I&O Manual

DEKA DURATION DD5300
33
2.3.1 LOW VOLTAGE PARALLEL CONFIGURATION
The DIP switch must be set as follows to allow a single Battery Module to communicate with an inverter using CAN communications:
WHEN THE INVERTER HAS A CANBUS COMMUNICATION PORT, SWITCH #7 OF THE MASTER
BATTERY MUST ALWAYS BE SET TO “ON.
DIP CONFIGURATION UP TO FIFTEEN MODULES IN PARALLEL
From the 1
st
to the last module (or 15
th
) for a SINGLE CLUSTER in Low Voltage Configuration,
the DIP setting of each battery must be set as per the picture below:
For Single Cluster Parallel Configuration*
*DIP Switch settings for multiple clusters are covered in a separate section of this manual.
2.3.2 LED Visual Indication Lights
There are three sources of visual indications on the Battery Module:
POWER SWITCH ON/OFF
RUN BUTTON GREEN LED
FRONT LED BAR Multi Color
2.4 Module Activation and Shutdown
START UP PROCEDURE
The Power Switch and Run Button are located to the right of the battery terminal connections on the side of the battery
chassis. The Power Switch is a mechanical switch that switches the battery ON or OFF. The Run Button is an LED button that
is only enabled when the Power Switch is in the ON (1) position. The Run Button provides several status indications that are
described in the table below.
RUN
BUTTON
POWER
SWITCH