12.1. Insulation
To avoid dew drops, provide sufficient anti-sweating insulation to the refrigerant and drain pipes. When us-
ing commercially available refrigerant pipes, be sure to cover with available insulating material with heat-
resistant temperature of more than 100 °C [212 °F] and thickness given below, on both liquid and gas
pipes. Insulate all indoor pipes with polyethylene insulation with a minimum density of 0.03 and a thickness
as specified in the table below.
Pipe size Insulation thickness
6.4 mm to 25.4 mm [1/4 to 1 in.] >10 mm [7/16 in.]
28.6 mm to 38.1 mm [1-1/8 to 1-1/2 in.] >15 mm [5/8 in.]
If the unit is used on the highest story of a building and under high temperature and high humidity, it is
necessary to use thicker insulation than specified in the table above
If there are customer’s specifications, please follow them
12.2. Piping size
Model
SVZ-KP•NA
12 18
Refrigerant pipe
Liquid pipe 6.35 mm [1/4]
Gas pipe 9.52 mm [3/8] 12.7 mm [1/2]
Drain Pipe O.D. 32 mm [1-1/4]
SVZ-KP12,18, 24, 30, 36NA