I&O Manual

DEKA DURATION DD5300
47
2.8 Power Connection of a Single Cluster
-Double BUS BAR-
ATTENTION: Both ends of the cluster must be connected with two output cables 50 mm2.
Cables length shall not exceed 250cm.
The suggested output cable is composed of two sets of 50 mm2 each.
ATTENTION: The terminal block pole can support a 19mm width Cable Lug.
2X 50 mm2 = 2 cables 50 mm2 connected to both poles
(Positive pole has two connection screws, Negative pole has two connection screws)
INFORMATION
COPPER BUS BAR
14 Nm (10.33 ft lb)
Terminal Block must be checked every 3 months.
1st
15
th
or Last
2X50/75mm²
2X50/75mm²
Rj45 CAN BMS
Rj45 PARALLEL COM