I&O Manual

DEKA DURATION DD5300
34
POWER ON: Turn ON the Power Switch (1 = ON 0= OFF)
A 2-second press on the Run Button will turn the Battery Module on.
During the startup procedure, the Run button will blink until the safety inspection has been completed by the BMS.
SHUTDOWN: A 5-second press and hold on the Run Button will turn the Battery Module off.
Turn OFF the Power Switch ( 1 = ON 0= OFF)
Other functions of the Run Button are explained in the relevant sections of this manual.
Attention: Read this entire manual thoroughly to understand the correct startup and shutdown procedures
for each battery configuration.
POWER SWITCH
For a complete shutdown of the Battery Module press the Run Button for 5 seconds and then set the Power Switch to the
OFF (0) position.
CAUTION: After setting the DIP switch, the Battery Module must be restarted for the DIP switch changes to take effect.
ATTENTION:
ALWAYS CONFIGURE THE DIP SWITCH SETTINGS IN ACCORDANCE WITH THIS MANUAL BEFORE
CONNECTING ANY POWER CABLES TO THE BATTERY TERMINALS B+ AND B-.
WHEN CHANGES HAVE BEEN MADE TO THE DIP SWITCH SETTINGS, THE BATTERIES MUST ALWAYS BE
RESTARTED FOR THE CHANGES TO TAKE EFFECT.
POWER CABLE CONNECTIONS MUST BE MADE IN STRICT ACCORDANCE WITH THE INSTRUCTIONS IN THIS
MANUAL. INCORRECT POWER CONNECTIONS CAN DAMAGE THE BATTERY MODULE AND CAUSE INJURIES.
WHEN THE INVERTER HAS A CANBUS COMMUNICATION PORT, SWITCH #7 OF THE MASTER BATTERY MUST
ALWAYS BE SET TO ON.”
Name
Meaning
Function or Indication Status
POWER SWITCH
On/Off Button
Switches the Battery Module on and off.
RUN BUTTON
Module Correct Operation
When the Battery Module is running normally, indicator light will
be STEADY GREEN.
LOW BATTERY
Low SOC
When the battery SoC is low (SoC<0-5%) the RUN Button will
blink in a GREEN color at 1 second intervals.
The RUN Button will stop blinking and turn STEADY GREEN when
the battery is in charging mode and the SoC reaches 10%.
FRONT LED BAR
Fault indicator light
(See Section 2.5.5)
When there is a fault with the Battery, the front LED BAR will
show a full RED LED LIGHT and the RUN BUTTON will show no
light within 10 seconds from the event.