each time when you press the AIR FLOW (UP/DOWN) button the mode changes as follows. (Flap stopped) (Swing) Angle of Flap from Horizontal Remote controller display COOL , DRY, FAN Approx. 10° Approx. 25° Approx. 40° Approx. 50° Approx. 60° HEAT Approx. 25° Approx. 40° Approx. 50° Approx. 60° Approx.
'09•SRK-DB-087D 6. 3D auto operation Control the flap and louver by 3D AUTO button on the wireless remote controller. Air f low selection and air flow direction are automatically controlled, allowing the entire indoor to efficiently conditioned. (1) During Cooling and Heating (Including auto cooling and heating) (a) Air f low selection is determined according to indoor temperature and setting temperature. Operation mode At cooling At heating Air flow selection AUTO Indoor temp. – Setting temp.
'09•SRK-DB-087D 7. Timer operation (1) Comfortable timer setting (ON timer) If the timer is set at ON when the operation select switch is set at the cooling or heating, or the cooling or heating in auto mode operation is selected, the comfortable timer starts and determines the starting time of next operation based on the initial value of 15 minutes and the relationship between the indoor temperature at the setting time (temperature of room temperature sensor) and the setting temperature.
'09•SRK-DB-087D 9.
'09•SRK-DB-087D 10.
'09•SRK-DB-087D 12. Protective control function (1) Frost prevention control (During cooling or dehumidifying) (a) Operating conditions 1) Indoor heat exchanger temperature (Th2) is lower than 5ºC. compressor command speed 2) 5 minutes after reaching the compressor command speed except 0 rps. (b) Detail of anti-frost operation Item Indoor heat exchanger temperature 5°C or lower 2.
'09•SRK-DB-087D (4) Cooling low outdoor air temperature protective control (a) Operating conditions: When the outdoor air temperature (TH2) is 22ºC or lower continues for 20 seconds while the compressor command speed is other than 0 rps. (b) Detail of operation: 1) The lower limit of the compressor command speed is set to 50 <44> (30) rps and even if the speed becomes lower than 50 <44> (30) rps, the speed is kept to 50 (44) (30) rps. However, when the thermo becomes OFF, the speed is reduced to 0 rps.
'09•SRK-DB-087D (6) Heating overload protective control (a) Indoor unit side 1) Operating conditions : When the outdoor air temperature (TH2) is 17ºC or higher continues for 30 seconds while the compressor command speed other than 0 rps. 2) Detail of operation : The indoor fan is stepped up by 1 speed step. (Upper limit 8th speed) 3) Reset conditions : The outdoor air temperature (TH2) is lower than 16ºC.
'09•SRK-DB-087D (8) Compressor overheat protection (a) Purpose: It is designed to prevent deterioration of oil, burnout of motor coil and other trouble resulting from the compressor overheat. (b) Detail of operation 1) Speeds are controlled with temperature detected by the sensor (TH3) mounted on the discharge pipe.
'09•SRK-DB-087D (13) Serial signal transmission error protection (a) Purpose: Prevents malfunction resulting from error on the indoor ↔ outdoor signals. (b) Detail of operation: If the compressor is operating and a serial signal cannot be received from the indoor control with outdoor control having serial signals continues for 7 minute and 35 seconds, the compressor is stopped.
'09•SRK-DB-087D Reference 2 TROUBLESHOOTING PROCEDURES FOR ELECTRICAL EQUIPMENT (1) Cautions (a) If you are disassembling and checking an air conditioner, be sure to turn off the power before beginning. When working on indoor units, let the unit sit for about 1 minute after turning off the power before you begin work.
'09•SRK-DB-087D (4) Troubleshooting procedure (If the air conditioner runs) Conf irm the contents of the customer complaint. NO The cause of the trouble can be specifically identified. Eliminate the cause of the trouble and perform an operation check. Check the self-diagnosis display. See page 41. Is an error code displayed by the self-diagnosis function? YES Using the Service mode, access the self-diagnosis displays generated in the past. NO See pages 42 ~ 48.
