When operating in stack mode, remove the upper (trapezoidal) front part from the Battery Module to allow the cables to pass through.
The front plate must be reinstalled to protect the cables after the installation is complete.
ATTENTION:
The DD5300 Battery Module has two terminals for connecting the power supply.
The installer must pay the utmost attention to the respective functions.
The low voltage screw terminal only supports parallel
connection with maximum voltage 60V
CAUTION> Connecting these terminals in series will
cause serious damage to the battery
DO NOT CONNECT IN SERIES
Fast Connector terminals only support series connections
up to 1000Vdc
CAUTION> Connecting these terminals in parallel will cause
serious damage to the battery
DO NOT CONNECT IN PARALLEL
REMOVE WHEN OPERATING IN
STACKABLE MODE
CABLES PASSAGE
LOW VOLTAGE
HIGH VOLTAGE