Indoor Installation Manual
Table Of Contents
- SVZ-KP12,18, 24, 30, 36NA
- Table of Contents
- SVZ-KP12,18, 24, 30, 36NA
- 1. Dimensions
- 2. Inspect shipment
- 3. Safety precautions
- 4. Indoor unit accessories
- 5. Selecting an installation site
- 6. Combining indoor units with outdoor units
- 7. Installing the unit
- 8. Side Return
- 9. Duct connection
- 10. Mount positions
- 11. Air filter
- 12. Refrigerant piping work
- 13. Drain connections
- 14. Electrical wiring
- 15. Test run
- SVZ-KP12,18, 24, 30, 36NA
- 1. Dimensions
- 2. Inspection du matériel livré
- 3. Mesures de sécurité
- 4. Accessoires de l’appareil intérieur
- 5. Sélection de l’emplacement d’installation
- 6. Combinaison des appareils intérieurs et extérieurs
- 7. Installation de l’appareil
- 8. Retour latéral
- 9. Raccordement des conduits
- 10. Positions de montage
- 11. Filtre à air
- 12. Travaux de tuyauterie de frigorigène
- 13. Raccordements de vidange
- 14. Câblage électrique
- 15. Essai de fonctionnement
- 15.1. Avant l’essai de fonctionnement
- 15.2. Essai de fonctionnement
- 15.3. Autotest
- 15.4. FONCTION D’AUTOREDÉMARRAGE
12.1. Insulation
To avoid dew drops, provide sufficient anti-sweating insulation to the refrigerant and drain pipes. When us-
ing commercially available refrigerant pipes, be sure to cover with available insulating material with heat-
resistant temperature of more than 100 °C [212 °F] and thickness given below, on both liquid and gas
pipes. Insulate all indoor pipes with polyethylene insulation with a minimum density of 0.03 and a thickness
as specified in the table below.
Pipe size Insulation thickness
6.4 mm to 25.4 mm [1/4 to 1 in.] >10 mm [7/16 in.]
28.6 mm to 38.1 mm [1-1/8 to 1-1/2 in.] >15 mm [5/8 in.]
• If the unit is used on the highest story of a building and under high temperature and high humidity, it is
necessary to use thicker insulation than specified in the table above
• If there are customer’s specifications, please follow them
12.2. Piping size
Model
SVZ-KP•NA
12 18
Refrigerant pipe
Liquid pipe 6.35 mm [1/4]
Gas pipe 9.52 mm [3/8] 12.7 mm [1/2]
Drain Pipe O.D. 32 mm [1-1/4]