'09•SRK-DB-087D (5) Self-diagnosis table When this air conditioner performs an emergency stop, the reason why the emergency stop occurred is displayed by the flashing of display lights. If the air conditioner is operated using the remote controller 3 minutes or more after the emergency stop, the trouble display stops and the air conditioner resumes operation.
'09•SRK-DB-087D (6) Service mode (Trouble mode access function) This air conditioner is capable of recording error displays and protective stops (service data) which have occurred in the past. If self-diagnosis displays cannot be confirmed, it is possible to get a grasp of the conditions at the time trouble occurred by checking these service data.
'09•SRK-DB-087D *3: To count the number of flashes in the service mode, count the number of flashes after the light lights up for 1.5 second initially (start signal). (The time that the light lights up for 1.5 second (start signal) is not counted in the number of flashes.) ’’ In the case of current cut (example: stop code 42’’) The RUN light (10’s digit) flashes 4 times and the TIMER light (1’s digit) flashes 2 times. 4×10+2×1=42 From the table, read the instructions for error code 42, current cut’’.
'09•SRK-DB-087D (Example) Remote controller setting Operation switching Cooling Displayed data Fan speed Temperature switching setting MED 21ºC Displays the reason for the stop (error code) the previous time an error was displayed. 22ºC Displays the reason for the stop (error code) 2 times previous when an error was displayed. 23ºC Displays the reason for the stop (error code) 3 times previous when an error was displayed.
'09•SRK-DB-087D (c) Error code, stop code table (Assignment of error codes and stop codes is done in common for all models.) Number of flashes when in service mode Stop coad RUN or TIMER light Error coad light (10's digit) (1's digit) OFF 3 time flash 4 time flash 5 time flash 6 time flash 8 time flash Error content Cause Occurrence conditions OFF 0 Normal 5 time flash 05 Can not receive signals for 35 Power supply is faulty.
'09•SRK-DB-087D Note (1) The number of flashes when in the Service Mode do not include the 1.5 second period when the lights light up at first (starting signal). (See the example shown below.) ’’ In the case of current cut (example: stop code 42’’) The RUN light (10’s digit) flashes 4 times and the TIMER light (1’s digit) flashes 2 times. 4×10+2×1=42 From the table, read the instructions for error code 42, current cut’’. ’’ 1.5 sec. RUN light (10’s digit) ON OFF 0.5 sec. TIMER light (1’s digit) 0.
'09•SRK-DB-087D (e) Room temperature sensor, indoor heat exchanger sensor, outdoor air temperature sensor, outdoor heat exchanger sensor table Units: °C TIMER light (1’s digit) RUN light (10’s digit) 0 1 2 3 4 5 6 7 8 9 6 -60 -61 -62 -63 -64 5 -50 -51 -52 -53 4 -40 -41 -42 -43 -54 -55 -56 -57 -58 -59 -44 -45 -46 -47 -48 -49 3 -30 -31 -32 2 -20 -21 -22 -33 -34 -35 -36 -37 -38 -39 -23 -24 -25 -26 -27 -28 -29 1 -10 -11 -12 -13 -14 -15 -16 -
'09•SRK-DB-087D (f) Discharge pipe sensor table Units: °C TIMER light (1’s digit) RUN light (10’s digit) 0 1 2 3 4 5 6 7 8 9 3 -60 -62 -64 2 -40 -42 -44 -46 -48 -50 -52 -54 -56 -58 1 -20 -22 -24 -26 -28 -30 -32 -34 -36 -38 -2 -4 -6 -8 -10 -12 -14 -16 -18 Buzzer sound Yes (sounds for 0.
'09•SRK-DB-087D Service data record form Model Customer Date of investigation Machine name Content of complaint Remote controller settings Temperature setting Operation switching Fan speed switching MED Cooling Heating Cooling Cooling HI Heating Cooling Cooling Indoor heat exchanger sensor on previous occasion. Remote controller information on previous occasion. MED Outdoor air temperature sensor on previous occasion. HI Outdoor heat exchanger sensor on previous occasion.
