I&O Manual

DEKA DURATION DD5300
37
STEP 2
AUTO WAKE-UP PROCESS (Pressing the RUN BUTTON )
Once all the connections have been checked, it is possible to start the Battery Module by enabling the automatic wake-up process.
Press the RUN button of the MASTER battery, the RUN BUTTON will Blink and will wake-up all the SUB batteries connected.
This process might take around 2-3 seconds per battery (Do not turn on the SUB manually as the automatic process will assign a battery ID in
sequence).
It is essential to check the startup progression and make sure that all LEDs of the RUN BUTTON are ON and showing steady GREEN lights after the
wake-up process (the entire process might take up to 30-45 seconds in case of 15 batteries).
During the startup process, all the RUN BUTTONS will blink until the last module sends the final consent to the MASTER to enable the contactors.
If during the process, one or more Battery Modules will not turn ON or if the LED does not become steady, it is mandatory to switch off the
MASTER and check all the connections between PORTS RS485B and A.
Make sure to turn ON and OFF every Battery Module after setting up the DIP switches.
Make sure all the Battery Modules remain active after the first cycle of charge and discharge.
In case of any anomaly during this process, it is necessary to shut down the entire cluster and repeat the procedure from STEP 1.
ATTENTION: All the SUB MODULES will automatically shut down after 60 seconds from the moment that the master is OFFLINE.
To completely turn off the cluster, it is compulsory to switch OFF all the POWER SWITCHES of each module.
PRESS THE RUN BUTTON 2 Sec.
TO ENABLE THE AUTO WAKE UP
ALL RUN BUTTONS MUST BE
STEADY GREEN AFTER THE START
UP COMPLETION