I&O Manual

DEKA DURATION DD5300
55
2.9.6 Power Connection Example
Communication Diagram + Power Connection
ATTENTION:
Each cluster must be equipped with an isolator to individually disconnect the battery
tower from the parallel bus bar in accordance with UL regulations.
ATTENTION:
The circuit between the inverter and the parallel bus bar must be separated by a manual switch in
accordance with UL regulations.
Master Inverter
NEGATIVE POWER
CABLES
2X50/75mm²
POSITIVE POWER
CABLES
2X50/75mm²
GROUND CABLES
10mm²
RS485 PARALLEL
RJ45 Cable
DATA COMM
GROUND CABLES
10mm²
TWO POLES
BREAKER
PARALLEL BUS
BAR
TWO POLES BREAKER
( US/UL Market)
CAN INPUT FROM
LAST CLUSTER