- Mitsumi Electronics Welding System User Manual

PARAMETERS
97
4.2.29 Applied motor (Pr. 71)
Pr. 71 "applied motor"
Set the motor used.
Parameter
Number
Factory
Setting
Setting Range
71 0 0, 1, 2
<Setting>
Refer to the following list and set this parameter according to the motor used.
Motor
Pr. 71
Setting
Thermal Characteristics of Electronic Overcurrent Protection
Standard
Constant
Torque
0 Thermal characteristics matching a standard motor
$
1 Thermal characteristics matching the Mitsubishi constant-torque motor
$
2
Thermal characteristics matching a standard motor
5-point flexible V/F characteristics
$
For the 5.5K and 7.5K, the Pr. 0 and Pr. 12 settings are automatically changed depending on the Pr. 71
setting.
Pr. 71 0, 2 1
Pr. 0 3% 2%
Pr. 12 4% 2%
Note: 1. When "9999" is set in Pr. 19, "2" cannot be set in Pr. 71. To set "2" in Pr. 71, set the appropriate
value (other than "9999") in Pr. 19.
2. When "2" is set in Pr. 71, Pr. 100 to Pr. 109 are displayed on the parameter unit (FR-PU04). In
other settings, if any of Pr. 100 to Pr. 109 settings is changed, the new setting is not displayed in
the "Default parameter list" and "Set parameter list".
CAUTION
Set this parameter correctly according to the motor used.
Incorrect setting may cause the motor to overheat and burn.
Pr. 0 "torque boost"
Pr. 12 "DC injection brake voltage"
Pr. 19 "base frequency voltage"
Pr. 60 "intelligent mode selection"
Pr. 100 to Pr. 109
(V/F frequency/voltage)
Related parameters
4