'09•SRK-DB-087D (7) Inspection procedures corresponding to detail of trouble Sensor error Broken sensor wire, connector poor connection NO Is connector connection good? Correct connection. YES NO Is sensor resistance value good? Replace sensor. YES Replace PCB. ◆ Discharge pipe sensor temperature characteristics (Broken wire) 180 ◆ Sensor temperature characteristics (Room temp., indoor heat exchanger temp., outdoor heat exchanger temp., outdoor air temp.
'09•SRK-DB-087D Current cut Compressor lock, Compressor wiring short circuit, Compressor output is open phase, Outdoor PCB is faulty, Service valve is closed, EEV is faulty, Compressor faulty. NO In the service valves of the outdoor unit open? Open the service valves YES Is there any shortcircuit? YES Secure space for inlet and outlet.
'09•SRK-DB-087D Over heat of compressor Is discharge pipe sensor resistance value good? Gas shortage, defective discharge pipe sensor NO (page 50) Connector connection check, resistance value check, replacement of discharge pipe sensor YES Is sufficient quantity of refrigerant circulated? NO Does trouble persist after charging gas? NO Check if there are any places where gas is leaking. YES YES Clogged capillary tube or strainer, defective EEV, etc.
'09•SRK-DB-087D Trouble of outdoor unit Is the power supply voltage OK? NO Insufficient refregerant amount, Faulty power transistor, Broken compressor wire Service valve close, Defective EEV, Defective outdoor PCB Check power supply. YES Is the service valves of the outdoor unit open? Proper power supply voltages are as follows. (At the power supply outlet) 220V : 198~242V 230V : 207~253V 240V : 216~264V NO Open the service valves.
'09•SRK-DB-087D Outdoor fan motor error Is connector connection good? NO Defective fan motor, connector poor connection, defective outdoor PCB Correct connector connection YES * Disconnect the fan motor connector, then investigate the fan motor and outdoor PCB separately. Is the output of the outdoor PCB normal? NO Is fan motor resistance value good? YES Replace outdoor fan motor NO YES Defective outdoor PCB Notes (1) See pages 89 for the fan motor and outdoor PCB check procedure.
'09•SRK-DB-087D (b) Outdoor unit Phenomenon Operation mode Sensor Shortcircuit Disconnected wire Heat exchanger sensor Cooling System can be operated normally. Heating Defrosting is not performed. Defrosting is performed for 10 minutes at approx. 45 minutes. Ourdoor air temperature sensor Cooling System can be operated normally. Compressor stop. Heating Defrosting is not operated. Defrosting is performed for 10 minutes at approx. 45 minutes.
'09•SRK-DB-087D (C) Power transistor inspection procedure [Use a tester with a needle indicator for the inspection. (Do not use a digital tester. Check in the AC 300 volt range.)] (1) If there is a self-diagnosis display, inspect the compressor system (burns, wiring mistakes, etc.) If no problems are found, check the output of the power transistor. (2) Output inspection procedure Disconnect the terminals for the compresseor.
Red WH White Y Yellow Y/G Yellow/Green Indoor unit L 1 N 2/N 250V 15A (BK) NOISE FILTER (WH) 3 (Y/G) t゜ R.IN F2 250V 20A + T L + Power source 1 Phase 220-240V 50Hz PWB ASSY POWER TRANSISTOR T1 T2 S.IN - (RD) C-2 F4 57 - (Y/G) G1 250V 10A CN20S 20S CNTH t゜ t゜ t゜ TH1TH2 TH3 Power source and serial signal inspection to N : AC 220/230/240V 1 to 2 : AC 220/230/240V 2 to 3 : Normal if the voltage oscillates between DC 0 and approx.
'09•SRK-DB-087D 3 1-3 1 2 1-4 Red Blue 4 Orange (6P, black) 5 Yellow Expansion valve connector 6 White (a) Inspection of electronic expansion valve Electronic expansion valve operates for approx. 10 seconds after the power on, in order to determine its aperture. Check the operating sound and voltage during the period of time. (Voltage cannot be checked during operation in which only the aperture change occurs.
INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONERS Air-Conditioning & Refrigeration Systems Headquarters 16-5, 2-chome, Kounan, Minato-ku, Tokyo, 108-8215, Japan Fax : (03) 6716-5926 Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice. c Copyright MITSUBISHI HEAVY INDUSTRIES.