Engineering Manual

6
OCD699
Unit: inch(mm)
Model A B C a b c
SUZ-KA09/12/15NA2
SUZ-KA09/12/15NAH2
11-1/16
(280)
5-9/16
(140)
9-1/2
(240)
31-1/2
(800)
11-1/4
(285)
21-5/8
(550)
2-1. OUTDOOR UNIT
c
C
A
a b
B
3
CORRECTION FACTORS
3-1. INVERTER TYPE
3-1.1 Cooling capacity corrections
2
POSITION OF THE CENTER OF GRAVITY
Model
Refrigerant piping length (one way: ft)
25 (std.) 40 65 100
SUZ-KA09/12/15NA2
SUZ-KA09/12/15NAH2
1.0 0.997 0.993 -
3-1.2 Heating capacity corrections
Model
Refrigerant piping length (one way: ft)
25 (std.) 40 65 100
SUZ-KA09/12/15NA2
SUZ-KA09/12/15NAH2
1.0 0.988 0.967 -
Max. Length
A
Max. Height
difference
B
Indoor
unit
Outdoor unit
3-1.3 Max. refrigerant piping length & max. Height difference
Model
Refrigerant piping: ft Piping size O.D: in
Max. Length
A
Max. Height
difference
B
Gas Liquid
SUZ-KA09/12NA2
SUZ-KA09/12NAH2
65 40 3/8 1/4
SUZ-KA15NA2
SUZ-KA15NAH2
65 40 1/2 1/4