(9) 3D auto operation
Control the ap and louver by 3D AUTO button on the wireless remote control.
Air ow selection and air ow direction are automatically controlled, allowing the entire indoor to efciently conditioned.
(a)
During Cooling and Heating (Including auto cooling and heating)
(i)
Air ow selection is determined according to indoor temperature and setting temperature.
(ii)
Air ow direction is controlled according to the indoor temperature and setting temperature.
1)
When 3D auto operation starts
2) When Indoor temp. – Setting temp. is
<
=
5ºC during cooling and when Setting temp. – Indoor temp. is
<
=
5ºC dur-
ing heating, the system switches to the following air ow direction control. After the louver swings left and right
symmetrically for 3 cycles, control is switched to the control in 3).
3)
After the ap swings for 5 cycles, control is switched to the control in 4).
4) For 5 minutes, the following air ow direction control is carried out.
5) After 5 minutes have passed, the air ow direction is determined according to the indoor temperature and setting
temperature.
(b)
During DRY Operation (including auto DRY operation)
Cooling
Air flow selection
Operation mode
AUTO HI MED LO
Heating
Indoor temp. – Setting temp. >5°C
Indoor temp. – Setting temp.
5°C
Setting temp. – Indoor temp. >5°C Setting temp. – Indoor temp.
5°C
HIGH POWER AUTO
HI MED LO
HIGH POWER AUTO
<
=
<
=
Flap
Louver
Cooling
Up/down Swing
Heating
Wide (fixed) Center (fixed)
Flap
Louver
Cooling Heating
Left/right Swing
Horizontal blowing (Fixed) Slant forwardl blowing (Fixed)
Flap
Louver
Cooling
Up/down Swing
Heating
Center (Fixed)
Wide (Fixed)
Flap
Louver
Cooling Heating
Horizontal blowing (Fixed) Slant forwardl blowing (Fixed)
Operation mode
Indoor temp. – Setting temp. 2°C
Setting temp. – Indoor temp. 2°C
Heating
Cooling
Air flow direction contorol
2°C < Setting temp.
– Indoor
temp. 5°C
2°C <
Indoor
temp.
–
Setting temp. 5°C
Indoor temp. – Setting temp. > 5°C
Setting temp. – Indoor temp. > 5°C
The control in 4) continues. Control returns to the control in 2). Control returns to the control in 1).
The control in 4) continues. Control returns to the control in 2). Control returns to the control in 1).
<
=
<
=
<
=
<
=
Wide (Fixed)
Flap
Louver
Horizontal blowing (Fixed)