I&O Manual

DEKA DURATION DD5300
54
2.9.5 Master ID Set Up and Connection Diagram
Communication Diagram
It is important to follow the diagrams below to make the connections in the correct sequence.
Each cluster must have its own unique address which will be assigned by the first battery of each cluster.
All the batteries in the group except the first must have the DIP switches set to 00000000 (see picture):
Only the first batteries of each cluster must be set following the sequence from ID 00 to ID 07 to allow the HUB to activate the
related logic based on the number of modules present in each cluster (minimum 3, maximum 15), and based on the number of
actual clusters connected to each other in a Daisy Chain (minimum 2 maximum 7).
All the master batteries must be connected in Daisy Chain from the first module to the last module, connecting the CAN
PORTS CAN1A and CAN2A to the last module from the CAN PORT CAN1A for connection to the HUB PORT -CAN INPUT-
CLUSTER
The First Battery of the cluster after being set with the
ID (acting on the DIP switches) will auto assign all the
sub Module addressees.
Example:
The Master Module of the cluster ID01 will be:
Master: 1.01,
SUB 01: 1.02
SUB 03: 1.03 and so on up to the last module.
The Master Module of the cluster ID02 will be:
Master: 2.01,
SUB 01: 2.02
SUB 03: 2.03 and so on up to the last module.