14.6. Humidifier
















 
 












max 30 ft.
Humidifier Control
Sequence of operation:
1. The humidistat closes CNF
2. The fan starts on high
3. CN25 provides 12VDC to turn on the Humidifier
(do not exceed 1 Watt draw per relay)
4. When the Humidistat opens, the fan continues to run for
30 seconds to clear the ductwork of moist air
5. If defrost starts during humidifier operation
CN25 de-energizes
SVZ-KP12,18, 24, 30, 36NA